Plan Review Details - Permit 21050786
Plan Review Stops For Permit 21050786
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-07-01 Cont ID  
Sent By rmcphers Date 2021-07-01 Time 14:54 Rev Time 0.00
Received By rmcphers Date 2021-07-01 Time 14:54 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-06-16 Cont ID  
Sent By rmcphers Date 2021-06-16 Time 12:07 Rev Time 0.00
Received By rmcphers Date 2021-06-16 Time 12:07 Sent To  
Notes
2021-06-16 12:08:09PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-07-01 Cont ID  
Sent By rmcphers Date 2021-07-01 Time 14:54 Rev Time 0.00
Received By rmcphers Date 2021-07-01 Time 14:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-16 Cont ID  
Sent By rmcphers Date 2021-06-16 Time 12:07 Rev Time 0.00
Received By rmcphers Date 2021-06-16 Time 09:51 Sent To  
Notes
2021-06-16 11:29:09BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) ON DRAWING A-4.1 - ACCESSIBLE FITTING ROOM - PLEASE
 SHOW THE BENCH SEAT TRANSFER CLEAR FLOOR SPACE BESIDE
 THE BENCH PER FBC ACCESSIBILITY 903.2
 2) ON DRAWING A-4.1 - ACCESSIBLE FITTING ROOM - PLEASE
 SHOW THE DOOR CLEAR FLOOR SPACE TO EXIT THE ACCESSIBLE
 FITTING ROOM FBC ACCESSIBILITY 404.2.4 (18" BESIDE THE
 DOOR LATCH SIDE)
 3) ON DRAWING A-4.1 - ACCESSIBLE FITTING ROOM - PLEASE
 SHOW THE CLEAR FLOOR SPACE PER FBC ACCESSIBILITY 803.3
 DOOR SWING. DOORS SHALL NOT SWING INTO THE ROOM UNLESS
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305.3 IS
 PROVIDED BEYOND THE ARC OF THE DOOR SWING.
 4) PLEASE SHOW THE HOURLY FIRE RATING FOR THE EXISTING
 TENNANT SEPARATION WALLS FBC 508
 5) BUILDING OCCUPANT LOAD AND THE EGRESS WIDTH DO NOT
 MATCH PER CALCULATIONS (198 X .02) - SHOWN ON DRAWING A
 0.1 FBC 1005.3.2
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-06-29 Cont ID  
Sent By jleahy Date 2021-06-29 Time 12:19 Rev Time 0.00
Received By jleahy Date 2021-06-29 Time 07:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-06-14 Cont ID  
Sent By jleahy Date 2021-06-14 Time 15:11 Rev Time 0.00
Received By jleahy Date 2021-06-14 Time 14:51 Sent To  
Notes
2021-06-14 15:13:31ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PANEL "L" NOT SHOWN ON RISER.
  
 2) ALL MATERIALS SUPPLIED BY THE OWNER SHALL BE
 INCLUDED IN THE VALUE OF THE PERMIT. LIGHT FIXTURES,
 LIGHTING CONTROL, PANELBOARDS, TRANSFORMER, ECT, ECT,
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2021-06-24 Time   Rev Time 0.00
Received By bdolan Date 2021-06-24 Time 11:28 Sent To  
Notes
2021-06-24 11:29:45THIS PLAN WAS REVIEWED AND APPROVED BY LT. BRIAN DOLAN,
 DIVISION OF FIRE PREVENTION
  
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-05-21 Time   Rev Time 0.00
Received By bdolan Date 2021-05-21 Time 12:23 Sent To  
Notes
2021-05-21 12:31:42THIS PLAN HAS BEEN REVIEWED BY THE DIVISION OF FIRE
 PREVENTION WITH THE FOLLOWING COMMENTS:
  
 PLAN SET DOES NOT INCLUDE A LIFE SAFETY PLAN..
  
 PLEASE INCLUDE AND RESUBMIT.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-14 Cont ID  
Sent By lcrespo Date 2021-07-14 Time 11:57 Rev Time 0.00
Received By lmarchan Date 2021-06-23 Time 16:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-16 Cont ID  
Sent By rmcphers Date 2021-06-16 Time 12:09 Rev Time 0.00
Received By rmcphers Date 2021-05-18 Time 11:34 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-06-16 Cont ID  
Sent By rmcphers Date 2021-06-16 Time 12:08 Rev Time 0.00
Received By rmcphers Date 2021-06-16 Time 12:08 Sent To  
Notes
2021-06-16 12:09:14EXISTING OCCUPANCY CLASSIFICATION BUILDOUT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-06-28 Cont ID  
Sent By medwards Date 2021-06-28 Time 11:23 Rev Time 0.00
Received By medwards Date 2021-06-28 Time 10:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-06-14 Cont ID  
Sent By medwards Date 2021-06-14 Time 07:50 Rev Time 0.00
Received By medwards Date 2021-06-14 Time 07:50 Sent To  
Notes
2021-06-14 07:52:04PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR ALL AREAS
 OF THIS TENANT SPACE BASED ON FBC M 403.3.1.1 AND TABLE
 403.3.1.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-07-02 Cont ID  
Sent By lcrespo Date 2021-07-02 Time 16:01 Rev Time 0.00
Received By lcrespo Date 2021-07-02 Time 10:35 Sent To  
Notes
2021-07-02 16:02:4007/02/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-06-12 Cont ID  
Sent By abelisle Date 2021-06-12 Time 09:17 Rev Time 0.00
Received By abelisle Date 2021-06-12 Time 08:30 Sent To  
Notes
2021-06-12 09:37:541ST REVIEW FBC-2020 PLUMBING
 PERMIT-21050786
 6/12/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1- THE CORRECT ADDRESS OF THE PROJECT MUST BE ON THE
 PLANS. SUBMITTED PERMIT APPLICATION STATES UNIT B19,
 THE PRESENT LOCATION OF THE BUSINESS IS B07? PLAN PAGE
 A 0.1 STATES UNIT B11. PLEASE CLARIFY THIS ADDRESS FOR
 THE PROPER UNIT NUMBER. WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 2- THERE IS NO PLUMBING PLAN SUBMITTED WITH THIS SET OF
 PLANS. PLAN PAGE A 0.1 INDICATES THERE IS GOING TO BE A
 WATER SUPPLY AND FLOOR DRAIN INSTALLED UNDER THE
 RESPOSIBILITIES OF THE GENERAL CONTRACTOR FOR THE
 BOILER AND STEAM PRESS. PLEASE CLARIFY. WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 3- THE TOILET ROOM ACCESSORIES INDICATED ON PLAN PAGE
 A-0.5 INDICATE THERE WILL BE SOME MODIFICATIONS TO THE
 EXISTING MENS AND WOMENS RESTROOMS. PLEASE PROVIDE AN
 ELEVATION WITH MEASUREMENTS THAT MEET FBC ACC. FOR
 THESE ITEMS.WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-28 Cont ID  
Sent By medwards Date 2021-06-28 Time 12:50 Rev Time 0.00
Received By medwards Date 2021-06-28 Time 12:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-06-14 Cont ID  
Sent By medwards Date 2021-06-14 Time 07:58 Rev Time 0.00
Received By medwards Date 2021-06-14 Time 07:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-07-14 Cont ID  
Sent By eschneid Date 2021-07-14 Time 11:47 Rev Time 0.25
Received By eschneid Date 2021-07-14 Time 10:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-06-03 Cont ID  
Sent By eschneid Date 2021-06-03 Time 15:23 Rev Time 0.25
Received By eschneid Date 2021-06-03 Time 15:08 Sent To  
Notes
2021-06-03 15:24:18FAILED
  
 1) THE LANDLORD APPROVAL STAMP IS REQUIRED ON THE
 PLANS. ALTERNATIVELY, A LETTER FROM THE LANDLORD
 LISTING THE APPROVED PLANS IS ACCEPTABLE.
  
 2) SHEET A-1.1 INCLUDES A NOTE THAT MENTIONS GRAPHIC
 WINDOW FILM. PLEASE PROVIDE DETAILS ON WHAT THIS
 ENTAILS. PLEASE NOTE THAT THE PALM BEACH OUTLETS DESIGN
 GUIDELINES LIMIT THE AMOUNT OF PERMANENT WINDOW SIGNAGE
 TO 10 PERCENT OF THE GLAZED AREA OF THE STOREFRONT. THE
 SIGNAGE SHALL NOT OBSTRUCT VIEWS FROM THE STREET INTO
 THE STOREFRONT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  