Plan Review Details - Permit 21050663
Plan Review Stops For Permit 21050663
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-06-11 Cont ID  
Sent By jgomez Date 2021-06-11 Time 13:51 Rev Time 0.00
Received By jgomez Date 2021-06-11 Time 13:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-08 Cont ID  
Sent By jgomez Date 2021-06-08 Time 14:50 Rev Time 0.00
Received By jgomez Date 2021-06-08 Time 14:49 Sent To  
Notes
2021-06-08 14:58:05RESIDENTIAL (R2) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21050663
  
 RESUBMITTAL COMMENTS:
 1-ONLY THE IMPACT SOUND TRANSMISSION TEST (IIC) WAS
 PROVIDED. ALSO, IMPACT SOUND TRANSMISSION TEST
 SUBMITTED IS FOR LAMINATED FLOORING. PROPOSED FLOORING
 IS NOT LAMINATED. PROVIDE TEST FOR TYPE OF FLOORING TO
 BE INSTALLED.
  
 2- NEED TO PROVIDE FLAME SPREAD TEST AND IMPACT
 INSULATION CLASS (IIC) TEST. SEE COMMENTS 1(A) AND 1(C)
 BELOW.
  
  
  
  
  
  
  
 1-FLOORING SOUND INSULATION MATERIAL:
 A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION
 (2020).
  
 B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 2- OK
  
 3- OK
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-04 Cont ID  
Sent By jgomez Date 2021-06-04 Time 10:48 Rev Time 0.00
Received By jgomez Date 2021-06-04 Time 10:45 Sent To  
Notes
2021-06-04 10:49:55RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21050663
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1-FLOORING SOUND INSULATION MATERIAL:
 A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION
 (2020).
  
 B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH. ALSO, THERE ARE
 TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT SUSPENDED
 ACOUSTICAL CEILINGS IN THESE BUILDINGS.
  
 2-PROVIDE FLOOR PLAN SHOWING AREAS OF WORK AND SQUARE
 FOOT PER ROOM OR AREA. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS AND
 CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL
 COSTS OR PROVIDE COPY OF SIGNED CONTRACTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-06-09 Cont ID  
Sent By pleduc Date 2021-06-09 Time   Rev Time 0.00
Received By pleduc Date 2021-06-09 Time 13:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-05-25 Cont ID  
Sent By pleduc Date 2021-05-25 Time   Rev Time 0.00
Received By pleduc Date 2021-05-25 Time 15:34 Sent To  
Notes
2021-05-25 15:42:52THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO FLOOR PLAN INDICATING WHERE THE TILE
 WILL/WILL NOT BE INSTALLED.
  
 PLEASE PROVIDE A FLOOR PLAN SHOWING LOCATIONS EVEN IF
 ENTIRE FLOOR PLAN.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-11 Cont ID  
Sent By jgomez Date 2021-06-11 Time 13:51 Rev Time 0.00
Received By jgomez Date 2021-06-11 Time 13:32 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-11 Cont ID  
Sent By lmarchan Date 2021-06-11 Time 12:13 Rev Time 0.00
Received By lmarchan Date 2021-06-08 Time 15:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-04 Cont ID  
Sent By jgomez Date 2021-06-04 Time 10:59 Rev Time 0.00
Received By jgomez Date 2021-05-14 Time 13:11 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-06-04 Cont ID  
Sent By jgomez Date 2021-06-04 Time 10:59 Rev Time 0.00
Received By jgomez Date 2021-06-04 Time 10:50 Sent To  
Notes
***NONE***