Plan Review Details - Permit 21051312
Plan Review Stops For Permit 21051312
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-01 Cont ID  
Sent By jwitmer Date 2021-07-01 Time 16:14 Rev Time 0.00
Received By jwitmer Date 2021-07-01 Time 15:15 Sent To  
Notes
2021-07-01 16:13:01WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21051312
 ADD: 3220 45TH ST.
 CONT: 1ST SOURCE CONSTRUCTION INC.
 TEL: 954-638-6028
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 01ST/ 2021
 ACTION: DENIED
  
 1) THE FLOOR PLAN AND RACK STORAGE PLAN DOES NOT
 INDICATE THE AUTHOR OF THE PLAN, WHO CREATED IT. THE
 PLAN DOES NOT INDICATE THAT IT WAS EITHER AN ARCHITECT
 OR ENGINEER.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION SECTION 107.3.4.3. THE
 CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF
 PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS DRAWN.
  
 2) THE PERMIT APPLICATION STATES THE PERMIT IS FOR
 STORAGE & PALLETS. IT IS ASSUMED THE PERMIT IS FOR NEW
 HIGH- RACK STORAGE.
 NEITHER THE PERMIT APPLICATION STATE WHAT TYPE OF ITEMS
 ARE GOING TO BE STORED IN THE RACK STORAGE SYSTEM.
 MISSING INFORMATION ON THE PALLET RACK FLOOR PLAN. WHAT
 OCCUPANCY TYPE IS THIS WAREHOUSE S1 OR S2, SEE SECTIONS
 311.2 & 311.3 OF THE 2020 FBC-BUILDING CODE FOR
 CLASSIFYING OCCUPANCY.
  
 3) IS THE WAREHOUSE AREA OF THIS BUILDING FIRE
 SPRINKLERED, THE PLAN DOES NOT STATE. 107.2.1.2.
  
 4) PLEASE PROVIDE DOCUMENTATION THE DESIGN AND TESTING
 AND UTILIZATION OF STORAGE RACKS MADE OF COLD FORMED OR
 HOT ROLLED STEEL STRUCTURAL MEMBERS SHALL BE IN
 ACCORDANCE WITH RMI/ANSI MH 16.1. CODE SECTION 2209.1
 STORAGE RACKS OF THE 2020 FBC-BUILDING. ALSO SEE
 STORAGE WAREHOUSE TABLE 1607.1(31) HEAVY 250 PSF/ LIGHT
 125 PSF. 2020FBC-BUILDING.
  
 5A) THERE IS NO ENGINEERING SHOWING THE SIZE FOR THE
 ANCHORS TO HOLD THE STORAGE RACKS IN PLACE AND TO KEEP
 THEM FROM TIPPING OVER IF HIT BY A FORKLIFT. 107.2.1.2.
  
 5B) WILL THERE BE CATWALKS AND STAIRS ABOVE THE 1ST
 FLOOR WITHIN THE RACK STORAGE ASSEMBLY? 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 5C) BECAUSE OF THE HIGH RACK STORAGE ADDITIONAL EXIT
 DIRECTIONAL LIGHTS WILL BE NEEDED TO INDICATE THE
 DIRECTION OF TRAVEL TO THE NEAREST EXIT. 2020
 FBC-BUILD. SECTION 1013.1 WHERE REQUIRED.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-06-25 Cont ID  
Sent By pleduc Date 2021-06-25 Time   Rev Time 0.00
Received By pleduc Date 2021-06-25 Time 14:40 Sent To  
Notes
2021-06-25 15:03:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF 24' HIGH RACKS.
  
 THERE ARE SLSO INDICATIONS OF AN EXISTING FIRE
 SPRINKLER SYSTEM
  
 THERE ARE NO INDICATIONS THAT THESE RACKS, SHELVING AND
 THE PRODUCTS STORED ARE PROTECTED BY THE FIRE SPRINKLER
 SYSTEM.
  
 PER NFPA 13
  
 3.9.1.17 HIGH-PILED STORAGE. SOLID-PILED, PALLETIZED,
 RACK
 STORAGE, BIN BOX, AND SHELF STORAGE IN EXCESS OF 12 FT
 (3.7 M)
 IN HEIGHT.
  
 16.1.2* SPRINKLER PROTECTION CRITERIA.
 16.1.2.1 SPRINKLER PROTECTION CRITERIA FOR THE STORAGE
 OF MATERIALS
 ON RACKS SHALL BE IN ACCORDANCE WITH SECTION 16.2 FOR
 STORAGE
 UP TO 25 FT (7.6 M) AND SECTION 16.3 FOR STORAGE OVER
 25 FT
  
 PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS THAT THESE
 RACKS AND THE PRODUCTS STORED ON THEM SHALL BE
 PPROTECTED BY THE FIRE SPRINKLER SYSTM IN ACCORDANCE
 WITH THE FIRE CODE.
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-01 Cont ID  
Sent By jwitmer Date 2021-07-01 Time 16:15 Rev Time 0.00
Received By jwitmer Date 2021-06-21 Time 05:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-07-01 Cont ID  
Sent By jwitmer Date 2021-07-01 Time 16:14 Rev Time 0.00
Received By jwitmer Date 2021-07-01 Time 15:15 Sent To  
Notes
2021-07-01 16:14:381ST REVIEW
 DATE: THURS. JULY 01ST/ 2021
 ACTION: DENIED
  
 1) THE FLOOR PLAN AND RACK STORAGE PLAN DOES NOT
 INDICATE THE AUTHOR OF THE PLAN, WHO CREATED IT. THE
 PLAN DOES NOT INDICATE THAT IT WAS EITHER AN ARCHITECT
 OR ENGINEER.
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION SECTION 107.3.4.3. THE
 CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF
 PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS DRAWN.
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  