Plan Review Details - Permit 21051328
Plan Review Stops For Permit 21051328
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2021-08-20 Cont ID  
Sent By cpuell Date 2021-08-20 Time 08:56 Rev Time 0.00
Received By cpuell Date 2021-08-20 Time 08:56 Sent To  
Notes
2021-08-20 08:57:141118 1/2 FLORIDA AVE AND 1120 FLOIDA AVE TO BE RETIRED

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2021-08-18 Cont ID  
Sent By cpuell Date 2021-08-18 Time 08:50 Rev Time 0.00
Received By cpuell Date 2021-08-18 Time 08:50 Sent To  
Notes
2021-08-18 08:50:56WORK TO BE DONE ON 1118 FLORIDA AVE, HALF ADDRESS STILL
 NEED TO BE READDRESSED. PLEASE HAVE THE OWNER CONTACT
 [email protected] OR CALL 561-805-6659 SO THAT THE HALF
 ADDRESS CAN BE READDRESSED.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-08-13 Cont ID  
Sent By cpuell Date 2021-08-13 Time 11:16 Rev Time 0.00
Received By cpuell Date 2021-08-13 Time 11:16 Sent To  
Notes
2021-08-13 11:16:38WHICH BUILDING IS THE WORK TO BE DONE, EAST OR WEST?
 THE WEST BUILDING HAS A HALF ADDRESS WHICH WILL NEED TO
 BE READDRESSED. PLEASE HAVE THE OWNER CONTACT
 [email protected] OR CALL 561-805-6659 TO READDRESS THE
 HALF ADDRESS.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-08-05 Cont ID  
Sent By cpuell Date 2021-08-05 Time 10:48 Rev Time 0.00
Received By cpuell Date 2021-08-05 Time 10:48 Sent To  
Notes
2021-08-05 10:49:43WHICH BUILDING IS THE WORK TO BE DONE, EAST OR WEST?
 THE WEST BUILDING HAS A HALF ADDRESS WHICH WILL NEED TO
 BE READDRESSED. PLEASE HAVE THE OWNER CONTACT
 [email protected] OR CALL 561-805-6659 TO READDRESS THE
 HALF ADDRESS.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-08-17 Cont ID  
Sent By lcrespo Date 2021-08-17 Time 09:54 Rev Time 0.00
Received By lcrespo Date 2021-08-17 Time 09:54 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-06-01 Cont ID  
Sent By lcrespo Date 2021-06-01 Time 10:43 Rev Time 0.00
Received By lcrespo Date 2021-06-01 Time 10:15 Sent To  
Notes
2021-06-01 10:45:2906/01/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION.
  
 2. THE BTU LOAD FOR THE GENERATOR IS INCORRECT. PLEASE
 SUPPLY MANUFACTURERS SPECIFICATIONS VERIFY COMPLIANCE
 WITH 2020 FBC RES. SEC. G2408.1.
  
 3. THE CITY HAS A RECORD OF AN EXISTING GAS METER;
 PLEASE PLANS INDICATE IF THIS IS A NEW METER OR TIED
 INTO EXISTING; IF SO; THE BTU LOAD OF THE EXISTING GAS
 SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE
 SYSTEM TO ENSURE THE EXISTING SYSTEM IS SIZED
 CORRECTLY. IF UNDERSIZED, THE EXISTING SYSTEM MUST BE
 REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS
 PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING
 APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE
 SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES PER THE 2020 FBC RES. SECS.
 G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC
 RES. SEC. G2413.4.1.
  
 5. PLEASE SUBMIT A COPY OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD USED IN THIS SYSTEM'S DESIGN PER THE
 2020 FBC RES. SEC. G2413.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-17 Cont ID  
Sent By lcrespo Date 2021-08-17 Time 09:54 Rev Time 0.00
Received By lcrespo Date 2021-08-13 Time 07:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-01 Cont ID  
Sent By lcrespo Date 2021-06-01 Time 10:45 Rev Time 0.00
Received By lcrespo Date 2021-05-27 Time 16:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-08-17 Cont ID  
Sent By lcrespo Date 2021-08-17 Time 09:53 Rev Time 0.00
Received By lcrespo Date 2021-08-17 Time 09:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-06-01 Cont ID  
Sent By lcrespo Date 2021-06-01 Time 10:42 Rev Time 0.00
Received By lcrespo Date 2021-06-01 Time 10:15 Sent To  
Notes
***NONE***