Plan Review Details - Permit 21050996
Plan Review Stops For Permit 21050996
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2021-12-15 Cont ID  
Sent By cthroop Date 2021-12-15 Time 16:44 Rev Time 0.00
Received By cthroop Date 2021-12-15 Time 16:22 Sent To  
Notes
2021-12-15 16:44:06PLAN PAGE A.101 WITH A LETTER FROM AN ENGINEER FOR THE
 TWO SMART VENTS INSTALLED IN THE OHD WILL BE SUBMITTED
 AS A RES REV TO PERMIT 20090239. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-23 Cont ID  
Sent By cthroop Date 2021-06-23 Time 16:10 Rev Time 0.00
Received By cthroop Date 2021-06-22 Time 16:15 Sent To  
Notes
2021-06-23 16:20:34PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. AN 8 X 16 ENGINEERED FLOOD VENT IS PROPOSED TO BE
 INSTALLED IN THE GARAGE DOOR. SUBMIT THE FLORIDA
 PRODUCT APPROVALS FOR A GARAGE DOOR WITH THE PROPOSED
 FLOOD VENT INSTALLED.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 2. SECTION C2 D) OF ELEVATION CERTIFICATE SHOWS TOP OF
 GARAGE FLOOR AT 5.3 FT NAVD. PLAN PAGE S-100 IN MASTER
 PERMIT 20090239 SHOWS TOP OF GARAGE FLOOR AT 8.0 FT
 NAVD. RES REV 20090239 WAS SUBMITTED TO LOWER THE
 GARAGE FLOOR. THIS REVISION HAS NOT BEEN APPROVED. NO
 DRAWINGS HAVE BEEN SUBMITTED FOR REVIEW.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 NOTE IN FINAL BLDG REVIEW FOR MASTER PERMIT 20090239,
 PER EOR ON 2/01/21:
  
 REVIEWED WITH DOR, PATRICK WITH DAILY AND JANSSEN.
 BLDG. REVIEW WILL BE APPROVED WITH THE FOLLOWING
 PROVISOS:
  
 1. NEW PLAN SHEET A-1.01 WILL BE SUBMITTED WITH NEW
 FLOOD VENT CONFIGURATIONS. 2-8X16 VENTS INSTALLED ON
 WEST WALL WITH BOTTOM OF VENTS AT FINISHED FLOOR
 ELEVATION OF 8.0 FEET NAVD. NOTE STATING TOP OF VENTS
 ARE BELOW DFE AND THE 1-8X16 VENT INSTALLED IN THE OHD
 WILL REMAIN. NOTES IDENTIFYING VENTS WILL BE AMMENDED.
  
 2. SP-1.01 WILL REMAIN WITH RED LINE OF DINING AREA FF
 ELEAVATION OF 9.0 FEET CHANGED TO 9.5 FEET NAVD AND
 LETTER ADDRESSING FINISHED GRADE OF 7.6 FEET NAVD AT
 WEST ELEVATION. LETTER ADDRESSES SITE WALL PERMIT
 20070578 AND REVISION 20070578 ISSUED UNDER PREVIOUS
 ADDRESS OF 101 SANTA LUCIA DR. LETTER WILL PROVIDE TOP
 OF WALL ELEVATION TO BE 8.0 FEET NAVD.
  
 3. SITE DRAINAGE PLAN TO BE SUBMITTED FOR REVIEW.
  
 4. UNDER CONSTRUCTION EC AND FINISHED CONSTRUCTION EC
 REQUIRED. - SEE PROVISO'S UNDER MASTER PERMIT 20090239
 - NFIP REVIEW.
 CT
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-23 Cont ID  
Sent By cthroop Date 2021-06-23 Time 17:00 Rev Time 0.00
Received By cthroop Date 2021-05-20 Time 10:55 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2021-12-21 Cont ID  
Sent By cthroop Date 2021-12-21 Time 09:13 Rev Time 0.00
Received By cthroop Date 2021-12-15 Time 16:22 Sent To  
Notes
2021-12-15 16:52:51DOCUMENTS SUBMITTED WITH EC:
 1. PRODUCT APPROVAL FL5822-R7 WITH BOTH SMART VENTS
 HIGHLIGHTED.
 2. INSTALLATION INSTRUCTIONS FOR BOTH SMART VENT MODELS
 TO BE INSTALLED.
 3. ICC-ES REPORT WITH BOTH SMART VENTS HIGHLIGHTED.
 4. FORM BOARD/TIE IN SURVEY.
 5. ENG. LTR. FOR SMART VENT INSTALLATION IN OHD'S.
 PROVIDED BY AOR, PATRCIK MAYFIELD, AIA
  
 NOTICE: INCLUDE THE FOLLOWING INFORMATION IN THE
 FINISHED CONSTRUCTION EC.
 1. ENTER DATA FOR SECTION C2(E.
 2. PROVIDE THE FOLLOWING INFORMATION FOR SECTION D,
 COMMENTS:
 2A.SECTION C2(E DATA
 2B. PRODUCT APPROVAL FL NUMBER AND SMART VENT MODEL
 NUMBERS - 1540-510 AND 1540-524
 2C. TOP OF SLAB FOR PROPOSED GENERATOR
 CT
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2021-06-23 Cont ID  
Sent By cthroop Date 2021-06-23 Time 16:20 Rev Time 0.00
Received By cthroop Date 2021-06-22 Time 16:15 Sent To  
Notes
2021-06-23 16:29:58PLAN REVIEW / NFIP
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
 CITY ORDINANCE NO. 4658-16
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: UNDER CONSTRUCTION ELEVATION CERTIFICATE (EC)
  
 1.
  
 2. SECTION C2 D) OF ELEVATION CERTIFICATE SHOWS TOP OF
 GARAGE FLOOR AT 5.3 FT NAVD. PLAN PAGE S-100 IN MASTER
 PERMIT 20090239 SHOWS TOP OF GARAGE FLOOR AT 8.0 FT
 NAVD. RES REV 20090239 WAS SUBMITTED TO LOWER THE
 GARAGE FLOOR. THIS REVISION HAS NOT BEEN APPROVED. NO
 DRAWINGS HAVE BEEN SUBMITTED FOR REVIEW.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 COMMENTS FROM FINAL BLDG REVIEW UNDER MASTER PERMIT
 20090239 PER EOR:
  
 REVIEWED WITH DOR, PATRICK WITH DAILY AND JANSSEN.
 BLDG. REVIEW WILL BE APPROVED WITH THE FOLLOWING
 PROVISOS:
  
 1. NEW PLAN SHEET A-1.01 WILL BE SUBMITTED WITH NEW
 FLOOD VENT CONFIGURATIONS. 2-8X16 VENTS INSTALLED ON
 WEST WALL WITH BOTTOM OF VENTS AT FINISHED FLOOR
 ELEVATION OF 8.0 FEET NAVD. NOTE STATING TOP OF VENTS
 ARE BELOW DFE AND THE 1-8X16 VENT INSTALLED IN THE OHD
 WILL REMAIN. NOTES IDENTIFYING VENTS WILL BE AMMENDED.
  
 2. SP-1.01 WILL REMAIN WITH RED LINE OF DINING AREA FF
 ELEAVATION OF 9.0 FEET CHANGED TO 9.5 FEET NAVD AND
 LETTER ADDRESSING FINISHED GRADE OF 7.6 FEET NAVD AT
 WEST ELEVATION. LETTER ADDRESSES SITE WALL PERMIT
 20070578 AND REVISION 20070578 ISSUED UNDER PREVIOUS
 ADDRESS OF 101 SANTA LUCIA DR. LETTER WILL PROVIDE TOP
 OF WALL ELEVATION TO BE 8.0 FEET NAVD.
  
 3. SITE DRAINAGE PLAN TO BE SUBMITTED FOR REVIEW.
  
 4. ELEVATION CERTIFICATE - SEE PROVISO'S UNDER NFIP
 REVIEW.
  
 NOTICE: PLEASE CALL TO DISCUSS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-21 Cont ID  
Sent By cthroop Date 2021-12-21 Time 09:12 Rev Time 0.00
Received By cthroop Date 2021-12-21 Time 09:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-06-23 Cont ID  
Sent By cthroop Date 2021-06-23 Time 17:00 Rev Time 0.00
Received By cthroop Date 2021-06-22 Time 16:15 Sent To  
Notes
***NONE***