| 2021-09-01 18:20:40 | RESIDENTIAL (R3) ROOFING SECOND BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21050808 |
| | |
| | 1- ITEM #1 AND #3 FROM PREVIOUS PLAN REVIEWER ARE OK. |
| | |
| | 2- ITEM #2 FROM PREVIOUS PLAN REVIEWER NEEDS TO BE |
| | ADDRESSED. |
| | A) NEW MODIFIED BITUMEN ROOF SYSTEM SUBMITTED |
| | FL1654-R23 IS OLD AND IT IS FOR THE PREVIOUS 2017 CODE. |
| | NEED CURRENT PRODUCT APPROVAL FOR 2020 CODE. |
| | |
| | B)SELECTED ASSEMBLY ON PAGE 19 OF 65 IS NOT CLEAR. |
| | SELECTED ASSEMBLY READS W-01 AND THE MAXIMUM DESIGN |
| | PRESSURE READS 12.5. CLARIFY/REVISE AS REQUIRED. AND |
| | NEED CURRENT PRODUCT APPROVAL. SEE ITEM 2(A) ABOVE. |
| | SELECT ASSEMBLY THAT MEETS THE DESIGN PRESSURES FOR ALL |
| | ROOF ZONES OR ENGINEERING WILL BE REQUIRED. |
| | |
| | 3- CLARIFY SHINGLES ROOF UNDERLAYMENT AS REQUIRED BY |
| | SEC. R905.1.1.1. FBC-RESIDENTIAL. INSTALLING TWO LAYERS |
| | OF 30# FELT? |
| | |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | ******************************************* |
| | |
| | |
| | COPY OF COMMENTS FROM PREVIOUS PLANS EXAMINER. |
| | |
| | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1. CITY OF WEST PALM BEACH IS NOT |
| | LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 128. |
| | 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL2533-R25 SELECTED SYSTEM NO. W-103 DO NOT |
| | MEET THE EXPOSURE CATEGORY C; ZONE 3 MINIMUM DESIGN |
| | PRESSURE REQUIREMENT OF -108.17. PLEASE SELECT SYSTEM |
| | NO. THAT MEETS OR EXCEEDS REQUIREMENTS OR PROVIDE |
| | SIGNED AND SEALED ENGINEERED NAILING CALCULATION FOR |
| | ZONE 3. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE |
| | CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN |
| | PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | 3. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED RIDGE VENT SYSTEM TO |
| | BE USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| | INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| | AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| | APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | |
| | |
| | |
| | |
| | |
| | |