Plan Review Details - Permit 21050816
Plan Review Stops For Permit 21050816
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-05-18 Cont ID  
Sent By cpuell Date 2021-05-18 Time 10:18 Rev Time 0.00
Received By cpuell Date 2021-05-18 Time 10:18 Sent To  
Notes
2021-05-18 10:18:46ADDRESS UPDATED

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-06-28 Cont ID  
Sent By rmcphers Date 2021-06-28 Time 09:43 Rev Time 0.00
Received By rmcphers Date 2021-06-28 Time 09:43 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-06-16 Cont ID  
Sent By rmcphers Date 2021-06-16 Time 14:28 Rev Time 0.00
Received By rmcphers Date 2021-06-16 Time 14:28 Sent To  
Notes
2021-06-16 14:30:01PROVIDED ASBESTOS LETTER NEEDS TO BE SIGNED BY THE
 CONTRACTOR
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-07-06 Cont ID  
Sent By rmcphers Date 2021-07-06 Time 09:08 Rev Time 0.00
Received By rmcphers Date 2021-07-06 Time 09:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-28 Cont ID  
Sent By rmcphers Date 2021-06-28 Time 09:37 Rev Time 0.00
Received By rmcphers Date 2021-06-28 Time 09:37 Sent To  
Notes
2021-06-28 09:41:20OFFICE ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE SINK AND
 APPLIANCES IN THE BREAK ROOM TO COMPLY WITH FBC
 ACCESSIBILITY 305 - A804.6.3 DISHWASHER.
 CLEAR FLOOR OR GROUND SPACE SHALL BE POSITIONED
 ADJACENT TO THE DISHWASHER DOOR. THE DISHWASHER DOOR,
 IN THE OPEN POSITION, SHALL NOT OBSTRUCT THE CLEAR
 FLOOR OR GROUND SPACE FOR THE DISHWASHER OR THE SINK.
 2) DRAWING IA-108 SHOWS DOUBLE DOOS NEAR THE ELEVATORS
 WHICH ARE NOT SHOWN ON THE OTHER DRAWINGS AND WAS NOT
 SHOWN ON THIS PREVIOUS DRAWING - FLOOR PLAN ON ALL
 DRAWINGS SHOULD MATCH.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-16 Cont ID  
Sent By rmcphers Date 2021-06-16 Time 14:55 Rev Time 0.00
Received By rmcphers Date 2021-06-16 Time 13:33 Sent To  
Notes
2021-06-16 14:47:11OFFICE ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) CODE USED FOR DESIGN SHOULD BE THE CODE IN EFFECT
 (2020 FBC)
 2) PLEASE SHOW THE HOURLY FIRE RATING FOR THE DOORS AND
 THE GLAZING IN THE DOORS (800 AND 829) FROM THE OFFICES
 TO THE EGRESS CORRIDOR FBC 716 - OR SHOW HOW THE
 ELEVATOR IS PROTECTED FBC 3006.2
 3) PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE SINK AND
 APPLIANCES IN THE BREAK ROOM TO COMPLY WITH FBC
 ACCESSIBILITY 305
 4) PLEASE SHOW THE REACH RANGE FOR THE MICROWAVE OVEN
 TO COMPLY WITH FBC ACCESSIBILITY 308
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-07-06 Cont ID  
Sent By jleahy Date 2021-07-06 Time 06:28 Rev Time 0.00
Received By jleahy Date 2021-07-06 Time 06:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-06-26 Cont ID  
Sent By jleahy Date 2021-06-26 Time 11:58 Rev Time 0.00
Received By jleahy Date 2021-06-26 Time 11:23 Sent To  
Notes
2021-06-26 11:58:29ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) MEETING ROOM/ CONFERENCE ROOM SHALL MEET THE
 REQUIREMENTS OF 210.71.
  
 210.71(B)(2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM
 THAT IS AT LEAST 3.7 M (12 FT) WIDE AND THAT HAS A
 FLOOR AREA OF AT LEAST 20 M2 (215 FT2) SHALL HAVE AT
 LEAST ONE RECEPTACLE OUTLET LOCATED IN THE FLOOR AT A
 DISTANCE NOT LESS THAN 1.8 M (6 FT) FROM ANY FIXED WALL
 FOR EACH 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR
 SPACE.
  
 2) OUTLETS IN KITCHEN TO BE GFI PROTECTED WHEN WITHIN
 6" OF THE SINK. 210.8(B)(5)

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-05-27 Cont ID  
Sent By jleahy Date 2021-05-27 Time 10:27 Rev Time 0.00
Received By jleahy Date 2021-05-26 Time 08:51 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 2 Status P Date 2021-07-08 Cont ID  
Sent By jleahy Date 2021-07-08 Time 08:15 Rev Time 0.00
Received By jleahy Date 2021-07-08 Time 08:15 Sent To  
Notes
2021-07-08 08:16:20VOICE AND DATA JLEAHY

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-05-27 Cont ID  
Sent By jleahy Date 2021-05-27 Time 10:31 Rev Time 0.00
Received By jleahy Date 2021-05-27 Time 10:31 Sent To  
Notes
2021-05-27 10:32:37VOICE AND DATA JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-07-08 Cont ID  
Sent By   Date 2021-07-08 Time   Rev Time 0.00
Received By bdolan Date 2021-07-08 Time 12:03 Sent To  
Notes
2021-07-08 12:03:56THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-06-25 Cont ID  
Sent By   Date 2021-06-25 Time   Rev Time 0.00
Received By bdolan Date 2021-06-25 Time 12:13 Sent To  
Notes
2021-06-25 12:13:44THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-06-18 Cont ID  
Sent By   Date 2021-06-18 Time   Rev Time 0.00
Received By bdolan Date 2021-06-18 Time 13:51 Sent To  
Notes
2021-06-18 14:00:29THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-07-09 Cont ID  
Sent By jleahy Date 2021-07-09 Time 15:58 Rev Time 0.00
Received By jleahy Date 2021-07-01 Time 10:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-06-29 Time   Rev Time 0.00
Received By aoliver Date 2021-06-24 Time 12:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-22 Cont ID  
Sent By pvalenti Date 2021-06-22 Time 06:56 Rev Time 0.00
Received By pvalenti Date 2021-05-25 Time 12:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-07-02 Cont ID  
Sent By medwards Date 2021-07-02 Time 07:46 Rev Time 0.00
Received By medwards Date 2021-07-02 Time 07:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-06-25 Cont ID  
Sent By medwards Date 2021-06-25 Time 10:48 Rev Time 0.00
Received By medwards Date 2021-06-25 Time 08:25 Sent To  
Notes
2021-06-25 10:48:542ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21050816
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M6.1: THE OUTDOOR AIR CALCULATIONS CHART
 INDICATES IT IS BASED ON THE FLORIDA MECHANICAL CODE
 2020, TABLE 403.3.1.1 BUT NOTE 1 INDICATES CALCULATIONS
 ARE BASED ON ARCHITECTURAL PLANS AND ASHRAE 62.1-16.
 PLEASE CHOSE WHICH METHOD THAT WILL BE USED AND PROVIDE
 THE CALCULATIONS BASED ON THAT METHOD. IF ASHRAE IS
 USED IT MUST BE USED FOR THE ENTIRE MECHANICAL SYSTEM.
 IT CANNOT BE USED JUST FOR THE VENTILATION
 CALCULATIONS. FBC M 403.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-05-26 Cont ID  
Sent By medwards Date 2021-05-26 Time 07:00 Rev Time 0.00
Received By medwards Date 2021-05-26 Time 07:00 Sent To  
Notes
2021-05-26 07:00:381ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21050816
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET G-000: PLEASE PROVIDE THE CURRENT FBC 7TH
 EDITION.
  
 2) SHEET M6.1: PLEASE PROVIDE DUCT SIZES ON ALL
 DUCTWORK. FBC 107.2.1
  
 3) PLEASE SHOW THE CONDENSATION PIPING AND TERMINATION
 LOCATION FOR THE COMPUTER ROOM CRAC UNIT. FBC M 307
  
 4) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE
 OF SPACE BASED ON FBC M 403.3.1.1 AND TABLE 403.3.1.1
 AND NOT THE ARCHITECTURAL OCCUPANT LOAD.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-06-29 Cont ID  
Sent By ccole Date 2021-06-29 Time 07:41 Rev Time 0.00
Received By ccole Date 2021-06-29 Time 07:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-06-01 Cont ID  
Sent By ccole Date 2021-06-01 Time 08:00 Rev Time 0.00
Received By ccole Date 2021-06-01 Time 07:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-07-02 Cont ID  
Sent By medwards Date 2021-07-02 Time 07:47 Rev Time 0.00
Received By medwards Date 2021-07-02 Time 07:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-06-28 Cont ID  
Sent By rmcphers Date 2021-06-28 Time 09:52 Rev Time 0.00
Received By rmcphers Date 2021-06-28 Time 09:52 Sent To  
Notes
2021-06-28 09:53:37SIGNATURE REVIEW
 THE "G" AND "AI" DRAWINGS UP LOADED TO PROJECTDOX ON
 5/19/2021 DO NOT SHOW AS ELECTRONICALLY SIGNED IN ADOBE
 READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED
 TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER
 OR ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR
 - IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-06-16 Cont ID  
Sent By rmcphers Date 2021-06-16 Time 14:53 Rev Time 0.00
Received By rmcphers Date 2021-06-16 Time 14:53 Sent To  
Notes
2021-06-16 14:54:51SIGNATURE REVIEW
 THE "G" AND "AI" DRAWINGS DO NOT SHOW AS ELECTRONICALLY
 SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 BY THE ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC
 PLAN REVIEW. - OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  