Plan Review Details - Permit 21050671
Plan Review Stops For Permit 21050671
Review Stop AD ADDRESSING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2021-08-09 Time   Rev Time 0.00
Received By cpuell Date 2021-08-09 Time 11:39 Sent To  
Notes
2021-08-09 11:41:05WORK IS BEING DONE ON 3065 S DIXIE HWY, UPDATED PERMIT.
 SPOKE TO APPLICANT WHO STATED THAT WHEN THE CONTRACTOR
 DOES A CHANGE OF CONTRACTOR THAT THE CORRECT ADDRESS
 WILL BE REFLECTED ON THE APPLICATION FORM.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-05-13 Cont ID  
Sent By cpuell Date 2021-05-13 Time 17:09 Rev Time 0.00
Received By cpuell Date 2021-05-13 Time 17:09 Sent To  
Notes
2021-05-13 17:12:12THIS PROJECT HAS BEEN ADDRESSED SPACE 8 IS NOT THE
 ADDRESS FOR THIS PROJECT. PLEASE PROVIDE A SITE PLAN
 SHOWING THE LOCATION OF THE UNIT, ESPECIALLY THE
 ENTRANCE OF THE UNIT IN RELATIONSHIP TO THE SITE PLAN.
 PLEASE EMAIL TO [email protected]

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-08-20 Cont ID  
Sent By pvalenti Date 2021-08-20 Time 11:02 Rev Time 0.00
Received By pvalenti Date 2021-08-20 Time 11:02 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-08-19 Cont ID  
Sent By pvalenti Date 2021-08-19 Time 15:57 Rev Time 0.00
Received By pvalenti Date 2021-08-19 Time 07:44 Sent To  
Notes
2021-08-19 15:58:54****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-06-15 Cont ID  
Sent By jwitmer Date 2021-06-15 Time 16:00 Rev Time 0.00
Received By jwitmer Date 2021-06-15 Time 14:09 Sent To  
Notes
2021-06-15 16:03:42COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-10-21 Cont ID  
Sent By pvalenti Date 2021-10-21 Time 16:28 Rev Time 0.00
Received By pvalenti Date 2021-10-21 Time 16:28 Sent To  
Notes
2021-10-21 16:29:46PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW APPROVED.
  
 THE APPLICANT SUBMITTED THE SPECIFICATIONS FOR THE
 LOUVER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-10-06 Cont ID  
Sent By pvalenti Date 2021-10-06 Time 15:22 Rev Time 0.00
Received By pvalenti Date 2021-10-06 Time 08:28 Sent To  
Notes
2021-10-06 15:27:48PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE PROVIDE THE PRODUCT APPROVAL FOR
 THE 16"X16"LOUVER AT THE LOWER SECTION OF WALL FOR
 ROASTERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-24 Cont ID  
Sent By pvalenti Date 2021-08-24 Time 16:07 Rev Time 0.00
Received By pvalenti Date 2021-08-19 Time 07:43 Sent To  
Notes
2021-08-24 16:10:15****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 2ND BUILDING REVIEW DENIED:
  
 1)FBC B 107.2.1, DISCREPANCY IN PLAN SHEETS C-1 & 1.3A
 STILL EXIST. PLEASE CORRECT THE OCCUPANCY NUMBERS
 TO MATCH. SHEET C-1 INDICATES 78 TOTAL NUMBER OF SEATS
 AND SHEET 1.3A INDICATES 72 MINIMUM OCCUPANT
 LOAD.
 2A) OK
 2B) OK
 2C) OK
 2D) OK
 3) OK
 4) OK
 5) OK
 6) FAILED, FBC B 1010.1.2.1, (PLAN SHEETS 1.0A & 1.3A)
 THE DOOR STILL SHOWS SWINGING INWARD. THIS DOOR
 MUST SWING OUTWARD AS IT IS AN EGRESS DOOR (PART OF A
 MEANS OF EGRESS).
 7) FAILED, FBC B 1028.4.2, MORE INFORMATION IS REQUIRED
 TO SHOW THE FIRE RATING HAS BEEN MET FOR THE WALL
 AND WALL OPENINGS. ALSO, THE NEW CHASE DETAIL FOR THE
 MECHANICAL (ROASTER) EXHAUST UNDER THE SOFFIT DOES
 NOT APPEAR TO FIT THE SIDE OF THE BUILDING. THIS
 BUILDING APPEARS TO BE THREE STORIES AT THIS LOCATION.
 PLEASE
 VERIFY.
 8) OK
 9) OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-15 Cont ID  
Sent By jwitmer Date 2021-06-15 Time 16:00 Rev Time 0.00
Received By jwitmer Date 2021-06-15 Time 14:10 Sent To  
Notes
2021-06-15 16:02:02WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21050671
 ADD: 3111 S. DIXIE HWY.
 CONT: TBD / TO BE DETERMINED
 TEL: ??
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JUNE 15TH/ 2021
 ACTION: DENIED
  
 1) DISCREPANCY IN PLANS. THE COVERSHEET C1 STATES THERE
 IS 129 SEATS OR OCCUPANTS NOT COUNTING THE KITCHEN AREA
 OR THE QUEUING AREA THAT WOULD ADD AN ADDITIONAL 20
 OCCUPANTS OR A TOTAL OF 92 OCCUPANTS. NEITHER SHEET
 SHOWS ANY SEASONAL SEATING. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2) SHEET 1.3A INDICATES 72 SEATS AND ONLY SHOW 1
 ACCESSIBLE SEAT. THE LIFE SAFETY SHEET DOES NOT SHOW
 COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY CODE.
 2A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT (72 X
 0.05 = 3.6 OR 4 ACCESSIBLE SEATS REQUIRED) OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 2B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 2C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 2D) 902.1. DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORKSTATIONS.
  
 2D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) THE SHEET 1.3A THE LIFE SAFETY PLAN DOES SHOW 2
 MEANS OF EGRESS, BUT THE PLANS DO NOT SHOW IF BOTH
 EXITS ARE ACCESSIBLE. 2020 FBC-ACCESSIBILITY CODE
 SECTION 207.1 MEANS OF EGRESS SHALL COMPLY WITH SECTION
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE (2000
 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF THE
 INTERNATIONAL BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 4) ON BOTH THE SHEETS 1.0A & 1.3A THE LIFE SAFETY SHEET
 IT APPEARS THE FRONT ENTRY DOOR IS DRAWN AS BOTH A
 LEFT-HAND AND ALSO A RIGHT-HAND OUTSWING DOOR.
 ADDITIONAL INFORMATION IS REQUIRED. 107.2.1.2.
  
 5) IN BOTH PLANS SHEET 1.0A AND 1.3A THE LIFE SAFETY
 PLAN THERE IS AN ENCLOSED EXIT STAIRWAY WITH AN INSWING
 DOOR NOT IN THE DIRECTION OF TRAVEL. 2020 FBC-B
 1010.1.2.1 DOOR SWING.
  
 6) IN BOTH PLANS SHEET 1.0A AND 1.3A THE LIFE SAFETY
 PLAN THERE IS AN ENCLOSED EXIT STAIRWAY WITH AN INSWING
 DOOR NOT IN THE DIRECTION OF TRAVEL. BEYOND THAT FROM
 THE NEW CAF? THERE IS ANOTHER EXIT DOOR TO WHAT APPEARS
 TO BE AN EXIT PASSAGEWAY. JUST TO THE LEFT OF THE CAF?
 EXIT DOOR THERE IS WHAT APPEARS TO BE 2 WINDOWS, THE
 PLAN DOES NOT SHOW THIS AREA AS A BLOCK WALL. THE DOOR
 SCHEDULE INDICATES EXISTING STEEL DOOR. SEE TABLE 716.5
 FOR WINDOW LISTINGS IN EXIT PASSAGEWAYS.
  
 7) SHEETS 1.0A, 1.3A THE LIFE SAFETY PLAN, 1.1A THE
 EQUIPMENT PLAN AT THE EQUIPMENT LABELED # 14 ROASTER
 THERE ARE 2 CIRCLES ON THE EXTERIOR OF THE WALL. SHEET
 4.1M SHOWS AN INTAKE LOUVER AND AN EXHAUST SINGLE WALL
 FLUE. IT APPEARS THAT YOU HAVE LEFT THE EXIT AT THE
 STAIRWELL AND ARE IN WHAT APPEARS TO BE AN EGRESS
 COURT. THE EGRESS COURT WILL NEED TO SHOW COMPLIANCE
 WITH 1028.4.2 CONSTRUCTION AND CAPACITY FOR BOTH THE
 NEW EXTERIOR METAL FRAMING , FRT. EXT. PLYWOOD AND
 PAPER LATH TO MATCH BUILDING, PROVIDE THE THICKNESS
 REQUIRED FOR 1 HOUR PROTECTION. PLEASE ALSO SHOW
 PROTECTION FOR THE 12 X12 INTAKE LOUVER. PROVIDE A
 STRUCTURAL DETAIL OF HOW THIS WALL SECTION IS TO BE
 BUILT, WHAT IS THE WALL FRAMING GOING TO ANCHOR TOO.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 8) SHEET 1.4A DETAILS. SECTION 1-1.4A SHOWS AN EXISTING
 PVC SANITARY PIPE. PLEASE SHOW ON EITHER THE EQUIPMENT
 PLAN OR FLOOR PLAN WHERE THIS PIPE IS LOCATED. PLEASE
 ALSO PROVIDE WITH WHAT MATERIALS THIS CHASE IS GOING TO
 BE BUILT, PROVIDE TYPE OF FRAMING. SIZE AND SPACING OF
 FRAMING, HOW IT WILL BE ANCHORED TO THE DECK ABOVE,
 TYPE OF MATERIAL TO CREATE THE CHASE, THICKNESS AND IF
 THE CHASE IS TO BE FIRE RATED OR NOT. 107.2.1.2.
 456.3.1.
  
 9) SHEET 1.4A WATER CLOSET DETAIL B SHOWS THE TOILET
 PAPER DISPENSER DIRECTLY IN FRONT OF THE TOILET. TOILET
 PAPER DISPENSERS. 2020 FBC-ACCESS. CODE 604.7. THE
 TOILET PAPER DISPENSER SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM TO 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-06-23 Cont ID  
Sent By jleahy Date 2021-06-23 Time 15:14 Rev Time 0.00
Received By jleahy Date 2021-06-23 Time 15:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-10 Cont ID  
Sent By cwalker Date 2021-08-10 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-06-01 Cont ID  
Sent By cwalker Date 2021-06-01 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-10-22 Cont ID  
Sent By ccole Date 2021-10-22 Time 08:58 Rev Time 0.00
Received By ccole Date 2021-10-22 Time 08:58 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-10-19 Cont ID  
Sent By ccole Date 2021-10-19 Time 11:20 Rev Time 0.00
Received By ccole Date 2021-10-18 Time 12:12 Sent To  
Notes
2021-10-19 11:21:373RD REVIEW FBC-2020 FUEL GAS
 PERMIT- 21050671
 10/19/21
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 3.1P: REFER TO PREVIOUSLY FAILED COMMENT #2
 FROM THE 1ST AND 2ND REVIEW PRINTED BELOW. PLEASE NOTE
 THAT THE LETTER FROM THE PRIMO ROASTING CEO DOES NOT
 PROVIDE INFORMATION OR EVIDENCE OF ANZI STANDARD
 APPROVAL FOR THE GAS BURNER AND ASSOCIATED COMPONENTS-
 SECTION 623.1 FBC FG.
 FAILED. 3.0P & 3.1P: SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE NEW COFFEE ROASTER- SECTION
 305.1 FBC FG. PLEASE HIGHLIGHT OR MARKUP THE SPEC TO
 SHOW THE LISTING STANDARD, BTU LOAD, AND GAS INPUT
 PRESSURE. THE SUBMITTED ROASTER SPECS DO NOT SHOW THE
 LISTING STANDARD, GAS INPUT PRESSURE, OR CATEGORY OF
 THE CATEGORY OF THE APPLIANCE. PLEASE REFER TO SECTIONS
 305.1 AND 623.1 FBC FG FOR LISTING REQUIREMENTS, AND
 SECTION 410.2- INPUT PRESSURE IS REQUIRED FOR
 DETERMINING THE REQUIRED SUPPLY PIPE PRESSURE AND
 REGULATOR SELECTION. ALSO MISSING WITH THE SUBMITTAL
 ARE MANUFACTURER?S INSTALLATION GUIDELINES FOR
 SUPPLYING COMBUSTION AIR, MAKEUP AIR, AND PROPER
 VENTING OF THE EQUIPMENT. THE CATEGORY OF THE APPLIANCE
 NEEDS TO BE ESTABLISHED IN ORDER FOR A COMPLETE REVIEW
 OF THE EXHAUST/VENT SYSTEM. PLEASE INDICATE CATEGORY I,
 II, III, OR IV PER SECTIONS 202, 503.6.9.1, & &
 503.6.9.3. FBC FG.
  
 2) SHEET 3.1P: REFER TO PREVIOUSLY FAILED COMMENT 3
 FROM THE 1ST AND 2ND REVIEWS PRINTED BELOW. THE REVISED
 PLAN SHOWS THE COMBUSTION AIR OPENING IN THE WRONG
 LOCATION. THE OPENING SHALL COMMENCE WITHIN 12 INCHES
 OF THE TOP OF THE ENCLOSURE- SECTION 304.6.2 FBC FG.
 FAILED. 3.0P & 3.1P: PROVIDE COMBUSTION AIR
 CALCULATIONS FOR THE COFFEE ROASTER AND INDICATE HOW
 THE AIR IS BEING SUPPLIED- SECTION 304.1 FBC FG. THE
 RESPONSE NARRATIVE INDICATES INDOOR COMBUSTION AIR IS
 TO BE USED, HOWEVER THE PLAN SHOWS A CALCULATION FOR
 MECHANICALLY SUPPLIED AIR PER 304.9 USING AN OPENING TO
 THE OUTDOORS: A) MECHANICAL AIR MUST BE SUPPLIED BY AN
 AIR SUPPLY SYSTEM- MEANING CONDUCTED FROM A SUPPLY
 UNIT. COMBUSTION AIR THROUGH ONE WALL OPENING SHALL
 COMPLY WITH 304.6.2- 1 SQ. INCH PER 3000 BTUH. SEE
 COMMENT #3 FOR COMBUSTION AIR/VENTING COMPLIANCES.
  
 3) SHEETS 4.0M & 4.1M: REFER TO PREVIOUS REVIEW COMMENT
 #4 PRINTED BELOW.
 FAILED. 3.0P & 3.1P: THE TYPE AND SIZE OF
 EXHAUST/VENTING SYSTEM IS DEPENDENT ON THE CATEGORY OF
 THE APPLIANCE. PLEASE INDICATE CATEGORY I, II, III, OR
 IV PER SECTIONS 202, 503.6.9.1 & 503.6.9.3.FBC FG.
 A) CLARIFY HOW THE SYSTEM WAS DESIGNED- SUBMIT COFFEE
 ROASTERS VENTING/MAKEUP-COMBUSTION AIR SYSTEM
 SPECIFICATIONS AND GUIDELINES- 305.1, 503.3, 503.3.1 &
 623.1.
 B) PROVIDE EXHAUST/VENT DUCTS SIZING CALCULATIONS AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 GUIDELINES FOR THE VENT SYSTEM.
 C) PROVIDE A DIMENSIONED EXHAUST/VENT DIAGRAM SHOWING
 CONNECTOR AND TOTAL RUN LENGTH OF THE SYSTEM CONSISTENT
 WITH THE MANUFACTURER'S SPECIFICATIONS AND/OR
 ENGINEERED CALCULATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-08-26 Cont ID  
Sent By ccole Date 2021-08-26 Time 15:08 Rev Time 0.00
Received By ccole Date 2021-08-26 Time 08:31 Sent To  
Notes
2021-08-26 15:08:202ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21050671
 8/26/21
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
  
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW LISTED BELOW WITH ADDITIONAL NOTES IN CAPS.
  
 2) FAILED. 3.0P & 3.1P: SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE NEW COFFEE ROASTER- SECTION
 305.1 FBC FG. PLEASE HIGHLIGHT OR MARKUP THE SPEC TO
 SHOW THE LISTING STANDARD, BTU LOAD, AND GAS INPUT
 PRESSURE. THE SUBMITTED ROASTER SPECS DO NOT SHOW THE
 LISTING STANDARD, GAS INPUT PRESSURE, OR CATEGORY OF
 THE CATEGORY OF THE APPLIANCE. PLEASE REFER TO SECTIONS
 305.1 AND 623.1 FBC FG FOR LISTING REQUIREMENTS, AND
 SECTION 410.2- INPUT PRESSURE IS REQUIRED FOR
 DETERMINING THE REQUIRED SUPPLY PIPE PRESSURE AND
 REGULATOR SELECTION. ALSO MISSING WITH THE SUBMITTAL
 ARE MANUFACTURER?S INSTALLATION GUIDELINES FOR
 SUPPLYING COMBUSTION AIR, MAKEUP AIR, AND PROPER
 VENTING OF THE EQUIPMENT. PLEASE NOTE THE ROASTER SPECS
 INDICATE A BTUH LOAD OF 144,000 NOT 140,000 AS
 INDICATED ON THE RISER. THE CATEGORY OF THE APPLIANCE
 NEEDS TO BE ESTABLISHED IN ORDER FOR A COMPLETE REVIEW
 OF THE EXHAUST/VENT SYSTEM. PLEASE INDICATE CATEGORY I,
 II, III, OR IV PER SECTIONS 202, 503.6.9.1, & &
 503.6.9.3. FBC FG.
  
 3) FAILED. 3.0P & 3.1P: PROVIDE COMBUSTION AIR
 CALCULATIONS FOR THE COFFEE ROASTER AND INDICATE HOW
 THE AIR IS BEING SUPPLIED- SECTION 304.1 FBC FG. THE
 RESPONSE NARRATIVE INDICATES INDOOR COMBUSTION AIR IS
 TO BE USED, HOWEVER THE PLAN SHOWS A CALCULATION FOR
 MECHANICALLY SUPPLIED AIR PER 304.9 USING AN OPENING TO
 THE OUTDOORS: A) MECHANICAL AIR MUST BE SUPPLIED BY AN
 AIR SUPPLY SYSTEM- MEANING CONDUCTED FROM A SUPPLY
 UNIT. COMBUSTION AIR THROUGH ONE WALL OPENING SHALL
 COMPLY WITH 304.6.2- 1 SQ. INCH PER 3000 BTUH. SEE
 COMMENT #3 FOR COMBUSTION AIR/VENTING COMPLIANCES.
  
 4) FAILED. 3.0P & 3.1P: PROVIDE GAS VENTING PLANS FOR
 THE ROASTER- SECTIONS 305.1, 502.1, 502.5, AND 503.1-.
 THE DRAWING SPEARS TO INDICATE TWO VENT DUCTS FOR THE
 ROASTER THAT ARE PENETRATING THROUGH THE WALL AND
 TURNING UPWARD. PLEASE PROVIDE A DIAGRAM AND ELEVATION
 VIEW SHOWING THE TYPES AND SIZES OF VENT FLUES OR
 DUCTS, HORIZONTAL CONNECTORS, VERTICAL FLUES, AND
 TERMINATION CAPS. PLEASE PROVIDE THE VENT TERMINATION
 CLEARANCE DISTANCES TO DOOR AND WINDOW OPENINGS INTO
 THE BUILDING- SECTIONS 305.1, 403.4, 503.6 & 503.8 FBC
 FG. RTHE TYPE AND SIZE OF EXHAUST/VENTING SYSTEM IS
 DEPENDENT ON THE CATEGORY OF THE APPLIANCE. PLEASE
 INDICATE CATEGORY I, II, III, OR IV PER SECTIONS 202,
 503.6.9.1 & 503.6.9.3.FBC FG. THE CURRENT
 EXHAUST/VENTING PLAN ON SHEET 4.1M IS INCOMPLETE AND
 SHOWS ONLY ONE THE TWO DUCT SYSTEMS.
 A) CLARIFY HOW THE SYSTEM WAS DESIGNED- SUBMIT COFFEE
 ROASTERS VENTING/MAKEUP-COMBUSTION AIR SYSTEM
 SPECIFICATIONS AND GUIDELINES- 305.1, 503.3, 503.3.1 &
 623.1.
  
 B) PROVIDE EXHAUST/VENT DUCTS SIZING CALCULATIONS AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 GUIDELINES FOR THE SINGLE-WALL ZERO CLEARANCE DUCT-
 305.1, 503.3, 503.3.1.503.7.9.
  
 C) PROVIDE A DIMENSIONED EXHAUST/VENT DIAGRAM SHOWING
 CONNECTOR AND TOTAL RUN LENGTH OF THE SYSTEM CONSISTENT
 WITH THE MANUFACTURER'S SPECIFICATIONS AND/OR
 ENGINEERED CALCULATIONS.
  
 D) PLEASE NOTE THE FOLLOWING LIMITATIONS OF USE FOR
 SINGLE WALL DUCT-
  
 SECTION 503.7.3: SINGLE WALL PIPE SHALL EXTEND NOT LESS
 THAN 2 FT. HIGHER THAN ANY PORTION OF A BUILDING WITHIN
 A HORIZONTAL DISTANCE OF 10 FT. THE DRAWNIG IS
 NON-COMPLIANT.
  
 503.7.4: SINGLE-WALL METAL DUCT SHALL BE USED ONLY FOR
 RUNS DIRECTLY FROM THE SPACE IN WHICH THE APPLIANCE IS
 LOCATED THROUGH THE ROOF OR EXTERIOR WALL TO THE
 OUTDOOR ATMOSPHERE. DRAWING IS NON-COMPLIANT.
  
 503.7.5: A PIPE PASSING THROUGH A ROOF SHALL EXTEND
 WITHOUT INTERRUPTION THROUGH THE ROOF FLASHING, ROOF
 JACK OR ROOF THIMBLE. WHERE A SINGLE-WALL METAL PIPE
 PASSES THROUGH A ROOF CONSTRUCTED OF COMBUSTIBLE
 MATERIAL, A NONCOMBUSTIBLE, NONVENTILATING THIMBLE
 SHALL BE USED AT THE POINT OF PASSAGE. THE THIMBLE
 SHALL EXTEND NOT LESS THAN 18 INCHES (457 MM) ABOVE AND
 6 INCHES (152 MM) BELOW THE ROOF WITH THE ANNULAR SPACE
 OPEN AT THE BOTTOM AND CLOSED ONLY AT THE TOP. THE
 THIMBLE SHALL BE SIZED IN ACCORDANCE WITH SECTION
 503.7.7. DRAWING IS NON-COMPLIANT.
  
 503.7.6: SINGLE-WALL METAL PIPE SHALL NOT ORIGINATE IN
 ANY UNOCCUPIED ATTIC OR CONCEALED SPACE AND SHALL NOT
 PASS THROUGH ANY ATTIC, INSIDE WALL, CONCEALED SPACE OR
 FLOOR. THE INSTALLATION OF A SINGLE-WALL METAL PIPE
 THROUGH AN EXTERIOR COMBUSTIBLE WALL SHALL COMPLY WITH
 SECTION 503.7.7. DRAWING IS NON-COMPLIANT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-06-29 Cont ID  
Sent By ccole Date 2021-06-29 Time 12:44 Rev Time 0.00
Received By ccole Date 2021-06-29 Time 12:03 Sent To  
Notes
2021-06-29 12:44:411ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21050671
 6/29/21
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 3.1P: PROVIDE A COMPLETE GAS RISER DRAWING
 THAT INCLUDES ALL NEW AND EXISTING GAS PIPING AND
 APPLIANCES BEING SUPPLIED BY THE METER- SECTION 401.4
 FBC FG. THE DRAWING SHOWS A 2 INCH BRANCH LINE
 SUPPLYING 879 MBTUH. REFER TO SECTION 402 AND PROVIDE:
 A) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 B) TYPES AND SIZES OF PIPING.
 C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 E) LOCATIONS OF REGULATORS, SHUTOFF VALVES, DRIPLEGS,
 AND PIPE UNIONS.
 F) OUTLET PRESSURES AT REGULATORS.
 G) LOCATIONS AND TYPES OF PIPE SLEEVES.
 H) LIST PIPE SIZING TABLES.
  
 2) 3.0P & 3.1P: SUBMIT MANUFACTURER?S SPECIFICATIONS
 FOR THE NEW COFFEE ROASTER- SECTION 305.1 FBC FG.
 PLEASE HIGHLIGHT OR MARKUP THE SPEC TO SHOW THE LISTING
 STANDARD, BTU LOAD, AND GAS INPUT PRESSURE.
  
 3) 3.0P & 3.1P: PROVIDE COMBUSTION AIR CALCULATIONS FOR
 THE COFFEE ROASTER AND INDICATE HOW THE AIR IS BEING
 SUPPLIED- SECTION 304.1 FBC FG.
  
 4) 3.0P & 3.1P: PROVIDE GAS VENTING PLANS FOR THE
 ROASTER- SECTIONS 305.1, 502.1, 502.5, AND 503.1-. THE
 DRAWING SPEARS TO INDICATE TWO VENT DUCTS FOR THE
 ROASTER THAT ARE PENETRATING THROUGH THE WALL AND
 TURNING UPWARD. PLEASE PROVIDE A DIAGRAM AND ELEVATION
 VIEW SHOWING THE TYPES AND SIZES OF VENT FLUES OR
 DUCTS, HORIZONTAL CONNECTORS, VERTICAL FLUES, AND
 TERMINATION CAPS. PLEASE PROVIDE THE VENT TERMINATION
 CLEARANCE DISTANCES TO DOOR AND WINDOW OPENINGS INTO
 THE BUILDING- SECTIONS 305.1, 403.4, 503.6 & 503.8 FBC
 FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2021-10-19 Time   Rev Time 0.00
Received By aoliver Date 2021-09-30 Time 15:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-08-26 Time   Rev Time 0.00
Received By aoliver Date 2021-08-09 Time 08:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-27 Cont ID  
Sent By lmarchan Date 2021-07-27 Time 09:34 Rev Time 0.00
Received By lmarchan Date 2021-05-27 Time 14:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-10-12 Cont ID  
Sent By medwards Date 2021-10-12 Time 10:45 Rev Time 0.00
Received By medwards Date 2021-10-12 Time 10:45 Sent To  
Notes
2021-10-12 10:50:46APPROVED WITH NOTES.
  
 SHEET 4.0M:THIS APPEARS TO BE MISLABELED. THERE SHOULD
 NOT BE A FIRE DAMOER IN THE ROASTER EXHAUST DUCT.
 INSPECTOR TO CHECK IN THE FIELD.
 SHEET 4.1M: COOLING FAN DETAILS CALLS FOR A 6 INCH
 SINGLE WALL COOLING DUCT. INSPECTOR TO VERIFY IN FIELD.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-08-25 Cont ID  
Sent By medwards Date 2021-08-25 Time 12:46 Rev Time 0.00
Received By medwards Date 2021-08-25 Time 12:45 Sent To  
Notes
2021-08-25 12:47:582ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21050671
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ATTACHED SPECIFICATIONS DO NOT SHOW THE EXHAUST
 PIPING DETAILS. PLEASE PROVIDE DETAILS FOR THE EXHAUST
 SYSTEM OF THIS ROASTER, TYPE OF PIPE, SIZE OF PIPE,
 LENGTH OF PIPE. INFORMATION FROM THE MANUFACTURER
 REFERENCING THE EXHAUST PIPING USED. FBC 107.2.1
  
 2) SHEET 4.1M: PLEASE PROVIDE THE USE OF SPACE BASED ON
 FBC M TABLE 403.3.1.1 FOR THE OUTDOOR AIR CALCULATIONS.
 ARE YOU USING KITCHEN FOR THE PREP AREA AND DINING FOR
 THE CUSTOMER AREA? ACCORDING TO FBC M 403.3.1.1 WE MUST
 US THE TABLE FOR CALCULATING THE NUMBER OF PEOPLE IN
 EACH SPACE NOT THE ARCHITECT?S OCCUPANT LOAD. PLEASE
 KEEP IN MIND FOOTNOTE (A) ALLOWS US TO USE THE NET AREA
 AND NOT THE GROSS FLOOR AREA.
  
 3) PLEASE SHOW HOW YOU WILL BE BRINGING IN THE MAKEUP
 AIR FOR THE EXHAUST FAN ON THE ROASTER ( 1125 CFM?S).
 FBC FG 304.9.1
  
 4) THE ROASTER VENTILATION DETAIL SUBMITTED ON SHEET
 4.1M DOES NOT DEPICT THE BUILDING WHERE THIS TENANT
 SPACE IS LOCATED. THIS IS A 3 STORY WITH RETAIL ON THE
 FIRST FLOOR BUT RESIDENTIAL ON THE 2ND AND 3RD FLOORS.
 THIS DRAWING SHOWS ?ZERO CLEARANCE PIPE THRU WALL BOXED
 OUT TO ROOF? BUT DOES NOT SHOW BOTH FLOORS ABOVE NOR
 DOES IT HAVE A NOTE DESCRIBING THIS SITUATION. THIS
 DRAWING ALSO SHOWS A FD IN THE ROASTER EXHAUST PIPE
 ABOVE THE FLOOR IN WHAT APPEARS TO BE A BOX. PLEASE
 SHOW THE MANUFACTURER?S INSTALLATION INSTRUCTIONS FOR
 THIS TYPE OF PIPING METHOD.
  
 5) SHEET 4.1M: THE ROASTER VENTILATION DETAIL DOES NOT
 SHOW THE EXHAUST FOR THE COOLING TUB.
  
  
 6) PLEASE PROVIDE THE LISTING FOR THIS APPLIANCE. FBC M
 301.7
  
 7) PLEASE EXPLAIN YOUR ANSWER TO MY 1ST CYCLE COMMENT
 NUMBER (5): PLEASE SHOW THE OUTDOOR AIR DUCT FOR BOTH
 AHU-1 UNITS. YOUR ANSWER WAS ?BOTH AIR HANDLERS UNITS
 HAVE OUTSIDE AIR DUCT WORK TO THE KNOCK OUT PROVIDED
 WITH BUILDING? PLEASE SHOW THE OUTDOOR AIR DUCT WORK
 AND SIZE ON THE DRAWING. FBC 107.2.1
  
 8) 1ST CYCLE REVIEW COMMENT NUMBER (6) AHU-2 FOR THE
 KITCHEN AREA: CFM?S ON SHEET 4.0M SHOWS A TOTAL OF 2200
 CFM?S OF SUPPLY AIR BEING SUPPLIED INTO THE KITCHEN
 AREA. SHEET 4.1M INDICATES THE MAX. CFM OF SUPPLY FOR
 THIS UNIT IS 2000 CFM?S. PLEASE BE CONSISTENT. FBC
 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-06-22 Cont ID  
Sent By medwards Date 2021-06-22 Time 14:47 Rev Time 0.00
Received By medwards Date 2021-06-22 Time 13:51 Sent To  
Notes
2021-06-22 14:47:381ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21050671
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE
 OF SPACE ACCORDING TO FBC M 403.3.1.1 AND TABLE
 403.3.1.1.
  
 2) PLEASE PROVIDE THE SPECIFICATIONS FOR THE ROASTING
 EQUIPMENT AND THE VENTING OF THIS EQUIPMENT. FBC
 107.2.1
  
 3) PLEASE SHOW THE CONDENSATE PIPING MATERIAL AND
 SIZING ALONG WITH THE TERMINATION LOCATION. THE
 CONDENSATE IS REQUIRED TO GO TO STORM OR AN APPROVED
 OUTDOOR LOCATION. FBC M 307
  
 4) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THIS TENANT SPACE.
  
 5) PLEASE SHOW THE OUTDOOR AIR DUCT FOR BOTH AHU-1
 UNITS. FBC 107.2.1
  
 6) THE KITCHEN AHU-1 IS SUPPLY 2400 CFM?S OF AIR BUT
 THE SPECS SHOW IT CAN ONLY SUPPLY 2000 CFM. PLEASE
 CORRECT THIS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-10-22 Cont ID  
Sent By ccole Date 2021-10-22 Time 08:58 Rev Time 0.00
Received By ccole Date 2021-10-22 Time 08:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-10-19 Cont ID  
Sent By ccole Date 2021-10-19 Time 11:22 Rev Time 0.00
Received By ccole Date 2021-10-18 Time 12:12 Sent To  
Notes
2021-10-19 11:23:153RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21050671
 6/29/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS 3.0P & 3.1P: 3RD REQUEST- A MASTER
 THERMOSTATIC MIXING VALVE IS SPECIFIED TO PROVIDE
 TEMPERED WATER AT 108 DEGREES F TO ALL FIXTURES EXCEPT
 THE MOP SINK AND 3-COMPARTMENT, HOWEVER THE PLAN AND
 WATER RISER EACH SHOW HOT WATER LINES AT 140 AND 110
 DEGREES F BEING. PLEASE SEE SECTION 202 FOR DEFINITIONS
 OF HOT AND TEMPERED WATER AND CORRECT THE PLAN. PLEASE
 NOTE THAT THE TEMPERED WATER IS ONLY REQUIRED FOR THE
 LAVATORIES REQUIRED FOR THE LAVATORIES- SECTION 419.5
 FBC P. THE DESIGNER HAS THE OPTION OF USING POINT OF
 USE MIXING VALVES OR SUPPLY COLD WATER ONLY.
  
 2) 3.0P: 3RD REQUEST TO SHOW THE HOT WATER RETURN LINE
 CONNECTING TO THE MIXING VALVE AND TO THE COLD WATER
 INLET PIPE TO THE WATER HEATER- SECTION 607.2.2. FBC P.
  
 3) 3.1P: 2ND REQUEST TO CORRECT THE SANITARY RISER
 DRAWING SHOWING THE EXISTING 4-INCH SANITARY DRAIN
 CONNECTING TO THE NEW GREASE WASTE LINE- SECTION
 107.2.1 WPB AND 1003.3.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-08-26 Cont ID  
Sent By ccole Date 2021-08-26 Time 15:12 Rev Time 0.00
Received By ccole Date 2021-08-26 Time 08:31 Sent To  
Notes
2021-08-26 15:14:481ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21050671
 6/29/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH ADDITIONAL NOTED IN CAP LETTERS.
  
 10) FAILED. 3.1P: ONE HAND SINK LABEL IS MISSING IN THE
 WATER RISER- SECTION 107.2.1 WPB. PROVIDE THE MISSING
 HS LABEL.
  
 11) FAILED. 3.1P WATER RISER: PLEASE PROVIDE A
 DIFFERENT LINE SYMBOL FOR THE HOT WATER RETURN LINE.
 THE SAME HOT WATER SYMBOL IS BEING USED TO DESIGNATE HW
 AT 110 DEGREES, HW AT 140 DEGREES, AND HW RETURN. REFER
 TO THE MASTER MIXING VALVE DETAIL ON SHEET 3.0P: THE
 DETAIL SHOWS INLETS FOR 140 DEGREE HW AND CW, AND ONE
 OUTLET FOR 110 DEGREE TEMPERED. NEITHER THE WATER RISER
 NOR THE ENLARGED WATER HEATER PIPING DETAIL MATCH WITH
 THE VALVE DETAIL. PLEASE REFER TO SECTION 607.2.2 FBC P
 AND REVISE THE DRAWINGS- WHERE A THERMOSTATIC MIXING
 VALVE IS USED IN A SYSTEM WITH A HOT WATER
 RECIRCULATING PUMP, THE HOT WATER OR TEMPERED WATER
 RETURN LINE SHALL BE ROUTED TO THE COLD WATER INLET
 PIPE OF THE WATER HEATER AND THE COLD WATER INLET PIPE
 OR THE HOT WATER RETURN CONNECTION OF THE THERMOSTATIC
 MIXING VALVE. A) PLRASE LABEL THE MIXING VALVE ON THE
 RISER DRAING. THE REQUESTED LINE SYMBOL CHANGEES WERE
 NOT PROVIDED.
  
 14) FAILED. 3.1P: PROVIDE A PLUMBING FIXTURE SCHEDULE
 LISTING MAKES AND MODELS BATHROOM FIXTURES, MOP SINK,
 3-COMPARTMENT SINK, HAND SINKS, DUMP SINK, FLOOR SINKS,
 FLOOR DRAIN, AND WATER FILTER SYSTEM- SECTIONS
 107.3.5.1.3 & 107.2.1 WPB. THE MOP SINK, 3-COMPARTMENT
 SINK, HAND SINKS, DUMP SINK, FLOOR SINKS, FLOOR DRAIN,
 AND WATER FILTER SYSTEM WERE NOT INCLUDED IN THE
 FIXTURE SCHEDULE HOWEVER THESE ITEMS MAY BE DEFERRED IF
 NECESSARY. PLEASE PROVIDE A LIST OF ALL REQUESTED
 DEFERRED SUBMITTALS ON THE PLAN- SECTION 107.3.4.1 WPB.
  
 15) FAILED. 3.1P: PROVIDE A DEVICE SCHEDULE LISTING
 MAKES AND MODELS OF WATER HAMMER ARRESTORS, MIXING
 VALVES, RECIRCULATION PUMP, AND BACKFLOW PREVENTERS-
 SECTIONS 107.3.5.1.3 & 107.2.1 WPB. A DEVICE SCHEDULE
 WAS NOT PROVIDED HOWEVER THE WATER HAMMER ARRESTORS,
 MIXING VALVES, AND BACKFLOW PREVENTERS MAY BE DEFERRED
 SUBMITTALS IF NECESSARY. PLEASE PROVIDE A LIST OF ALL
 REQUESTED DEFERRED SUBMITTALS ON THE PLAN- SECTION
 107.3.4.1 WPB.
  
 17) FAILED. 3.1P GREASE INTERCEPTOR: PLEASE NOTE A
 SEPARATE PERMIT IS REQUIRED FOR INSTALLATION OF THE
 INTERCEPTOR AND A COMPLETE PLANS AND SPECIFICATIONS
 SHALL BE SUBMITTED INCLUDING A CIVIL PLAN- SECTION
 107.2.1 WPB. FOR THE PURPOSES OF THIS PERMIT PLEASE
 SHOW REQUIRED CLEANOUTS AT THE INLET AND OUTLET OF THE
 INTERCEPTOR AND THE LOCATION OF THE SAMPLING PORT.
 PROVIDE A DETAIL FOR INSTALLATION OF THE PORT PER
 MANUFACTURER?S SPECIFICATIONS- SECTION 1003.3.3 FBC P.
 THE GREASE INTERCEPTOR IS INDICATED TO BE A SCHIER GB50
 ON SHEET 3.0P, AND A GBHF-250-250 ON SHEET 3.1P.
  
 A) FAILED. 3.1P: PROVIDE SIZING CALCULATIONS FOR THE
 INTERCEPTOR IN ACCORDANCE WITH ASME A112.14.3, ASME
 A112.14.4, ASME A112.14.6, CSA B481.3 OR PDI G101-
 SECTION 1003.3.3 FBC P. THE CALCULATIONS ON SHEET 3,0P
 DO NOT INCLUDE THE DUMP SINK.
  
 NEW COMMENTS.
  
 1) 3.0P & 3.1P: THE 4-INCH EXISTING SANITARY IS SHOWN
 CONNECTING TO THE GREASE WASTE LINE IN THE SANITARY
 RISER DRAWING- SECTION 107.2.1 WPB.
  
 2) 3.0: THE LOCATION OF THE CLEANOUT AT THE JUNCTION OF
 THE SANITARY AND SEWER DRAIN NOT PROVIDED.
  
 3) 3.0P & 3.1P: CORRECT THE SUPPLY PIPING LAYOUT TO THE
 URINAL AND LAVATORY ON 3.0P- 107.2.1 WPB.
  
 4) 3.0P & 3.1P: THE PLAN IS NOT SHOWING HOW TEMPERED
 WATER WILL BE PROVIDED TO THE LAVATORIES AS REQUIRED BY
 SECTION 419.5 FBC P. PLEASE NOTE THE MASTER MIXING
 VALVE IS SUPPLYING HOT WATER AT 110 DEGREES F. TEMPERED
 WATER IS DEFINED AS WATER HAVING A TEMPERATURE RANGE
 BETWEEN 85 DEGREES AND 110 DEGREES F.
  
 5) 1.1A, 3.0P & 3.1P: THE WATER FILTERING SYSTEM IS NOT
 INCLUDED IN THE EQUIPMENT SCHEDULE, AND THE WATER RISER
 IS NOT SHOWING ALL THE FILTERED WATER SUPPLY LINES TO
 THE EQUIPMENT IN THE SCHEDULE. PLEASE MODIFY THE RISER
 OR PROVIDE A SEPARATE FILTERED WATER SYSTEM RISER-
 SECTION 107.2.1. PLEASE NOTE THAT INDIVIDUAL BACKFLOW
 PREVENTERS ARE REQUIRED ON EACH SUPPLY LINE TO THE
 COFFEE EQUIPMENT.
  
 6) 3.0P & 3.1P: IT IS ACKNOWLEDGED THAT THE GREASE
 INTERCEPTOR WILL BE UNDER SEPARATE PERMIT, HOWEVER MORE
 INFORMATION UNDER THE MAIN PERMIT IS REQUIRED INCLUDING
 THE JUNCTION LOCATIONS OF THE EXISTING SANITARY, GREASE
 WASTE OUTLET PIPE, AND EXISTING SEWER LINE. PLEASE ALSO
 SHOW THE LOCATION OF THE INTERCEPTOR SAMPLING PORT AND
 CLARIFY IF THE INTERCEPTOR IS LOCATED IN A DRIVE OR
 LANDSCAPED AREA. PLEASE NOTE THAT HEAVY DUTY TRAFFIC
 LIDS AT ACCESS COVERS ARE REQUIRED FOR INTERCEPTORS IN
 DRIVE AREAS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-06-29 Cont ID  
Sent By ccole Date 2021-06-29 Time 12:00 Rev Time 0.00
Received By ccole Date 2021-06-29 Time 07:52 Sent To  
Notes
2021-06-29 12:00:271ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21050671
 6/29/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET C1: THE PLUMBING FIXTURE CALCULATIONS BASED ON
 72 OCCUPANTS DOES NOT MATCH THE 129 NUMBER OF SEATS
 SHOWN. PLEASE CORRECT- TABLE 403.1 FBC P.
  
 2) 1.0A & 1.4A: PLEASE PROVIDE ENLARGED MEN'S AND
 WOMEN'S TOILET ROOM ENLARGED DIMENSIONED DRAWINGS ON
 1.4A THAT MATCH THE FLOOR PLAN DRAWINGS ON 1.0A. THE
 FLOOR PLAN SHOWS DOORS SWINGING IN TO THE TOILET ROOMS
 WHICH IS NOT ALLOWED PER SECTION 603.2.3 FBC ACC. THE
 FLOOR PLAN ALSO DOES NOT PROVIDE A WIDTH MEASUREMENT
 FOR THE WOMEN'S TOILET ROOM- SECTION 107.2.1 WPB.
  
 3) 1.4A: LOCATION OF THE TOILET PAPER DISPENSER IS NOT
 SHOWN TO BE IN COMPLIANCE WITH SECTION 604.7 FBC ACC.
  
 4) 1.4A: PROVIDE AN ELEVATION VIEW OF THE CONDIMENTS
 COUNTER TO VERIFY ACCESSIBILITY COMPLIANCES- SECTIONS-
 904.5 & 308 FBC ACC.
  
 5) 1.1A, 3.0P, & 3.1P: THE HAND SINKS- #10, #28, AND
 THE FLOOR SINK BY THE ICE MAKER AND BIN SHALL NOT DRAIN
 IN TO THE GREASE WASTE LINE AND INTERCEPTOR- SECTION
 1003.3.1 FBC P. THE FIXTURES ARE NOT CONSIDERED TO BE
 SIGNIFICANT GREASE CONTRIBUTORS.
  
 6) 1.1A, 3.0P, & 3.1P: THE DUMP SINK #21 REQUIRES AN
 INDIRECT WASTE- SECTION 802.1 FBC P.
  
 7) 1.1A, 3.0P, & 3.1P: HAND SINK #28 APPEARS TO MISSING
 FROM THE ISOMETRIC DRAWINGS.
  
 8) 3.0P: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER
 HEATER MAKE AND MODEL AND EFFICIENCY RATING- SECTION
 502.1 FBC P. SHOW THE PAN DRAIN AND PAN DRAIN LINE RUN
 AND TERMINATION LOCATION- SECTIONS 504.6- 504.7.2 FBC
 P.
  
 9) 3.0P: THE SERVICE ACCESS TO THE WATER HEATER APPEARS
 TO BE BLOCKED BY THE ADJACENT SINKS- SECTION 501.4 FBC
 P.
  
 10) 3.1P: ONE HAND SINK LABEL IS MISSING IN THE WATER
 RISER- SECTION 107.2.1 WPB.
  
 11) 3.1P WATER RISER: PLEASE PROVIDE A DIFFERENT LINE
 SYMBOL FOR THE HOT WATER RETURN LINE. THE SAME HOT
 WATER SYMBOL IS BEING USED TO DESIGNATE HW AT 110
 DEGREES, HW AT 140 DEGREES, AND HW RETURN. IT ALSO
 APPEARS THAT NO COLD WATER IS BEING SUPPLIED TO THE
 LAVATORY SINKS.
  
 12) 3.1P: ONE LAVATORY IS NOT LABELED IN THE SANITARY-
 SECTION 107.2.1 WPB.
  
 13) THE URINAL IS NOT INCLUDED IN THE DEFINITION OF A
 BATHROOM GROUP SO THE FIXTURE DRAIN FROM THE URINAL
 SHALL NOT CONNECT INTO THE HORIZONTAL WET VENT-
 SECTIONS 202 AND 912.1 FBC P. THE FIXTURE MUST BE
 INDIVIDUALLY VENTED AND CONNECTION OF THE DRAIN SHALL
 BE DOWNSTREAM OF THE WET VENT.
 14) 3.1P: PROVIDE A PLUMBING FIXTURE SCHEDULE LISTING
 MAKES AND MODELS BATHROOM FIXTURES, MOP SINK,
 3-COMPARTMENT SINK, HAND SINKS, DUMP SINK, FLOOR SINKS,
 FLOOR DRAIN WATER FILTER SYSTEM- SECTIONS 107.3.5.1.3 &
 107.2.1 WPB.
  
 15) 3.1P: PROVIDE A DEVICE SCHEDULE LISTING MAKES AND
 MODELS OF WATER HAMMER ARRESTORS, MIXING VALVES,
 RECIRCULATION PUMP, AND BACKFLOW PREVENTERS- SECTIONS
 107.3.5.1.3 & 107.2.1 WPB.
  
 16) 3.1P: PROVIDE CLEANOUT AT THE JUNCTION OF THE
 SANITARY BUILDING DRAIN AND SEWER LINE- SECTION 708.1.3
 FBC P.
  
 17) 3.1P GREASE INTERCEPTOR: PLEASE NOTE A SEPARATE
 PERMIT IS REQUIRED FOR INSTALLATION OF THE INTERCEPTOR
 AND A COMPLETE PLANS AND SPECIFICATIONS SHALL BE
 SUBMITTED INCLUDING A CIVIL PLAN- SECTION 107.2.1 WPB.
 FOR THE PURPOSES OF THIS PERMIT PLEASE SHOW REQUIRED
 CLEANOUTS AT THE INLET AND OUTLET OF THE INTERCEPTOR
 AND THE LOCATION OF THE SAMPLING PORT. PROVIDE A DETAIL
 FOR INSTALLATION OF THE PORT PER MANUFACTURER?S
 SPECIFICATIONS- SECTION 1003.3.3 FBC P.
  
 A) 3.1P: PROVIDE SIZING CALCULATIONS FOR THE
 INTERCEPTOR IN ACCORDANCE WITH ASME A112.14.3, ASME
 A112.14.4, ASME A112.14.6, CSA B481.3 OR PDI G101-
 SECTION 1003.3.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status N Date 2021-10-22 Cont ID  
Sent By ccole Date 2021-10-22 Time 09:05 Rev Time 0.00
Received By ccole Date 2021-10-22 Time 09:05 Sent To  
Notes
2021-10-22 09:05:47SEPARATE PERMIT REQUIRED FOR GREASE INTERCEPTOR
 INSTALLATION.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-10-22 Cont ID  
Sent By ccole Date 2021-10-22 Time 08:59 Rev Time 0.00
Received By ccole Date 2021-10-22 Time 08:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-10-19 Cont ID  
Sent By ccole Date 2021-10-19 Time 11:25 Rev Time 0.00
Received By ccole Date 2021-10-18 Time 12:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-24 Cont ID  
Sent By pvalenti Date 2021-08-24 Time 16:16 Rev Time 0.00
Received By pvalenti Date 2021-08-24 Time 16:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-06-22 Cont ID  
Sent By medwards Date 2021-06-22 Time 14:49 Rev Time 0.00
Received By medwards Date 2021-06-22 Time 14:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-08-18 Cont ID  
Sent By jroach Date 2021-08-18 Time 09:50 Rev Time 0.00
Received By jroach Date 2021-08-18 Time 09:50 Sent To  
Notes
2021-08-18 09:51:37THIS REVIEW IS LIMITED TO THE INTERIOR BUILD-OUT ONLY.
  
 THE CASA MARA COMMERCIAL PLANNED DEVELOPMENT SHALL BE
 SUBJECT TO ALL DEVELOPMENT ORDER CONDITIONS, AS
 OUTLINED IN RESOLUTION NO. 108-21, APPROVED ON JUNE 1,
 2021, AND AS MAY BE AMENDED.
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE DEVELOPER SHALL DESIGNATE AT LEAST 71 ON-SITE
 PARKING SPACES (OUTSIDE OF THE SECURITY GATE-CONTROLLED
 PARKING FIELDS) TO BE RESERVED FOR USE BY PATRONS AND
 EMPLOYEES OF THE NON-RESIDENTIAL USES. THE SPACES SHALL
 BE RESERVED FOR SUCH USE BETWEEN THE HOURS OF 11:00 AM
 AND 7:00 PM. OUTSIDE OF THOSE HOURS, THESE 71 PARKING
 SPACES WILL BE AVAILABLE FOR USE BY THE NON-RESIDENTIAL
 PATRONS/EMPLOYEES AS WELL AS RESIDENTS. SIGNAGE AND/OR
 MARKING TO DESIGNATE THESE SPACES WILL BE DETERMINED
 AND IMPLEMENTED BY THE OWNER, SUBJECT TO REVIEW AND
 APPROVAL BY THE CITY?S PLANNING DIVISION. THE HOURS AND
 NUMBER OF SPACES DESIGNATED MAY BE ADJUSTED THROUGH AN
 ADMINISTRATIVE APPROVAL BY CITY?S PLANNING DIVISION IF
 THE USE AND/OR OPERATING HOURS OF COMMERCIAL TENANTS
 SIGNIFICANTLY CHANGES IN THE FUTURE.
  
 _______________________________________________________
 _____________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 P: 561.822.1448 | E: [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2021-08-11 Cont ID  
Sent By jroach Date 2021-08-11 Time 09:34 Rev Time 0.00
Received By jroach Date 2021-08-11 Time 09:10 Sent To  
Notes
2021-08-11 09:34:40ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 08.11.2021
 PERMIT NO.: 21050671
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. [ SATISFIED ] - PLEASE PROVIDE A SITE PLAN OR
 SIMILAR SHOWING WHICH BUILDING AND WHICH SPACE THIS
 IMPROVEMENT PERTAINS TO. THERE IS NO CONTEXT ON THE
 FLOOR PLAN FOR ME TO KNOW WHERE THIS IMPROVEMENTS ARE
 TAKING PLACE.
  
 2. [ SATISFIED ] - WHAT IS HAPPENING TO THE EXTERIOR
 DOOR ON THE NORTH SIDE OF THE BUILDING, CLOSEST TO
 SOUTH DIXIE HIGHWAY? THERE IS A SYMBOL WITH THE #1
 THERE, BUT NO LEGEND OR KEY FOR ME TO KNOW WHAT IS
 PROPOSED.
  
 3. [ SATISIFED ] - WHAT IS HAPPENING TO THE
 EASTERN-MOST DOOR THAT CONNECTS TO THE CORRIDOR IN THE
 MIDDLE OF THE BUILDING?
  
 4. [ SATISFIED ] - ON SHEET 1.1A, WHAT ARE THE TWO AREA
 OUTLINED WITH A DASHED LINE AND CONTAINING A SQUARE
 FOOTAGE CALCULATION?
  
 5. [ SATISFIED ] - THE OUTDOOR SEATING SHOWN ON THE
 PLAN DOES NOT MATCH THAT WHICH WAS APPROVED ON THE CASA
 MARA CPD SITE PLAN. THE AREAS SHALL MATCH, OR IF THE
 AREA IS PROPOSED TO BE MODIFIED, AN AMENDMENT TO THE
 CPD SHALL BE SUBMITTED TO AND APPROVED BY THE PLANNING
 DIVISION.
  
 6. [ SATISFIED ] - THE OUTDOOR SEATING SHOWN ON THE
 PLAN CONFLICTS WITH THE ACCESSIBLE ROUTE FROM THE
 ADJACENT ACCESSIBLE PARKING SPACES.
  
 7. [ NOT SATISFIED ] - THE PLANS DO NOT ACCURATELY
 REFLECT THE SIDEWALK, LANDSCAPING ISLANDS, PARKING,
 ETC. ON THE EAST SIDE OF THE BUILDING (ALONG SOUTH
 DIXIE HIGHWAY).
  
 8. [ SATISIFED - SUBJECT TO PROVISO ] - PURSUANT TO
 RESOLUTION NO. 108-21, THE DEVELOPER SHALL DESIGNATE AT
 LEAST 71 ON-SITE PARKING SPACES (OUTSIDE OF THE
 SECURITY GATE-CONTROLLED PARKING FIELDS) TO BE RESERVED
 FOR USE BY PATRONS AND EMPLOYEES OF THE NON-RESIDENTIAL
 USES. THE SPACES SHALL BE RESERVED FOR SUCH USE BETWEEN
 THE HOURS OF 11:00 AM AND 7:00 PM. OUTSIDE OF THOSE
 HOURS, THESE 71 PARKING SPACES WILL BE AVAILABLE FOR
 USE BY THE NON-RESIDENTIAL PATRONS/EMPLOYEES AS WELL AS
 RESIDENTS.
  
 SIGNAGE AND/OR MARKING TO DESIGNATE THESE SPACES WILL
 BE DETERMINED AND IMPLEMENTED BY THE OWNER, SUBJECT TO
 REVIEW AND APPROVAL BY THE CITY?S PLANNING DIVISION.
 THE HOURS AND NUMBER OF SPACES DESIGNATED MAY BE
 ADJUSTED THROUGH AN ADMINISTRATIVE APPROVAL BY CITY?S
 PLANNING DIVISION IF THE USE AND/OR OPERATING HOURS OF
 COMMERCIAL TENANTS SIGNIFICANTLY CHANGES IN THE FUTURE.
  
 9. [ SATISFIED ] - PLEASE CONFIRM THAT VENTING THE
 ROASTING EQUIPMENT INTO THE CORRIDOR IS PERMITTED BY
 APPLICABLE BUILDING CODES, ETC.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-07-27 Cont ID  
Sent By jroach Date 2021-07-27 Time 09:25 Rev Time 0.00
Received By jroach Date 2021-07-27 Time 09:25 Sent To  
Notes
2021-07-27 09:26:09ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 07.27.2021
 PERMIT NO.: 21050671
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE A SITE PLAN OR SIMILAR SHOWING WHICH
 BUILDING AND WHICH SPACE THIS IMPROVEMENT PERTAINS TO.
 THERE IS NO CONTEXT ON THE FLOOR PLAN FOR ME TO KNOW
 WHERE THIS IMPROVEMENTS ARE TAKING PLACE.
  
 2. WHAT IS HAPPENING TO THE EXTERIOR DOOR ON THE NORTH
 SIDE OF THE BUILDING, CLOSEST TO SOUTH DIXIE HIGHWAY?
 THERE IS A SYMBOL WITH THE #1 THERE, BUT NO LEGEND OR
 KEY FOR ME TO KNOW WHAT IS PROPOSED.
  
 3. WHAT IS HAPPENING TO THE EASTERN-MOST DOOR THAT
 CONNECTS TO THE CORRIDOR IN THE MIDDLE OF THE BUILDING?
  
 4. ON SHEET 1.1A, WHAT ARE THE TWO AREA OUTLINED WITH A
 DASHED LINE AND CONTAINING A SQUARE FOOTAGE
 CALCULATION?
  
 5. THE OUTDOOR SEATING SHOWN ON THE PLAN DOES NOT MATCH
 THAT WHICH WAS APPROVED ON THE CASA MARA CPD SITE PLAN.
 THE AREAS SHALL MATCH, OR IF THE AREA IS PROPOSED TO BE
 MODIFIED, AN AMENDMENT TO THE CPD SHALL BE SUBMITTED TO
 AND APPROVED BY THE PLANNING DIVISION.
  
 6. THE OUTDOOR SEATING SHOWN ON THE PLAN CONFLICTS WITH
 THE ACCESSIBLE ROUTE FROM THE ADJACENT ACCESSIBLE
 PARKING SPACES.
  
 7. THE PLANS DO NOT ACCURATELY REFLECT THE SIDEWALK,
 LANDSCAPING ISLANDS, PARKING, ETC. ON THE EAST SIDE OF
 THE BUILDING (ALONG SOUTH DIXIE HIGHWAY).
  
 8. PURSUANT TO RESOLUTION NO. 108-21, THE DEVELOPER
 SHALL DESIGNATE AT LEAST 71 ON-SITE PARKING SPACES
 (OUTSIDE OF THE SECURITY GATE-CONTROLLED PARKING
 FIELDS) TO BE RESERVED FOR USE BY PATRONS AND EMPLOYEES
 OF THE NON-RESIDENTIAL USES. THE SPACES SHALL BE
 RESERVED FOR SUCH USE BETWEEN THE HOURS OF 11:00 AM AND
 7:00 PM. OUTSIDE OF THOSE HOURS, THESE 71 PARKING
 SPACES WILL BE AVAILABLE FOR USE BY THE NON-RESIDENTIAL
 PATRONS/EMPLOYEES AS WELL AS RESIDENTS.
  
 SIGNAGE AND/OR MARKING TO DESIGNATE THESE SPACES WILL
 BE DETERMINED AND IMPLEMENTED BY THE OWNER, SUBJECT TO
 REVIEW AND APPROVAL BY THE CITY?S PLANNING DIVISION.
 THE HOURS AND NUMBER OF SPACES DESIGNATED MAY BE
 ADJUSTED THROUGH AN ADMINISTRATIVE APPROVAL BY CITY?S
 PLANNING DIVISION IF THE USE AND/OR OPERATING HOURS OF
 COMMERCIAL TENANTS SIGNIFICANTLY CHANGES IN THE FUTURE.
  
 9. PLEASE CONFIRM THAT VENTING THE ROASTING EQUIPMENT
 INTO THE CORRIDOR IS PERMITTED BY APPLICABLE BUILDING
 CODES, ETC.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION