Plan Review Details - Permit 21050931
Plan Review Stops For Permit 21050931
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-05-24 Cont ID  
Sent By cthroop Date 2021-05-24 Time 07:05 Rev Time 0.00
Received By cthroop Date 2021-05-22 Time 08:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-05-25 Cont ID  
Sent By equinone Date 2021-05-21 Time 15:28 Rev Time 0.00
Received By equinone Date 2021-05-21 Time 15:03 Sent To  
Notes
2021-05-21 15:31:23PROVISO: FEEDER FROM EXISTING PANEL TO POOL PANEL IS
 PROTECTED BY A 2P - 80 AMPS BREAKER AND CONDUCTOR SIZE
 IS SHOWN AS 2#6 CU BUT IT MUSTBE #4 CU MINIMUM. SEE
 NOTE ON DRAWING. EQ
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-05-25 Cont ID  
Sent By lcrespo Date 2021-05-25 Time 10:31 Rev Time 0.00
Received By lcrespo Date 2021-05-25 Time 10:31 Sent To  
Notes
2021-05-25 10:31:56GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK FOR THE GAS HEATER. PROVIDE COMPLETE PLANS
 AND GAS RISER THAT REFLECTS THE ENTIRE SCOPE OF GAS
 WORK TO BE DONE PER THE WPB AMENDMENTS TO FBC SEC.
 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-11 Cont ID  
Sent By jleahy Date 2021-06-11 Time 15:41 Rev Time 0.00
Received By jleahy Date 2021-05-20 Time 10:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-05-25 Cont ID  
Sent By lcrespo Date 2021-05-25 Time 11:39 Rev Time 0.00
Received By lcrespo Date 2021-05-25 Time 10:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-05-24 Cont ID  
Sent By cthroop Date 2021-05-24 Time 07:05 Rev Time 0.00
Received By cthroop Date 2021-05-22 Time 08:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-06-09 Cont ID  
Sent By awooten Date 2021-06-09 Time   Rev Time  
Received By awooten Date 2021-06-09 Time   Sent To  
Notes
***NONE***