| 2021-05-28 12:07:41 | 05/28/21 1ST POOL PLUMBING REVIEW**DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | 1. ON ELECTRICAL LOAD CALCS IT IS CALLING OUT A HEAT |
| | PUMP, PLEASE CLARIFY THE TYPE OF UNIT BEING USED PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. PLEASE PROVIDE DOCUMENTATION THAT THE POOL HEATER |
| | SHALL HAVE A MINIMUM THERMAL EFFICIENCY OF 82% PER THE |
| | 2020 FBC-ENERGY SEC. R403.10.4. |
| | |
| | 3. PLEASE INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS |
| | FOR THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 4. HEATED SWIMMING POOLS AND IN GROUND PERMANENTLY |
| | INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT |
| | COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR |
| | OTHER MEANS PROVEN TO REDUCE HEAT LOSS AND A SOLAR |
| | COVER REQUIRED FOR GAS HEATER PER 2020 FBC RE 403.10.3. |
| | |
| | 5. ON PAGE 3 IN THE TDH IT SHOWS A SLAT SYSTEM AND IT |
| | IS NOT IN THE LEGEND OR THE EQUIPMENT LAYOUT, PLEASE |
| | CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 6. PLEASE NOTE IF THIS IS A MULTI-DWELLING THE |
| | FOLLOWING COMMENT WILL APPLY; THE WATER USERS WILL BE |
| | REQUIRED TO INSTALL A BACKFLOW PREVENTION ASSEMBLY AT |
| | THE POINT OF DELIVERY. THE TYPE OF BACKFLOW ASSEMBLY |
| | REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF HAZARD |
| | POSED BY THE WATER USER. A REDUCED PRESSURE ZONE |
| | BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER |
| | THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND |
| | THEIR CONNECTION CONTROL PROGRAM. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |