| 2021-06-01 10:45:29 | 06/01/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | 1. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS. SUBMIT A |
| | GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF |
| | EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE |
| | PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| | THE SECTION. |
| | |
| | 2. THE BTU LOAD FOR THE GENERATOR IS INCORRECT. PLEASE |
| | SUPPLY MANUFACTURERS SPECIFICATIONS VERIFY COMPLIANCE |
| | WITH 2020 FBC RES. SEC. G2408.1. |
| | |
| | 3. THE CITY HAS A RECORD OF AN EXISTING GAS METER; |
| | PLEASE PLANS INDICATE IF THIS IS A NEW METER OR TIED |
| | INTO EXISTING; IF SO; THE BTU LOAD OF THE EXISTING GAS |
| | SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE |
| | SYSTEM TO ENSURE THE EXISTING SYSTEM IS SIZED |
| | CORRECTLY. IF UNDERSIZED, THE EXISTING SYSTEM MUST BE |
| | REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS |
| | PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING |
| | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE |
| | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN |
| | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO |
| | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE |
| | EXISTING APPLIANCES PER THE 2020 FBC RES. SECS. |
| | G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC |
| | RES. SEC. G2413.4.1. |
| | |
| | 5. PLEASE SUBMIT A COPY OF THE SIZING TABLE USED IN THE |
| | DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| | OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| | ANOTHER STANDARD USED IN THIS SYSTEM'S DESIGN PER THE |
| | 2020 FBC RES. SEC. G2413.3. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |