Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-07-16 Cont ID  
Sent By jwitmer Date 2021-07-16 Time 14:50 Rev Time 0.00
Received By jwitmer Date 2021-07-16 Time 14:30 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-06-29 Cont ID  
Sent By jwitmer Date 2021-06-29 Time 09:43 Rev Time 0.00
Received By jwitmer Date 2021-06-29 Time 09:15 Sent To  
Notes
2021-06-29 09:37:43TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-08-04 Cont ID  
Sent By jwitmer Date 2021-08-04 Time 11:00 Rev Time 0.00
Received By jwitmer Date 2021-08-04 Time 10:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-07-16 Cont ID  
Sent By jwitmer Date 2021-07-16 Time 15:00 Rev Time 0.00
Received By jwitmer Date 2021-07-16 Time 14:30 Sent To  
Notes
2021-07-16 14:59:08WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21051284
 ADD: 400 N. FLAGLER DR. # 504
 CONT: SERVICE RESOURCE CBC1263808
 TEL: 561-389-0065
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: JULY 16TH /2021
 ACTION: DENIED
  
 ***********4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B)*************
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
 1) 2ND REQUEST. THE FLOOR PLAN DOES NOT INDICATE WHO
 THE AUTHOR OF THE PLAN IS. CERTIFICATION BY CONTRACTOR.
 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME,
 SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE
 LICENSED IN AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) 2ND REQUEST. THE PERMIT APPLICATION INDICATES NEW
 FLOORING, WHERE AND WHAT TYPE. FLOOR INSULATION/
 UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6INCH CONCRETE SLAB / NO DROPPED
 CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) 2ND REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) 2ND REQUEST. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B.
  
 3) 2ND REQUEST. PLEASE PROVIDE A NARRATIVE TO IF WHAT
 IS HAPPENING IN THE BATHROOMS, IT APPEARS THERE MAYBE
 RELOCATION OF EITHER TUBS AND OR SHOWERS?
  
 3A) 2ND REQUEST.POST TENSION SLAB/ NEW HOLES. THE PLAN
 IS SILENT AS IF THE LOCATION OF THE EXISTING TUB DRAIN
 IS GOING TO BE REUSED IN THE SAME LOCATION. IF NOT,
 THEN THE FLOOR SLAB WILL NEED TO BE X-RAYED TO FIND THE
 POST TENSION CHORD LOCATIONS. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3B) 2ND REQUEST. THROUGH-PENETRATIONS FIRESTOP SYSTEMS
 (HORIZONTAL ASSEMBLIES). IF A NEW FLOOR PENETRATION IS
 MADE FOR THE FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW
 COMPLIANCE WITH THE 2020 FBC-B SECTION 714.5.1.2.
 THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY
 A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN
 ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL
 HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT
 NOT LESS THAN THE REQUIRED RATING OF THE FLOOR
 PENETRATED.
  
 3C) 2ND REQUEST. 2020 FBC-B 2509.2 BASE FOR TILE.
 MATERIALS USED AS A BASE FOR WALL TILE IN TUB AND
 SHOWER AREAS AND WALLS AND CEILING PANELS IN SHOWER
 AREAS SHALL BE OF MATERIALS LISTED IN TABLE 2509.2 AND
 INSTALLED IN ACCORDANCE WITH MANUFACTURER?S
 RECOMMENDATIONS. WATER RESISTANT GYPSUM BACKING BOARD
 SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET
 COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH
 GA-216 OR ASTM C840 AND THE MANUFACTURE?S
 RECOMMENDATIONS.
  
 3D) 2ND REQUEST. 2020 FBC-B SHOWERS & TUBS 1210.3.
 SHOWER COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER
 HEADS SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO
 A HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-06-29 Time 09:44 Rev Time 0.00
Received By jwitmer Date 2021-06-29 Time 09:15 Sent To  
Notes
2021-06-29 09:36:42WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21051284
 ADD: 400 N. FLAGLER DR. # 504
 CONT: SERVICE RESOURCE CBC1263808
 TEL: 561-389-0065
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JUNE 29TH /2021
 ACTION: DENIED
 1) THE FLOOR PLAN DOES NOT INDICATE WHO THE AUTHOR OF
 THE PLAN IS. CERTIFICATION BY CONTRACTOR. 107.3.4.3.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
 2) THE PERMIT APPLICATION INDICATES NEW FLOORING, WHERE
 AND WHAT TYPE. FLOOR INSULATION/ UNDERLAYMENT (FBC-B
 2020) FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING
 ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED
 FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET
 THE QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS
 FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED
 CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 2C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B.
  
 3) PLEASE PROVIDE A NARRATIVE TO IF WHAT IS HAPPENING
 IN THE BATHROOMS, IT APPEARS THERE MAYBE RELOCATION OF
 EITHER TUBS AND OR SHOWERS?
  
 3A) POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS
 IF THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO
 BE REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR
 SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION
 CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3B) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE
 FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE
 WITH THE 2020 FBC-B SECTION 714.5.1.2.
 THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY
 A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN
 ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL
 HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT
 NOT LESS THAN THE REQUIRED RATING OF THE FLOOR
 PENETRATED.
  
 3C) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS
 A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 3D) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-07-27 Cont ID  
Sent By pleduc Date 2021-07-27 Time   Rev Time 0.00
Received By pleduc Date 2021-07-27 Time 09:30 Sent To  
Notes
2021-07-27 09:37:42FIRE PROVISO:
  
 THESE AREAS MAY REQUIRE A FIRE SPRINKLER MODIFICATION
 TO ENSURE CODE COMPLIANT COVERAGE.
  
 A FIRE SPRINKLER CONTRACTOR IS REQUIRED TO REVIEW AND
 PROVIDE A LETTER OF COMPLIANCE FOR THE FIRE INSPECTION
 INSPECTION OR SUBMIT A SEPARATE PERMIT & SHOP
 DRAWINGS FOR THE WORK.
  
 FAILURE TO PROVIDE EITHER OF THE ABOVE MAY RESULT
 IN A FAILED FIRE INSPECTION UNTIL SUCH IS PROVIDED.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-07-14 Cont ID  
Sent By pleduc Date 2021-07-14 Time   Rev Time 0.00
Received By pleduc Date 2021-07-14 Time 10:34 Sent To  
Notes
2021-07-14 10:46:09FIRE PROVISO:
  
 THESE AREAS MAY REQUIRE A FIRE SPRINKLER MODIFICATION
 TO ENSURE CODE COMPLIANT COVERAGE.
  
 A FIRE SPRINKLER CONTRACTOR IS REQUIRED TO REVIEW AND
 PROVIDE A LETTER OF COMPLIANCE FOR THE FIRE INSPECTION
 INSPECTION OR SUBMIT A SEPARATE PERMIT & SHOP
 DRAWINGS FOR THE WORK.
  
 FAILURE TO PROVIDE EITHER OF THE ABOVE MAY RESULT
 IN A FAILED FIRE INSPECTION UNTIL SUCH IS PROVIDED.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-06-03 Cont ID  
Sent By pleduc Date 2021-06-03 Time   Rev Time 0.00
Received By pleduc Date 2021-06-03 Time 13:11 Sent To  
Notes
2021-06-03 13:15:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF FLOOR UNDERLAYMENT BUT NO
 SPECIFICATIONS SHEETS THAT INDICATE MEETING THE
 REQUIREMENTS PER NFPA'
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
  
 30.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7.1 OR
 10.2.7.2, AS APPLICABLE
  
 10.2.1.1 CLASSIFICATION OF INTERIOR FINISH MATERIALS
 SHALL BE IN
 ACCORDANCE WITH TESTS MADE UNDER CONDITIONS SIMULATING
 ACTUAL
 INSTALLATIONS, PROVIDED THAT THE AUTHORITY HAVING
 JURISDICTION IS
 PERMITTED TO ESTABLISH THE CLASSIFICATION OF ANY
 MATERIAL FOR WHICH
 CLASSIFICATION BY A STANDARD TEST IS NOT AVAILABLE,
 UNLESS OTHERWISE
 PROVIDED IN 10.2.1.2 OR 10.2.1.4.
 10.2.1.2 THE PROVISIONS OF 10.2.1.1 SHALL NOT APPLY TO
 MATERIALS HAVING
 A TOTAL THICKNESS OF LESS THAN 1?28 IN. (0.9 MM) THAT
 ARE APPLIED DIRECTLY
 TO THE SURFACE OF WALLS AND CEILINGS WHERE BOTH OF THE
 FOLLOWING
 CONDITIONS ARE MET:
 (1) THE WALL OR CEILING SURFACE IS A NONCOMBUSTIBLE OR
 LIMITED COMBUSTIBLE
 MATERIAL.
 (2) THE MATERIALS APPLIED MEET THE REQUIREMENTS OF
 CLASS A INTERIOR
 WALL OR CEILING FINISH WHEN TESTED IN ACCORDANCE WITH
 10.2.3,
 USING FIBER CEMENT BOARD AS THE SUBSTRATE MATERIAL.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 PLEASE REVIEW AND PROVIDE FLOORING AND UNDERLAYMENT
 SPEC SHEETS IN COMPLINACE.
  
  
 2) THERE ARE INDICATIONS OF WALL AND VANITY REPLACEMENT
 AND PAINTING.
  
 ANY WORK INVOLVING FIRE SPRINKLERS/FIRE ALARM SYSTEMS
 OR EQUIPMENT SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS.
  
 FIRE SPRINKLERS AND FIRE ALARM EQUIPMENT SHALL BE
 PROTECTED FROM PAINTING OR DAMAGE.
  
 THE FIRE SPRINKLER/FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO AND RECONSTRUCTION.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND ENSURE
 COMPLIANCE.
  
  
 3) THERE IS NO ADDRESS NOR UNIT NUMBER ON THE FLOOR
 PLAN.
  
 PLEASE PROVIDE THE ADDRESS AND UNIT NUMBER ON THE FLOOR
 PLAN SHEET.
  
  
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-08-04 Cont ID  
Sent By jwitmer Date 2021-08-04 Time 11:01 Rev Time 0.00
Received By jwitmer Date 2021-07-26 Time 11:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-07-23 Time   Rev Time 0.00
Received By lmarchan Date 2021-07-13 Time 14:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-06-29 Time 09:44 Rev Time 0.00
Received By cdecoeur Date 2021-05-28 Time 11:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-07-28 Cont ID  
Sent By ccole Date 2021-07-28 Time 16:56 Rev Time 0.00
Received By ccole Date 2021-07-28 Time 16:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-07-23 Cont ID  
Sent By ccole Date 2021-07-23 Time 11:29 Rev Time 0.00
Received By ccole Date 2021-07-23 Time 11:25 Sent To  
Notes
2021-07-23 11:32:282ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21051284
 7/23/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. THE 1ST REVIEW COMMENTS
 FROM 6/16 COPIED BELOW STILL EXIST. AFTER REVIEWING THE
 COMMENTS, IF YOU NEED ASSISTANCE PLEASE CONTACT ME
 IMMEDIATELY. PLEASE NOTE THAT A PLUMBING SUB-PERMIT
 WILL BE REQUIRED FOR REPLACEMENT OF PLUMBING FIXTURES-
 SECTIONS 105.1 & 105.2 WPB.
  
 1) THE SUBMITTED CONTRACT WORK DESCRIPTION INDICATES
 KITCHEN AND BATH WORK, AND ROUGH AND FINAL PLUMBING.
 PLEASE PROVIDE A PLUMBING PLAN DRAWN TO SCALE BY EITHER
 THE PLUMBING CONTRACTOR OF RECORD OR A FL. LICENSED
 ENGINEER. A DIGITAL SIGNATURE AND SEAL ARE REQUIRED FOR
 ENGINEERED PLANS. CONTRACTOR DRAWN PLANS REQUIRE THE
 SIGNATURE OF THE CONTRACTOR OR QUALIFIER- SECTION
 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) &
 471.025.
  
 2) THE $40,000 JOB VALUE ON THE PERMIT APPLICATION DOES
 NOT MATCH THE $135,664.60 SHOWN ON THE CONTRACT HOWEVER
 IT APPEARS THAT THERE IS A LOT OF FINISH WORK INCLUDED
 WHICH DOES NOT REQUIRE PERMITTING AND INSPECTIONS.
 PLEASE PROVIDE AN ITEMIZED SCOPE OF WORK THAT IS BEING
 INCLUDED UNDER THE $40,000 JOB COST- SECTION 109.3 WPB.
 WILL ANY ELECTRICAL WORK BE PERFORMED?
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-06-16 Cont ID  
Sent By ccole Date 2021-06-16 Time 09:24 Rev Time 0.00
Received By ccole Date 2021-06-16 Time 08:36 Sent To  
Notes
2021-06-16 09:24:451ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21051284
 6/16/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED CONTRACT WORK DESCRIPTION INDICATES
 KITCHEN AND BATH WORK, AND ROUGH AND FINAL PLUMBING.
 PLEASE PROVIDE A PLUMBING PLAN DRAWN TO SCALE BY EITHER
 THE PLUMBING CONTRACTOR OF RECORD OR A FL. LICENSED
 ENGINEER. A DIGITAL SIGNATURE AND SEAL ARE REQUIRED FOR
 ENGINEERED PLANS. CONTRACTOR DRAWN PLANS REQUIRE THE
 SIGNATURE OF THE CONTRACTOR OR QUALIFIER- SECTION
 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) &
 471.025.
  
 2) THE $40,000 JOB VALUE ON THE PERMIT APPLICATION DOES
 NOT MATCH THE $135,664.60 SHOWN ON THE CONTRACT HOWEVER
 IT APPEARS THAT THERE IS A LOT OF FINISH WORK INCLUDED
 WHICH DOES NOT REQUIRE PERMITTING AND INSPECTIONS.
 PLEASE PROVIDE AN ITEMIZED SCOPE OF WORK THAT IS BEING
 INCLUDED UNDER THE $40,000 JOB COST- SECTION 109.3 WPB.
 WILL ANY ELECTRICAL WORK BE PERFORMED?
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-08-04 Cont ID  
Sent By jwitmer Date 2021-08-04 Time 11:00 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-07-23 Cont ID  
Sent By ccole Date 2021-07-23 Time 11:41 Rev Time 0.00
Received By ccole Date 2021-07-23 Time 11:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-06-29 Cont ID  
Sent By jwitmer Date 2021-06-29 Time 09:44 Rev Time  
Received By jwitmer Date 2021-06-29 Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved