| 2021-06-10 16:57:06 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1.PLUMBING NOTES REFER TO 2017 FBC. PER WPB FBC |
| | 107.2.1, ALL FLORIDA BUILDING CODE REFERENCES SHALL BE |
| | 2020, 7TH EDITION. |
| | |
| | 2.PROVIDE SCHEDULE; MANUFACTURER, MODEL #, CAPACITY |
| | (GPM FOR TANKLESS), ELECTRICAL OR GAS CHARACTERISTICS. |
| | SHOW THAT IT IS RATED FOR OUTDOOR USE. IF GAS, A GAS |
| | PERMIT WILL BE REQUIRED AND PLANS SUBMITTED. |
| | |
| | 3.PER WPB FBC 107.2.1, PROVIDE DETAIL OF TANKLESS WATER |
| | HEATER SHOWING ALL REQUIRED CONNECTIONS, SAFETY DEVICES |
| | AND VALVES. |
| | |
| | 4.WET BAR; SINK; THE VENT SHALL CONNECT ABOVE THE TRAP |
| | WEIR OF THE FIXTURE AND RISE VERTICALLY TO 6 INCHES |
| | ABOVE THE FLOOD LEVEL RIM OF THE FIXTURE BEFORE |
| | OFFSETTING HORIZONTALLY. FBC RES P3104.4, P3105.1 AND |
| | P3201.5. ADDITIONALLY, THE VENT AS SHOWN IS 3 INCH |
| | CONNECTED TO 2 INCH. CLARIFY. |
| | |
| | 5. PER WPB FBC 107.2.1, CORRECTLY IDENTIFY THE SINK |
| | (WET BAR) ON THE RISER DIAGRAM. IT IS NOT A LAVATORY. |
| | |
| | 6.RE: 3 INCH VENT AT INFILLED WINDOW AT BATHROOM #2; |
| | THIS APPEARS TO BE IN A BEARING BLOCK WALL. PER WPB FBC |
| | 107.2.1, PROVIDE DETAIL SHOWING HOW VENT SHALL |
| | PENETRATE EXISTING BEAM(S) OR OFFSET AROUND SAID |
| | BEAM(S). |
| | |
| | NOTE; REVIEW VENT SIZES. FBC RES DOES NOT REQUIRE 3 |
| | INCH VENTS ON THIS PROJECT AND THEY MAY STRUCTURALLY |
| | IMPACT THE WALLS/PARTITIONS AND BEAMS. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | PLEASE CALL 561-246-0882 WITH ANY QUESTIONS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21050800 520 HAMPTON RD |