Plan Review Details - Permit 21051277
Plan Review Stops For Permit 21051277
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-09-07 Cont ID  
Sent By shill Date 2021-09-07 Time 16:49 Rev Time 0.00
Received By shill Date 2021-09-07 Time 16:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-17 Cont ID  
Sent By shill Date 2021-06-17 Time 09:09 Rev Time 0.00
Received By shill Date 2021-06-17 Time 09:09 Sent To  
Notes
2021-06-17 09:10:24****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 109, PROVIDE A COPY OF THE CONTRACT FOR THIS
 JOB.
  
 2. FS479, PROVIDE ENGINEERING. DETAIL PROVIDED LACKS
 WIND DESIGN CRITERIA, FBC B 1609.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-09-30 Cont ID  
Sent By fgiaquin Date 2021-09-30 Time 06:32 Rev Time 0.00
Received By fgiaquin Date 2021-09-29 Time 20:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-06-07 Cont ID  
Sent By fgiaquin Date 2021-06-07 Time 22:09 Rev Time 0.00
Received By fgiaquin Date 2021-06-07 Time 21:18 Sent To  
Notes
2021-06-07 22:09:47ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. DISCONNECT REQURIED WITHIN SIGHT OF SIGN PER NEC
 600.6A1
  
 2. VALUE LOW FOR AMOUNT OF WORK SHOWN. PROVIDE ACCURATE
 VALUE PER FBC 109.3
  
 3. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2021-09-30 Cont ID  
Sent By fgiaquin Date 2021-09-30 Time 06:33 Rev Time 0.00
Received By fgiaquin Date 2021-09-03 Time 13:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-06-18 Time   Rev Time 0.00
Received By cdecoeur Date 2021-05-24 Time 11:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-09-07 Cont ID  
Sent By shill Date 2021-09-07 Time 16:49 Rev Time 0.00
Received By shill Date 2021-09-07 Time 16:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-06-18 Cont ID  
Sent By ccole Date 2021-06-18 Time 10:40 Rev Time 0.00
Received By ccole Date 2021-06-18 Time 10:21 Sent To  
Notes
2021-06-18 10:45:04REQUIRED WIND LOAD ENGINEERING AND DIGITAL SIGNATURE
 AND SEAL NOT SUBMITTED FOR REVIEW.
 THE RESUBMITTED ENGINEERING SHALL BEAR THE DIGITAL
 SIGNATURE AND SEAL OF THE ENGINEER OF RECORD- FL.
 STATUTE 471.025 AND SECTION 61G15-23.005 FAC.

Review Stop Z ZONING
Rev No 2 Status P Date 2021-09-23 Cont ID  
Sent By llouie Date 2021-09-23 Time   Rev Time 0.00
Received By llouie Date 2021-09-23 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-06-01 Cont ID  
Sent By llouie Date 2021-06-01 Time   Rev Time  
Received By llouie Date 2021-06-01 Time   Sent To  
Notes
2021-06-01 17:09:53** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE ? INSUFFICIENT INFORMATION PROVIDED:
  
 1.) HOW MANY SIGNS ARE EXISTING FOR THE BUSINESS-
 PLEASE PROVIDE PHOTOGRAPHS OF ALL FACADES.
  
 2.) PLEASE PROVIDE THE DIMENSIONS OF THE BUILDING
 FACADE. THE BUILDING FA?ADE DIMENSIONS ARE NECESSARY IN
 ORDER TO CALCULATE THE MAXIMUM ALLOWABLE SIGN AREA.
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: I
  