| Plan Review Stops For Permit 21050816 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2021-05-18 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-05-18 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-05-18 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2021-05-18 10:18:46 | ADDRESS UPDATED |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2021-06-28 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-06-28 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-06-28 |
Time |
09:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2021-06-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-06-16 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-06-16 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2021-06-16 14:30:01 | PROVIDED ASBESTOS LETTER NEEDS TO BE SIGNED BY THE | | | CONTRACTOR | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2021-07-06 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-07-06 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-07-06 |
Time |
09:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-06-28 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-06-28 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-06-28 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2021-06-28 09:41:20 | OFFICE ALTERATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE SINK AND | | | APPLIANCES IN THE BREAK ROOM TO COMPLY WITH FBC | | | ACCESSIBILITY 305 - A804.6.3 DISHWASHER. | | | CLEAR FLOOR OR GROUND SPACE SHALL BE POSITIONED | | | ADJACENT TO THE DISHWASHER DOOR. THE DISHWASHER DOOR, | | | IN THE OPEN POSITION, SHALL NOT OBSTRUCT THE CLEAR | | | FLOOR OR GROUND SPACE FOR THE DISHWASHER OR THE SINK. | | | 2) DRAWING IA-108 SHOWS DOUBLE DOOS NEAR THE ELEVATORS | | | WHICH ARE NOT SHOWN ON THE OTHER DRAWINGS AND WAS NOT | | | SHOWN ON THIS PREVIOUS DRAWING - FLOOR PLAN ON ALL | | | DRAWINGS SHOULD MATCH. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-06-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-06-16 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-06-16 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2021-06-16 14:47:11 | OFFICE ALTERATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) CODE USED FOR DESIGN SHOULD BE THE CODE IN EFFECT | | | (2020 FBC) | | | 2) PLEASE SHOW THE HOURLY FIRE RATING FOR THE DOORS AND | | | THE GLAZING IN THE DOORS (800 AND 829) FROM THE OFFICES | | | TO THE EGRESS CORRIDOR FBC 716 - OR SHOW HOW THE | | | ELEVATOR IS PROTECTED FBC 3006.2 | | | 3) PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE SINK AND | | | APPLIANCES IN THE BREAK ROOM TO COMPLY WITH FBC | | | ACCESSIBILITY 305 | | | 4) PLEASE SHOW THE REACH RANGE FOR THE MICROWAVE OVEN | | | TO COMPLY WITH FBC ACCESSIBILITY 308 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2021-07-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-07-06 |
Time |
06:28 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-07-06 |
Time |
06:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2021-06-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-06-26 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-06-26 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2021-06-26 11:58:29 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1) MEETING ROOM/ CONFERENCE ROOM SHALL MEET THE | | | REQUIREMENTS OF 210.71. | | | | | | 210.71(B)(2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM | | | THAT IS AT LEAST 3.7 M (12 FT) WIDE AND THAT HAS A | | | FLOOR AREA OF AT LEAST 20 M2 (215 FT2) SHALL HAVE AT | | | LEAST ONE RECEPTACLE OUTLET LOCATED IN THE FLOOR AT A | | | DISTANCE NOT LESS THAN 1.8 M (6 FT) FROM ANY FIXED WALL | | | FOR EACH 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR | | | SPACE. | | | | | | 2) OUTLETS IN KITCHEN TO BE GFI PROTECTED WHEN WITHIN | | | 6" OF THE SINK. 210.8(B)(5) |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-05-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-05-27 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-05-26 |
Time |
08:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
2 |
Status |
P |
Date |
2021-07-08 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-07-08 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-07-08 |
Time |
08:15 |
Sent To |
|
|
| Notes |
| 2021-07-08 08:16:20 | VOICE AND DATA JLEAHY |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
1 |
Status |
P |
Date |
2021-05-27 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-05-27 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-05-27 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2021-05-27 10:32:37 | VOICE AND DATA JLEAHY |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2021-07-08 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-07-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
bdolan |
Date |
2021-07-08 |
Time |
12:03 |
Sent To |
|
|
| Notes |
| 2021-07-08 12:03:56 | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL | | | AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE | | | FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR | | | CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS. | | | | | | 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE | | | ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND | | | SHOP DRAWINGS BY CERTIFIED CONTRACTORS. | | | | | | 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL | | | REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION | | | PERIODS. | | | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2021-06-25 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-06-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
bdolan |
Date |
2021-06-25 |
Time |
12:13 |
Sent To |
|
|
| Notes |
| 2021-06-25 12:13:44 | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL | | | AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE | | | FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR | | | CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS. | | | | | | 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE | | | ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND | | | SHOP DRAWINGS BY CERTIFIED CONTRACTORS. | | | | | | 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL | | | REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION | | | PERIODS. | | | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-06-18 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-06-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
bdolan |
Date |
2021-06-18 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2021-06-18 14:00:29 | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL | | | AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE | | | FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR | | | CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS. | | | | | | 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE | | | ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND | | | SHOP DRAWINGS BY CERTIFIED CONTRACTORS. | | | | | | 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL | | | REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION | | | PERIODS. | | | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-07-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-07-09 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-07-01 |
Time |
10:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-06-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2021-06-24 |
Time |
12:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-06-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-06-22 |
Time |
06:56 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-05-25 |
Time |
12:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2021-07-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-07-02 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-07-02 |
Time |
07:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2021-06-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-06-25 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-06-25 |
Time |
08:25 |
Sent To |
|
|
| Notes |
| 2021-06-25 10:48:54 | 2ND REVIEW FBC-2020 MECHANICAL | | | PERMIT-21050816 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M6.1: THE OUTDOOR AIR CALCULATIONS CHART | | | INDICATES IT IS BASED ON THE FLORIDA MECHANICAL CODE | | | 2020, TABLE 403.3.1.1 BUT NOTE 1 INDICATES CALCULATIONS | | | ARE BASED ON ARCHITECTURAL PLANS AND ASHRAE 62.1-16. | | | PLEASE CHOSE WHICH METHOD THAT WILL BE USED AND PROVIDE | | | THE CALCULATIONS BASED ON THAT METHOD. IF ASHRAE IS | | | USED IT MUST BE USED FOR THE ENTIRE MECHANICAL SYSTEM. | | | IT CANNOT BE USED JUST FOR THE VENTILATION | | | CALCULATIONS. FBC M 403.2 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-05-26 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-26 |
Time |
07:00 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-26 |
Time |
07:00 |
Sent To |
|
|
| Notes |
| 2021-05-26 07:00:38 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21050816 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET G-000: PLEASE PROVIDE THE CURRENT FBC 7TH | | | EDITION. | | | | | | 2) SHEET M6.1: PLEASE PROVIDE DUCT SIZES ON ALL | | | DUCTWORK. FBC 107.2.1 | | | | | | 3) PLEASE SHOW THE CONDENSATION PIPING AND TERMINATION | | | LOCATION FOR THE COMPUTER ROOM CRAC UNIT. FBC M 307 | | | | | | 4) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE | | | OF SPACE BASED ON FBC M 403.3.1.1 AND TABLE 403.3.1.1 | | | AND NOT THE ARCHITECTURAL OCCUPANT LOAD. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2021-06-29 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-06-29 |
Time |
07:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-06-29 |
Time |
07:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2021-06-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-06-01 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-06-01 |
Time |
07:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-07-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-07-02 |
Time |
07:47 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-07-02 |
Time |
07:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-06-28 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-06-28 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-06-28 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2021-06-28 09:53:37 | SIGNATURE REVIEW | | | THE "G" AND "AI" DRAWINGS UP LOADED TO PROJECTDOX ON | | | 5/19/2021 DO NOT SHOW AS ELECTRONICALLY SIGNED IN ADOBE | | | READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED | | | TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER | | | OR ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR | | | - IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN | | | ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE | | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE | | | FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-06-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-06-16 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-06-16 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2021-06-16 14:54:51 | SIGNATURE REVIEW | | | THE "G" AND "AI" DRAWINGS DO NOT SHOW AS ELECTRONICALLY | | | SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN | | | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED | | | BY THE ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC | | | PLAN REVIEW. - OR - IF YOUR ARCHITECT OR ENGINEER DOES | | | NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN | | | DROP OFF THE ORIGINAL SIGNED AND SEALED | | | DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING | | | DIVISION AT THE CITY HALL. | | | |
|
|