| 2021-12-03 09:04:57 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21051398 |
| | 12/2/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A2.3 FBC ACCESSIBILITY CORRECTIONS: |
| | A) THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR SPACE |
| | REQUIRED FOR THE LAVATORY- SECTION 603.2.3 |
| | B) SHOW A MINIMUM 30X48-INCH CLEAR FLOOR SPACE APPROACH |
| | AT THE DRINKING FOUNTAIN- 602.2. |
| | C) SHOW THE SPOUT HEIGHT OF THE DRINKING FOUNTAIN- |
| | 602.4. |
| | D) SHOW THE REACH RANGE HEIGHT OF THE BOTTLE FILLER- |
| | SECTION 308 |
| | E) SHOW THE 40-INCH HEIGHT OF THE MIRROR FROM THE |
| | FINISHED FLOOR TO THE REFLECTIVE SURFACE- SECTION 603.3 |
| | F) SHOW THE LOCATIONS OF THE WATER CLOSET FLUSH CONTROL |
| | - SECTION 604.6. |
| | G) SHOW THE 7-INCH MINIMUM AND 9-INCH MAXIMUM |
| | CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED FROM |
| | THE FRONT OF THE WATER CLOSETS- SECTION AND FIGURE |
| | 604.7. |
| | H) IT APPEARS A PARALLEL APPROACH WILL BE USED FOR THE |
| | KITCHENETTE SINK. PLEASE SHOW A MINIMUM 30X48 INCH |
| | CLEAR FLOOR SPACE AT THE SINK- 606.2 |
| | I) SHOW THE KNEE AND TOE CLEARANCES FOR THE LAVATORIES- |
| | SECTION 606.2 & FIGURES 306.2 & 306.3. |
| | J) SHOW THE WATER CLOSET GRAB BAR MEASUREMENTS TO THE |
| | TOPS OF THE GRIPPING SURFACES- 609.4. |
| | |
| | 2) PLEASE CORRECT THE NOTE SPECIFYING PAINTED GYPSUM |
| | BOARD FOR THE WALLS SURROUNDING THE MOP SINK. IN |
| | ACCORDANCE WITH SECTION 310.3 FBC P AND 1210.2.2 FBC B- |
| | WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, |
| | URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL |
| | ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF |
| | A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. THE |
| | WPB BUILDING DEPARTMENT DOES NOT ACCEPT PAINTED GYPSUM |
| | BOARD AS A COMPLIANT MATERIAL. PLEASE PROVIDE TILE, |
| | FRP, OR OTHER SMOOTH, HARD, NON-ABSORBENT MATERIAL FOR |
| | THE WALLS. |
| | |
| | 3) P401, P601: INDICATE HOW TEMPERED WATER WILL BE |
| | DELIVERED FROM THE LAVATORIES- 419.5 FBC P. |
| | |
| | 4) P401, P601, P701: THE PLAN SHOWS NON-COMPLIANCE WITH |
| | SECTION & TABLE C404.5.1 FBC EC. A 1/2 INCH HW PIPE HAS |
| | A MAXIMUM ALLOWABLE LENGTH OF 2FT. FROM THE NEAREST HOT |
| | WATER SOURCE TO THE FIXTURE SUPPLY PIPE AT THE |
| | LAVATORIES. PLEASE PROVIDE EITHER POINT OF USE WATER |
| | HEATERS AT THE LAVATORIES OR A HOT WATER RECIRCULATION |
| | PUMP. |
| | |
| | 5) P401, P601, P801: PLEASE PROVIDE SYMBOLS TO THE |
| | LOCATIONS OF WATER HAMMER ARRESTORS AND BACKFLOW |
| | PREVENTERS- SECTIONS 604.9 & 608.3 FBC P. |
| | |
| | 6) P801: PLEASE PROVIDE THE LISTING STANDARDS FOR THE |
| | BACKFLOW PREVENTERS SHOWN IN THE SCHEDULE- TABLE 608.3 |
| | FBC P. |
| | |
| | 7) P701: SHOW THE LOCATION OF THE WATER HEATER |
| | EXPANSION TANK IN THE DETAIL- SECTION 607.3 FBC P. |
| | |
| | 8) A1.0: PLEASE SHOW THE WATER AND SEWER CAPPING |
| | LOCATIONS- SECTION 107.2.1 WPB. |
| | |
| | 9) PLEASE REVIEW THE GUIDELINES LISTED BELOW FOR |
| | BUILDING OR PARTIAL BUILDING DEMOLITION AS SOME |
| | REQUIREMENTS MAY BE APPLICABLE TO THE PROPOSED PROJECT: |
| | |
| | DEMOLITION OF A BUILDING. |
| | THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A |
| | DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303: |
| | |
| | UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC) |
| | RELEASE OF SERVICE CONFIRMATION |
| | |
| | UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS) |
| | RELEASE OF SERVICE CONFIRMATION |
| | |
| | UTILITY RELEASE - CITY OF WEST PALM BEACH WATER |
| | DEPARTMENT, REQUEST FOR METER PULL, ON THEIR FORM |
| | "DEMOLITION APPLICATION" |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | IF A WATER TRUCK IS DESIRED FOR WATERING DOWN SITE, |
| | DETAILS WILL BE REQUIRED. |
| | |
| | IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, |
| | THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM. |
| | PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR AN |
| | RPZ BACKFLOW PREVENTER DEVICE AT THE PROPERTY, AND THE |
| | INSTALLATION MUST HAVE A FINAL PASSED INSPECTION |
| | INCLUDING TESTING AND CERTIFICATION OF THE DEVICE BY |
| | THE WPB UTILITIES DEPARTMENT PRIOR TO SCHEDULING THE |
| | FINAL DEMOLITION INSPECTION. FOR FURTHER INFORMATION |
| | ABOUT THE BACKFLOW PREVENTER PLEASE CONTACT THE |
| | UTILITIES DEPT. AT 561-822-2244. |
| | FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO |
| | 561-822-2183. |
| | |
| | SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT |
| | APPLICATION TO BUILDING DIVISION); SCHEDULE A FINAL |
| | PLUMBING #703. |
| | |
| | EXTERMINATION LETTER - LETTER FROM A LICENSED PEST |
| | CONTROL COMPANY STATING THAT DEMOLITION ADDRESS HAS |
| | BEEN INSPECTED AND/OR TREATED FOR RODENTS. |
| | |
| | COMPLETE THE DEMO DEBRIS REMOVAL FORM: |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR |
| | THE FORM TO [email protected]. |
| | |
| | PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF THE |
| | STRUCTURE(S) TO BE DEMOLISHED, FBC 107. |
| | |
| | PROVIDE A STORMWATER POLLUTION PREVENTION PLAN. |
| | |
| | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE |
| | CONTRACTOR, ON LETTERHEAD, STATING THAT THE |
| | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM |
| | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH |
| | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE |
| | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS |
| | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: |
| | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE |
| | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- |
| | RENOVATION.HTML |
| | |
| | 10) PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR |
| | INSTALLATION OF THE POTABLE WATER SERVICE BACKFLOW |
| | PREVENTER. A FL. LICENSED PLUMBING CONTRACTOR SHALL |
| | OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| | BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| | AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |