| Plan Review Stops For Permit 21050545 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2021-05-12 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-05-12 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-05-12 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2021-05-12 12:27:43 | ADDRESS DOES NOT NEED TO CHANGE, ORIGINAL ADDRESS OF | | | 810 34TH ST OK TO REMAIN. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2022-12-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-12-05 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-12-05 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2022-12-05 16:40:54 | BUILDING REVIEW APPROVED WITH PROVISO. | | | (NOTE: SUBMIT INFORMATION FOR REVIEW PRIOR TO | | | INSTALLATION/INSPECTIONS TO AVOID CONFLICTS/DELAYS): | | | | | | 1-REVISE MAIN HOUSE ENERGY CALCULATIONS: MISSING | | | WINDOWS ON THE EAST SIDE. SEE FLOOR PLAN. | | | 2- REVISE REAR STRUCTURE ENERGY CALCULATIONS WINDOWS | | | INFORMATION: GLASS DOORS SQUARE FOOTAGE DOESN'T MATCH | | | PLANS. | | | 3- PROVIDE PRODUCT APPROVAL FOR (NOTE: SUBMIT | | | INFORMATION FOR REVIEW PRIOR TO INSTALLATION/INSPECTION | | | TO AVOID CONFLICTS/DEALAYS): | | | A)DEN FRENCH DOORS NOA THAT MEET OR EXCEED THE DESIGN | | | PRESSURES SHOWN ON PLANS. | | | B)ENTRY DOOR (SOLID WOOD AS SHOWN ON PLANS). | | | C)HURRICANE SHUTTERS FOR DOORS WITHOUT IMPACT GLAZING. | | | AND, PROVIDE COMPLETE INSTALLATION SCHEDULE. | | | D)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | TO BE INSTALLED (NOTE: WOOD ROOF & CONCRETE BALCONY). | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-09-29 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-09-29 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2022-09-29 16:24:54 | BUILDING REVIEW APPROVED WITH PROVISO. | | | (NOTE: SUBMIT INFORMATION FOR REVIEW PRIOR TO | | | INSTALLATION/INSPECTIONS TO AVOID CONFLICTS/DELAYS): | | | | | | 1-REVISE MAIN HOUSE ENERGY CALCULATIONS: MISSING | | | WINDOWS ON THE EAST SIDE. SEE FLOOR PLAN. | | | 2- REVISE REAR STRUCTURE ENERGY CALCULATIONS WINDOWS | | | INFORMATION: GLASS DOORS SQUARE FOOTAGE DOESN'T MATCH | | | PLANS. | | | 3- PROVIDE PRODUCT APPROVAL FOR (NOTE: SUBMIT | | | INFORMATION FOR REVIEW PRIOR TO INSTALLATION/INSPECTION | | | TO AVOID CONFLICTS/DEALAYS): | | | A)DEN FRENCH DOORS NOA THAT MEET OR EXCEED THE DESIGN | | | PRESSURES SHOWN ON PLANS. | | | B)ENTRY DOOR (SOLID WOOD AS SHOWN ON PLANS). | | | C)HURRICANE SHUTTERS FOR DOORS WITHOUT IMPACT GLAZING. | | | AND, PROVIDE COMPLETE INSTALLATION SCHEDULE. | | | D)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | TO BE INSTALLED (NOTE: WOOD ROOF & CONCRETE BALCONY). | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-08-29 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-08-29 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2022-08-29 13:34:44 | NEW SINGLE FAMILY RESIDENCE (R3), FOURTH BUILDING | | | REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #21050545 | | | 810 34TH ST | | | | | | NOTE: | | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER | | | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID | | | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. | | | CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT | | | THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION | | | BEFORE PERMIT ISSUANCE. | | | | | | ORIGINAL COMMENT: | | | 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | R101.5.1 FBC-ENERGY CONSERVATION. | | | NOTE: NEED TWO SEPARATE ENERGY CALCULATIONS. ONE FOR | | | THE MAIN HOUSE AND ONE FOR THE REAR STRUCTURE. | | | PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL THE | | | REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED | | | AGENT TO AVOID CONFLICT/DELAYS. | | | BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE | | | LEVEL (EPL) DISPLAY CARD SUBMITTED. SEC. R405.4.3 FBC- | | | ENERGY CONSERVATION. | | | | | | RESPONSE: | | | REVISE MAIN HOUSE ENERGY CALCULATIONS: | | | | | | PREVIOUS COMMENT: | | | E)REVISE WINDOWS AREA AND OVERHANG DEPTH & SEPARATION | | | TO MATCH PLANS. | | | NOTE: DOORS WITH GLAZING NEED TO BE CONSIDERED IN THE | | | WINDOWS GLAZING SECTION. | | | | | | RESPONSE: | | | MISSING WINDOWS ON THE EAST SIDE. SEC. R101.5.1.1.2 | | | FBC-ENERGY CONSERVATION. | | | | | | REVISE REAR STRUCTURE ENERGY CALCULATIONS: | | | | | | PREVIOUS COMMENT: | | | B)FLOOR INFORMATION ON ITEM #9 ON PAGE ONE DOESN'T | | | MATCH PLANS. NEED INSULATION BETWEEN A/C AND NON A/C | | | AREAS. ALSO, REVISE A/C SQUARE FOOTAGES. SEE PLANS AND | | | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY | | | CONSERVATION. | | | | | | RESPONSE: | | | INFORMATION DOESN'T MATCH PLANS. SQUARE FOOTAGES DON'T | | | MATCH. WHAT IS THE INSULATION R-VALUE BETWEEN GARAGE | | | AND SECOND FLOOR? WHAT IS "OTHER" AND WHERE ARE THE | | | DETAILS SPECIFIED UNDER ITEM "C"?. SEC. R101.5.1.1.2 | | | FBC-ENERGY CONSERVATION. | | | | | | PREVIOUS COMMENT: | | | F)REVISE WINDOWS AREA AND OVERHANG DEPTH & SEPARATION | | | TO MATCH PLANS. ALSO, MAKE SURE ALL WINDOWS ARE | | | INCLUDED IN THE CALCULATIONS. SEE PLANS. | | | NOTE: DOORS WITH GLAZING NEED TO BE CONSIDERED IN THE | | | WINDOWS GLAZING SECTION. | | | | | | RESPONSE: | | | WINDOWS INFORMATION DOESN'T MATCH PLANS. SQUARE FOOTAGE | | | OF GLASS DOORS DOESN'T MATCH DOESN'T MATCH SIZES | | | SPECIFIED ON PLANS. SEC. R101.5.1.1.2 FBC-ENERGY | | | CONSERVATION. | | | | | | 2- OK. | | | 3- OK. | | | 4- OK. | | | 5- OK. | | | | | | 6- PRODUCT APPROVALS | | | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 | | | FOR: | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW | | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | | | | | A)SLIDING GLASS DOORS NOA 19-0219.11 SUBMITTED: THE | | | DOORS DON'T MEET THE DESIGN PRESSURES CALCULATED BY THE | | | ENGINEER OF RECORD FOR ALL SLIDING GLASS DOORS SHOWN ON | | | PLANS. NEED TO PROVIDE PRODUCT APPROVAL THAT MEETS OR | | | EXCEEDS THE CALCULATED DESIGN PRESSURES. | | | | | | B)FRENCH DOORS NOA 20-0310.11 SUBMITTED: THE DOORS | | | DON'T MEET THE DESIGN PRESSURES CALCULATED BY THE | | | ENGINEER OF RECORD FOR ALL DOORS SHOWN ON PLANS. NEED | | | TO PROVIDE PRODUCT APPROVAL THAT MEETS OR EXCEEDS THE | | | CALCULATED DESIGN PRESSURES. | | | | | | C)ENTRY DOOR (SOLID WOOD AS SHOWN ON PLANS). REPEAT | | | COMMENT. | | | | | | D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE | | | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION | | | SCHEDULE. SEE CITY SAMPLE. | | | NOTE: SEE COMMENT 6(A) ABOVE. | | | | | | E) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NEED | | | PRODUCT APPROVAL FOR WOOD FRAMED ROOF AND FOR CONCRETE | | | BALCONY. | | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS ARE REQUIRED. | | | REPEAT COMMENT. | | | | | | F) ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | 7- OK. | | | 8- OK. | | | 9- OK. | | | 10-OK. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-07-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-07-05 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-07-05 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2022-07-05 11:21:26 | NEW SINGLE FAMILY RESIDENCE (R3), THIRD BUILDING REVIEW | | | COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #21050545 | | | | | | NOTE: | | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER | | | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID | | | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. | | | CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT | | | THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION | | | BEFORE PERMIT ISSUANCE. | | | | | | | | | | | | ORIGINAL COMMENT: | | | 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | R101.5.1 FBC-ENERGY CONSERVATION. | | | NOTE: NEED TWO SEPARATE ENERGY CALCULATIONS. ONE FOR | | | THE MAIN HOUSE AND ONE FOR THE REAR STRUCTURE. | | | PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL THE | | | REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED | | | AGENT TO AVOID CONFLICT/DELAYS. | | | BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE | | | LEVEL (EPL) DISPLAY CARD SUBMITTED. SEC. R405.4.3 FBC- | | | ENERGY CONSERVATION. | | | | | | RESPONSE: | | | REVISE MAIN HOUSE ENERGY CALCULATIONS: | | | A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, | | | INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND | | | JURISDICTION NUMBER (THIS JURISDICTION IS 604700). SEC. | | | R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | | | B)CEILING INFORMATION ON ITEM #11 OF PAGE 1 DOESN'T | | | MATCH PLANS. COORDINATE WITH ARCHITECT TO AVOID MORE | | | CONFLICTS/DELAYS AND REVISE AS REQUIRED. | | | NOTE: COORDINATE WITH ITEM #9 BELOW. ARCHITECT IS NOT | | | SPECIFYING UNVENTED ATTIC. ARCHITECT NEEDS TO SPECIFY | | | ATTIC VENTILATION AS REQUIRED BY SEC. R806.1 | | | FBC-RESIDENTIAL. | | | | | | C)PROJECT INFORMATION ON PAGE 2 IS INCORRECT. THE MAIN | | | HOUSE IS ONE STORY NOT TWO STORY. REVISE AS REQUIRED. | | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | | | D) REVISE/CLARIFY NUMBER OF OCCUPANTS SPECIFIED ON PAGE | | | TWO UNDER SPACES. | | | THIS IS A 3 BEDROOM HOUSE. CLARIFY WHY LIMITING THE USE | | | OF THIS HOUSE TO ONLY TWO OCCUPANTS?. SEC. R101.5.1.1.2 | | | FBC-ENERGY CONSERVATION. | | | | | | E)REVISE WINDOWS AREA AND OVERHANG DEPTH & SEPARATION | | | TO MATCH PLANS. | | | NOTE: DOORS WITH GLAZING NEED TO BE CONSIDERED IN THE | | | WINDOWS GLAZING SECTION. | | | | | | REVISE REAR STRUCTURE ENERGY CALCULATIONS: | | | A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, | | | INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND | | | JURISDICTION NUMBER (THIS JURISDICTION IS 604700). SEC. | | | R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | | | B)FLOOR INFORMATION ON ITEM #9 ON PAGE ONE DOESN'T | | | MATCH PLANS. NEED INSULATION BETWEEN A/C AND NON A/C | | | AREAS. ALSO, REVISE A/C SQUARE FOOTAGES. SEE PLANS AND | | | REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY | | | CONSERVATION. | | | | | | C)CEILING INFORMATION ON ITEM #11 OF PAGE 1 DOESN'T | | | MATCH PLANS. COORDINATE WITH ARCHITECT TO AVOID MORE | | | CONFLICTS/DELAYS AND REVISE AS REQUIRED. | | | NOTE: ARCHITECT IS NOT SPECIFYING UNVENTED ATTIC. | | | ARCHITECT NEEDS TO SPECIFY ATTIC VENTILATION AS | | | REQUIRED BY SEC. R806.1 FBC-RESIDENTIAL. | | | | | | D)THERE IS NOT KITCHEN IN THIS STRUCTURE. SEE PLANS AND | | | REVISE AS REQUIRED. | | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | | | E)DOORS INFORMATION IS INCORRECT. THERE ARE NO SOLID | | | WOOD DOORS IN THE REAR STRUCTURE. SEE PLANS AND REVISE | | | AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | | | F)REVISE WINDOWS AREA AND OVERHANG DEPTH & SEPARATION | | | TO MATCH PLANS. ALSO, MAKE SURE ALL WINDOWS ARE | | | INCLUDED IN THE CALCULATIONS. SEE PLANS. | | | NOTE: DOORS WITH GLAZING NEED TO BE CONSIDERED IN THE | | | WINDOWS GLAZING SECTION. | | | | | | 2- OK. | | | 3- OK. | | | 4- OK. | | | 5- OK. | | | | | | 6- DEFERRED SUBMITTAL: | | | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 | | | FOR | | | A)ALL WINDOWS AS SPECIFIED ON PLANS. | | | B)ALL EXTERIOR DOORS AS SPECIFIED ON PLANS. | | | C)ENTRY DOOR (SOLID WOOD AS SHOWN ON PLANS). | | | D)OVERHEAD GARAGE DOOR. | | | E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE | | | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION | | | SCHEDULE. SEE CITY SAMPLE. | | | F) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | | | 7- OK. | | | 8- OK. | | | | | | 9- ARCHITECT IS NOT DESIGNING AN UNVENTED ATTIC. | | | COORDINATE WITH ENERGY CALCULATIONS COMMENTS. ARCHITECT | | | NEEDS TO SPECIFY ATTIC/ROOF VENTILATION AS REQUIRED BY | | | SEC. R806.1 FBC-RESIDENTIAL. | | | NOTE: FIRST FLOOR PLAN ON SHEET A-1 SPECIFIES R-20 | | | ICYNENE INSULATION ABOVE GARAGE. IF ARCHITECT IS | | | DESIGNING AN UNVENTED ATTIC, THEN ICYNENE INSULATION | | | MAY BE USED ON MAIN HOUSE AND SECOND FLOOR ROOF ALSO. | | | IF SO, REVISE PLANS/SECTIONS ACCORDINGLY. | | | | | | 10- DRAWINGS M1, M2, E1 NEED ARCHITECT'S ORIGINAL | | | DIGITAL SIGNATURE. DRAWINGS S1 THRU S9 NEED ENGINEER'S | | | ORIGINAL DIGITAL SIGNATURE. | | | ALSO, THE GEOTECHNICAL REPORT AND SURVEY NEED THE | | | DESIGN PROFESSIONAL ORIGINAL SEAL/SIGNATURE. | | | CHAPTER 481, CHAPTER 471 FLORIDA STATUTES. | | | | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-02-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-02-23 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-02-23 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2022-02-23 13:45:16 | NEW SINGLE FAMILY RESIDENCE (R3), SECOND BUILDING | | | REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #21050545 | | | | | | ORIGINAL COMMENT: | | | 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | R101.5.1 FBC-ENERGY CONSERVATION. | | | NOTE: NEED TWO SEPARATE ENERGY CALCULATIONS. ONE FOR | | | THE MAIN HOUSE AND ONE FOR THE REAR STRUCTURE. | | | PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL THE | | | REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED | | | AGENT TO AVOID CONFLICT/DELAYS. | | | BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE | | | LEVEL (EPL) DISPLAY CARD SUBMITTED. SEC. R405.4.3 FBC- | | | ENERGY CONSERVATION. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | ORIGINAL COMMENT: | | | 2- LOT DRAINAGE | | | PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE | | | FOLLOWING: | | | R401.3 FBC-RESIDENTIAL. | | | SEC. 107.2.5 CITY AMENDMENTS. | | | SEC. 110.9 CITY AMENDMENTS. | | | | | | RESPONSE: | | | DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED GRADE | | | ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM ADJACENT | | | PROPERTIES, SPECIALLY ON THE EAST SIDE, WHERE THE GRADE | | | ELEVATION IS LOWER (SEE SURVEY). | | | NOTE: CHECK IF RETAINING WALLS WILL BE REQUIRED. | | | COMPLETE DETAILS WILL BE REQUIRED ON A SEPARATE PERMIT. | | | | | | 3- SHEET A-1: | | | A)OK. | | | B)OK. | | | | | | ORIGINAL COMMENT: | | | C)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE | | | CONSTRUCTION OF THE STAIRWAY SHOWING COMPLIANCE WITH | | | SEC. R311.7 FBC-RESIDENTIAL. PROVIDE COMPLETE | | | INFORMATION FOR RISERS, TREADS, WINDER TREADS, | | | HANDRAILS AND GUARDRAILS (INCLUDING BALCONY GUARDRAIL), | | | STAIRWAY HEADROOM, ETC. | | | | | | RESPONSE: | | | DETAILS ON SHEET A-2.1: | | | (1)STAIR DETAIL PLAN 1/A-2.1 AND DETAIL 3/A-2.1 SHOW | | | KNEE-WALLS ON BOTH SIDES OF STAIRWAY. NEED TO SHOW | | | COMPLIANCE WITH THE HANDRAILS SEC. R311.7.8 | | | FBC-RESIDENTIAL. NOTE: CHECK WITH REQUIRED STAIRWAY | | | WIDTH SEC. R311.7.1 FBC-RESIDENTIAL. | | | (2)WINDERS TO COMPLY WITH SEC. R311.7.5.2.1 | | | FBC-RESIDENTIAL. SPECIFY DIMENSION OF THE NARROW END OF | | | THE WINDER. (6" MIN.) | | | (3)TREAD DIMENSION SPECIFIED ON THE STAIR NOTE AND | | | TREAD DIMENSION SHOWN ON THE THE STAIR DETAIL PLAN | | | 1/A-2.1 DON'T MATCH. REVISE AS REQUIRED TO MATCH. | | | | | | | | | ORIGINAL COMMENT: | | | D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR | | | DWELLING- GARAGE FIRE SEPARATION AS REQUIRED BY SEC. | | | R302.6 FBC-RESIDENTIAL. | | | | | | RESPONSE: | | | FLOOR CEILING ASSEMBLY FIRE RATING NEEDS TO COMPLY WITH | | | TABLE R302.6 FBC-RESIDENTIAL. | | | | | | E) OK. | | | | | | ORIGINAL COMMENT: | | | F) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR | | | FIREBLOCKING IN ALL THE AREAS REQUIRED BY SEC. R302.11 | | | FBC-RESIDENTIAL. | | | | | | RESPONSE: | | | STAIR DETAILS ON SHEET A-2.1 REFER TO DRAFSTOPPING. | | | DRAFSTOPPING AND FIREBLOCKING ARE TWO SEPARATE | | | REQUIREMENTS. SEE SEC. R302.12 FBC-RESIDENTIAL AND SEC. | | | R302.11 FBC-RESIDENTIAL. REVISE DETAILS AS REQUIRED AND | | | PROVIDE FIREBLOCKING AT TOP OF STAIRS AS REQUIRED BY | | | SEC. R302.11(3) FBC-RESIDENTIAL. | | | | | | ORIGINAL COMMENT: | | | 4- SHEET A-2: | | | LOW SLOPE ROOFS: PROVIDE DETAILS AND SPECIFICATIONS FOR | | | OVERFLOW DRAINS AND SCUPPERS AS REQUIRED BY SEC. | | | R903.4.1 FBC-RESIDENTIAL. | | | PROVIDE DETAILS AND SPECIFY LOCATION ON ROOF. | | | | | | RESPONSE: | | | NEED TO SPECIFY THE OVERFLOW SCUPPERS COMPLYING WITH | | | R903.4.1 FBC-RESIDENTIAL. OVERFLOW SCUPPERS ARE LOCATED | | | NOT LESS THAN2" ABOVE THE FINISH ROOF. | | | NOTE: OVERFLOW SCUPPERS ARE ADDITIONAL TO THE REGULAR | | | SCUPPERS LOCATED AT THE LOWEST POINT OF THE ROOF. | | | | | | ORIGINAL COMMENT: | | | 5- PARAPET WALL DETAILS: PROVIDE COMPLETE DETAILS AND | | | SPECIFICATIONS FOR ATTACHMENT OF 2X8 WOOD-NAILER AND | | | WALL COPING. STRUCTURAL DETAILS DON'T PROVIDE THIS | | | INFORMATION. | | | SEC. R301.1 FBC-RESIDENTIAL. | | | | | | RESPONSE: | | | DETAILS ON SHEET A-2 STILL DON'T SPECIFY FASTENING OF | | | 2X P.T. WOOD NAILER TO TOP OF WALL. | | | | | | ORIGINAL COMMENT: | | | 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL): | | | A)ALL WINDOWS AS SPECIFIED ON PLANS. | | | B)ALL EXTERIOR DOORS AS SPECIFIED ON PLANS. | | | C)ENTRY DOOR. | | | D)OVERHEAD GARAGE DOOR. | | | E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE | | | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION | | | SCHEDULE. SEE CITY SAMPLE. | | | F) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | | | RESPONSE: | | | NO RESPONSE ON THIS ITEM. DEFERRED SUBMITTAL: PRODUCT | | | APPROVALS CAN BE SUBMITTED LATER AFTER THE PERMIT IS | | | ISSUED. | | | | | | ORIGINAL COMMENT: | | | 7- PROVIDE STRUCTURAL BUCK DETAIL AND FASTENING | | | SPECIFICATIONS FOR: | | | A) OK. | | | | | | B) EXTERIOR DOORS. | | | | | | RESPONSE: | | | 2X4 STRUCTURAL BUCK SPECIFIED ON DETAIL 8/A-2.1 ON | | | SHEET A-2 DOESN'T PROVIDE DOOR FRAME FULL SUPPORT AS | | | REQUIRED BY SEC. R609.7.2.1 FBC-RESIDENTIAL. REVISE AS | | | REQUIRED. | | | | | | ORIGINAL COMMENT: | | | 8- A SEPARATE PERMIT APPLICATION IS REQUIRED FOR EACH | | | INDEPENDENT STRUCTURE. THIS IS TO FACILITATE | | | INSPECTIONS AND RECORDS RETENTION. PROVIDE A SEPARATE | | | PERMIT APPLICATION FOR THE REAR STRUCTURE. SAME PLANS | | | CAN BE USED. NO NEED TO SUBMIT SEPARATE PLANS. JUST ADD | | | THE PERMIT APPLICATION. | | | SEC. 107.2.1.3 CITY AMENDMENTS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT DONE. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-07-08 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-07-08 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-07-08 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2021-07-08 16:54:02 | NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW | | | COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #21050545 | | | | | | 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | R101.5.1 FBC-ENERGY CONSERVATION. NOTE: NEED TWO | | | SEPARATE ENERGY CALCULATIONS. ONE FOR THE MAIN HOUSE | | | AND ONE FOR THE REAR STRUCTURE. | | | PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL THE | | | REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED | | | AGENT TO AVOID CONFLICT/DELAYS. | | | BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE | | | LEVEL (EPL) DISPLAY CARD SUBMITTED. SEC. R405.4.3 FBC- | | | ENERGY CONSERVATION. | | | | | | 2- LOT DRAINAGE | | | PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE | | | FOLLOWING: | | | R401.3 FBC-RESIDENTIAL. | | | SEC. 107.2.5 CITY AMENDMENTS. | | | SEC. 110.9 CITY AMENDMENTS. | | | | | | 3- SHEET A-1: | | | A)BEDROOMS #2 AND #3 SLIDING WINDOWS (4'-0"X6'-0") | | | DON'T COMPLY WITH THE MIN. WINDOW CLEAR WITH REQUIRED | | | BY SEC. R310.2.1 FBC-RESIDENTIAL FOR EMERGENCY EGRESS. | | | REVISE AS REQUIRED TO COMPLY OR PROVIDE MANUFACTURER'S | | | CUT SHEETS SHOWING THAT THIS WINDOW SIZE COMPLIES WITH | | | ALL THE EGRESS REQUIREMENTS. | | | | | | B)WINDOW AND DOOR WIND PRESSURES DON'T MATCH WIND | | | PRESSURES SPECIFIED ON SHEET S9. REVISE AS REQUIRED TO | | | MATCH. | | | SEC. 107.2.1 CITY AMENDMENTS. | | | NOTE: COORDINATE PRODUCT APPROVALS LISTED IN THE | | | WINDOW/DOOR SCHEDULE WITH PRODUCT APPROVALS TO BE | | | SUBMITTED TO AVOID CONFLICTS/DELAYS. | | | | | | C)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE | | | CONSTRUCTION OF THE STAIRWAY SHOWING COMPLIANCE WITH | | | SEC. R311.7 FBC-RESIDENTIAL. PROVIDE COMPLETE | | | INFORMATION FOR RISERS, TREADS, WINDER TREADS, | | | HANDRAILS AND GUARDRAILS (INCLUDING BALCONY GUARDRAIL), | | | STAIRWAY HEADROOM, ETC. | | | | | | D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR | | | DWELLING- GARAGE FIRE SEPARATION AS REQUIRED BY SEC. | | | R302.6 FBC-RESIDENTIAL. | | | | | | E) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR | | | UNDER STAIR PROTECTION AS REQUIRED BY SEC. R302.7 | | | FBC-RESIDENTIAL. | | | | | | F) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR | | | FIREBLOCKING IN ALL THE AREAS REQUIRED BY SEC. R302.11 | | | FBC-RESIDENTIAL. | | | | | | 4- SHEET A-2: | | | LOW SLOPE ROOFS: PROVIDE DETAILS AND SPECIFICATIONS FOR | | | OVERFLOW DRAINS AND SCUPPERS AS REQUIRED BY SEC. | | | R903.4.1 FBC-RESIDENTIAL. | | | PROVIDE DETAILS AND SPECIFY LOCATION ON ROOF. | | | | | | 5- PARAPET WALL DETAILS: PROVIDE COMPLETE DETAILS AND | | | SPECIFICATIONS FOR ATTACHMENT OF 2X8 WOOD-NAILER AND | | | WALL COPING. STRUCTURAL DETAILS DON'T PROVIDE THIS | | | INFORMATION. | | | SEC. R301.1 FBC-RESIDENTIAL. | | | | | | 6- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL): | | | A)ALL WINDOWS AS SPECIFIED ON PLANS. | | | B)ALL EXTERIOR DOORS AS SPECIFIED ON PLANS. | | | C)ENTRY DOOR. | | | D)OVERHEAD GARAGE DOOR. | | | E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE | | | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION | | | SCHEDULE. SEE CITY SAMPLE. | | | F) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | | | 7- PROVIDE STRUCTURAL BUCK DETAIL AND FASTENING | | | SPECIFICATIONS FOR: | | | A) OVERHEAD GARAGE DOOR. | | | B) EXTERIOR DOORS. | | | C)WINDOWS. | | | SEC. R301.1 FBC-RESIDENTIAL AND R609.7.2.1 | | | FBC-RESIDENTIAL. | | | | | | 8- A SEPARATE PERMIT APPLICATION IS REQUIRED FOR EACH | | | INDEPENDENT STRUCTURE. THIS IS TO FACILITATE | | | INSPECTIONS AND RECORDS RETENTION. PROVIDE A SEPARATE | | | PERMIT APPLICATION FOR THE REAR STRUCTURE. SAME PLANS | | | CAN BE USED. NO NEED TO SUBMIT SEPARATE PLANS. JUST ADD | | | THE PERMIT APPLICATION. | | | SEC. 107.2.1.3 CITY AMENDMENTS. | | | | | | 9- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW. | | | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S | | | OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS | | | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. VALUATION WAS | | | UPDATED TO $240,342. THE PERMIT FEE BALANCE IS | | | $4,991.82. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2022-09-16 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-09-16 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-09-16 |
Time |
16:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2022-06-02 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-02 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-06-02 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2022-06-02 11:06:29 | ELECTRIC REVIEW FAILED | | | 1) PLEASE DETAIL SMOKE/CARBON ALARM AT FIRST FLOOR OF | | | GARAGE STRUCTURE. FBC 553.883 | | | 2) IT APPEARS GUEST HOUSE/GARAGE DETAILS MORE THAN ONE | | | MULTI WIRE CIRCUIT/FEEDER NOT IN COMPLIANCE WITH NEC | | | 225.30. PLEASE INDICATE THAT GUEST HOUSE HAS SUBPANEL | | | FOR GUEST HOUSE LOADS. AS PER NEC 225.30. IN ADDITION, | | | PROVIDE A GROUNDING ELECTRODE SYSTEM AT SEPARATE | | | BUILDING. NEC 250.32 | | | 3) PLEASE LOCATE ELECTRIC PANEL ON FLOOR PLAN TO BE IN | | | COMPLIANCE WITH NEC 110.26 (A)(1) | | | 4) PLEASE DETAIL THE REQUIRED RECEPTACLES AT, MAIN | | | HOUSE AND GARAGE, NEXT TO ALL OUTSIDE AIR CONDITIONING | | | EQUIPMENT AS REQUIRED BY NEC 210.63 | | | 5) PLEASE DETAIL THE REQUIRED OUTDOOR RECEPTACLES AS | | | REQUIRED PER NEC 210.52(E)(3) AND 210.52 (G)(2) AT | | | GARAGE | | | 6) PLEASE DETAIL THE REQUIRED RECEPTACLE AT THE END OF | | | KITCHEN PENINSULAR AS REQUIRED PER NEC 210.52 (C)(3) | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-02-08 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-02-08 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-02-08 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2022-02-08 10:45:55 | ELECTRICAL REVIEW FAILED | | | 1) PLAN STILL DETAILS INCORRECT SIZED #3 CU CONDUCTORS | | | TO 150-AMP PANEL "A" NEC 310.15(B) | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-06-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-06-04 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-06-04 |
Time |
09:05 |
Sent To |
|
|
| Notes |
| 2021-06-04 09:17:33 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | RISER HAS 3 #6 AND A #10 TO PANEL A? | | | | | | LOAD CALCULATION TO INCLUDE AC OR HEAT, 5KW FOR DRYER, | | | 1.5KW LAUNDRY CKT REQUIRED PER 220 NEC | | | | | | KITCHEN COUNTER OUTLETS NEED TO BE CHECKED FOR CORRECT | | | NUMBER OF REQUIRED OUTLETS. | | | | | | INTERSYSTEM BONDING STRIP PER 250.94 REQUIRED. | | | | | | SMOKE ALARM REQUIRE ON DIRST FLOOR LEADING UP TO SECOND | | | FLOOR ROOM. | | | | | | GENERAL OUTLET SPACING NOT MEETING THE REQUIREMENTS OF | | | 210.52 (MSTR BD RM, LIVING RM, DINING RM, SITTING AREA, | | | KITCHEN COUNTER) |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
4 |
Status |
P |
Date |
2022-11-30 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-11-30 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-11-30 |
Time |
15:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-06-02 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-06-02 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-06-02 |
Time |
10:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-02-04 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-02-04 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-02-04 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2022-02-04 14:37:45 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | PLEASE REVISE FRONT PARAPET WALL TO BE 8 INCHES LOWER | | | AND PROVIDE A SAMPLE OF THE TILE THAT WILL BE ON THE | | | FRONT | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-07-14 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2021-07-14 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2021-07-14 |
Time |
08:04 |
Sent To |
|
|
| Notes |
| 2021-07-14 08:06:44 | NEW CONSTRUCTION IN A HISTORIC DISTRICT REQUIRES HPB | | | APPROVAL VIA A COA APPLICATION. NEEDS TO MET DESIGN | | | GUIDELINES AND LOT COVERAGE AND FAR. | | | | | | QUESTIONS, CONTACT: FRIEDERIKE MITTNER, CITY HISTORIC | | | PRESERVATION PLANNER | | | (561) 822-1457 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2022-12-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-12-05 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-10-25 |
Time |
16:05 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-09-29 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-09-29 |
Time |
11:23 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-09-16 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-09-16 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-08-24 |
Time |
16:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-07-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-07-05 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-05-13 |
Time |
16:01 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-02-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-02-23 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-01-26 |
Time |
08:39 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-07-14 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-07-14 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-05-21 |
Time |
10:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2022-12-16 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-12-16 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-12-06 |
Time |
12:04 |
Sent To |
|
|
| Notes |
| 2022-12-16 10:19:11 | RECEIPT MU-2022-054415 - $1945.04 PAID | | 2022-12-06 12:05:07 | 12/6/22 EMAILED IMPACT FOR REVIEW-AO |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-08-29 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-08-29 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2022-08-29 13:40:42 | IMPACT FEES | | | | | | PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR | | | IMPACT FEE ASSESSMENT. | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2021-07-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-07-09 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-07-09 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2021-07-09 09:22:07 | IMPACT FEES | | | | | | PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR | | | IMPACT FEE ASSESSMENT. | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-29 |
Time |
06:20 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-29 |
Time |
06:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2022-05-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-20 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-20 |
Time |
15:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2022-02-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-02-02 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-02-02 |
Time |
17:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-06-04 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-06-04 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-06-04 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2021-06-04 13:25:39 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21050545 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE A COMPLETE MECHANICAL DRAWING | | | INCLUDING ALL DUCT WORK, SIZES OF DUCTWORK, RETURN AIR | | | PATH FROM ALL ROOMS BACK TO THE AHU, DRYER DUCT | | | TERMINATION LOCATION, CONDENSATION TERMINATION | | | LOCATIONS. PLEASE ALSO PROVIDE DETAILS OF RANGE AND IF | | | A HOOD IS INSTALLED OVER IT. IF A HOOD IS INSTALLED IS | | | IT EXHAUSTED TO THE OUTDOORS? FBC 107.2.1 | | | | | | 2) PLEASE PROVIDE INFORMATION FOR THE BBQ ON THE PATIO, | | | DO THE INSTRUCTIONS REQUIRE A HOOD BECAUSE THE BBQ IS | | | UNDER THE PATIO STRUCTURE? | | | | | | 3) IS THE GARAGE/STORAGE OPEN TO THE SECOND FLOOR | | | SLEEPING? HOW IS THIS ENERGY EFFICIENT? | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2022-08-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-26 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-26 |
Time |
17:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2022-05-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-05-19 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-05-19 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2022-05-19 11:32:04 | 3RD REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 21050545 | | | 5/19/22 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) 3RD REQUEST- SHEET P-1: PLEASE REVIEW DEFINITIONS OF | | | BUILDING DRAIN AND BUILDING SEWER- SEC. 202 FBC RES AND | | | CORRECT THE PLANS TO SHOW THE LOCATIONS OF THE REQUIRED | | | CLEANOUTS AT EACH DRAIN/SEWER JUNCTION- SEE SECS. | | | P3005.2.3 & P3005.2.3 FBC RES. | | | | | | 2) DUE TO A CHANGE IN PROCESS, THE A POTABLE WATER | | | SERVICE BACKFLOW PERMIT IS REQUIRED TO BE SUBMITTED | | | PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS | | | APPLICABLE). YOU CAN SUBMIT AN APPLICATION ?TBD? (TO BE | | | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY | | | EMAILING A COMPLETED PERMIT APPLICATION TO | | | [email protected] . YOU WILL RECEIVE INSTRUCTIONS | | | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND | | | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS | | | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES | | | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE | | | PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL | | | CHANGE THE REVIEW STATUS TO PASS. | | | | | | 3) PREVIOUS REVIEW COMMENT- TWO DWELLINGS ON THE SAME, | | | OR CONSTRUCTION OF A COMMERCIAL BUILDING ON THE | | | PROPERTY WILL REQUIRE INSTALLATION OF A POTABLE WATER | | | SERVICE BACKFLOW PREVENTER DEVICE IN ACCORDANCE WITH | | | THE WPB DEPT. OF UTILITIES CROSS-CONNECTION CONTROL | | | MANUAL. PLEASE NOTE A SEPARATE PERMIT WILL BE REQUIRED | | | TO INSTALL A REDUCED PRESSURE ZONE (RPZ) BACKFLOW AT | | | THE WATER METER- SECS. C & E WPB CROSS-CONNECTION | | | MANUAL. | | | A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A | | | SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW | | | PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC. | | | 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE | | | TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT | | | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. | | | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS | | | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-02-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-02-01 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-02-01 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2022-02-01 14:45:52 | 2ND REVIEW FBC-2020 RES. | | | PERMIT- 21050545 | | | 2/1/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FORM THE | | | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN | | | CAPS. | | | | | | 1) FAILED. SHEET A2: REFER TO SECTION 903.4.1 & 903.4.2 | | | FBC RES AND SHOW OVERFLOW SCUPPER LOCATIONS. PROVIDE | | | SIZING CALCULATIONS FOR BOTH THE PRIMARY AND THE | | | OVERFLOW SCUPPERS AND PROVIDE CONSTRUCTION DETAILS. | | | REFER TO SECTIONS 1106.1- 1108.3 FBC P FOR FURTHER | | | REQUIREMENTS. THE OVERFLOW SCUPPERS WERE NOT PROVIDED | | | AS REQUIRED. | | | | | | 2) FAILED. P1: CLEANOUTS ARE REQUIRED AT THE JUNCTIONS | | | OF THE BUILDING DRAINS AND SEWER LINE AND SHALL BE | | | LOCATED AT THE JUNCTIONS OR A MAXIMUM OF 10 FT. | | | DEVELOPED LENGTH OF PIPING UPSTREAM OF THE JUNCTIONS- | | | SECTION- P3005.2.3 FBC RES. PLEASE NOTE THE DEFINITION | | | OF BUILDING DRAIN: THE LOWEST PIPING THAT COLLECTS THE | | | DISCHARGE FROM ALL OTHER DRAINAGE PIPING INSIDE THE | | | HOUSE AND EXTENDS 30 INCHES IN DEVELOPED LENGTH OF | | | PIPE, BEYOND THE EXTERIOR WALLS AND CONVEYS THE | | | DRAINAGE TO THE BUILDING SEWER. A) THE CLEANOUTS WERE | | | NOT PROVDED AS REQUIRED. B) THE MASTER BATH DRAIN AND | | | VENT SYSTEM IS NON-COMPLIANT. C) VENTS ARE MISSING FOR | | | THE KITCHEN SINK, WASHING MACHINE AND FLOOR DRAIN. | | | PLEASE REFER TO SECTION P3108.1- P3108.3 FBC RES: | | | DESIGN THE MASTER BATH WET VENT SIMILAR TO THE 1ST | | | FLOOR BATH VENT WITH ALL FIXTURE DRAINS CONNECTING TO | | | ONE BRANCH EXITING THE BUILDING TO THE SEWER DRAIN. THE | | | VENT FOR THE SYSTEM SHALL BE A DRY VENT LOCATED SO THAT | | | NOT MORE THAN ONE FIXTURE IS LOCATED UPSTREAM OF THE | | | VENT. CONCERNING RTHE KITCHEN SINK AND DISHWASHER, AN | | | AIR ADMITTANCE VALVE CAN BE INSTALLED IF THERE IS NO | | | MEANS OF GETTING A COMPLIANT VENT-TO RIDGE- SEE SECS. | | | P3106, P3107, AND P3114 FBC RES. CONCERNING THE WASHING | | | MACHINE AND FLOOR DRAIN, A VENT TO RIDGE FOR THE | | | WASHING MACHINE FIXTURE DRAIN CAN SERVE AS A COMMON | | | VENT FOR BOTH FIXTURES- SEC. P3106 FBC RES. | | | | | | NEW COMMENT. | | | | | | 1) PLEASE NOTE THAT TWO DWELLINGS ON THE SAME LOT WILL | | | REQUIRE INSTALLATION OF A POTABLE WATER SERVICE | | | BACKFLOW PREVENTER DEVICE IN ACCORDANCE WITH THE WPB | | | DEPT. OF UTILITIES CROSS-CONNECTION CONTROL MANUAL. | | | PLEASE NOTE A SEPARATE PERMIT WILL BE REQUIRED TO | | | INSTALL A REDUCED PRESSURE ZONE (RPZ) BACKFLOW AT THE | | | WATER METER- CHAPTER C (PAGE 12 WPB CROSS-CONNECTION | | | MANUAL. | | | A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A | | | SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW | | | PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC. | | | 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE | | | TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT | | | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. | | | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS | | | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-06-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-06-10 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-06-09 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2021-06-10 07:54:19 | 1ST REVIEW FBC-2020 RES. | | | PERMIT- 21050545 | | | 6/9/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A2: REFER TO SECTION 903.4.1 & 903.4.2 FBC RES | | | AND SHOW OVERFLOW SCUPPER LOCATIONS. PROVIDE SIZING | | | CALCULATIONS FOR BOTH THE PRIMARY AND THE OVERFLOW | | | SCUPPERS, AND PROVIDE CONSTRUCTION DETAILS. REFER TO | | | SECTIONS 1106.1- 1108.3 FBC P FOR FURTHER REQUIREMENTS. | | | | | | 2) P1: CLEANOUTS ARE REQUIRED AT THE JUNCTIONS OF THE | | | BUILDING DRAINS AND SEWER LINE AND SHALL BE LOCATED AT | | | THE JUNCTIONS OR A MAXIMUM OF 10 FT. DEVELOPED LENGTH | | | OF PIPING UPSTREAM OF THE JUNCTIONS- SECTION- P3005.2.3 | | | FBC RES. PLEASE NOTE THE DEFINITION OF BUILDING DRAIN: | | | THE LOWEST PIPING THAT COLLECTS THE DISCHARGE FROM ALL | | | OTHER DRAINAGE PIPING INSIDE THE HOUSE AND EXTENDS 30 | | | INCHES IN DEVELOPED LENGTH OF PIPE, BEYOND THE EXTERIOR | | | WALLS AND CONVEYS THE DRAINAGE TO THE BUILDING SEWER. | | | | | | 3) P1: PROVIDE A VENT FOR THE LAVATORY SINK SHOWN AT | | | THE UPSTREAM LOCATION IN THE ISOMETRIC DRAWING- SECTION | | | P3101.2.1 FBC P. | | | | | | 4) P1: THE PLUMBING FLOOR PLAN SHOWS A 2-INCH FIXTURE | | | BRANCH FOR THE WASHING MACHINE HOWEVER A 3-INCH PIPE IS | | | REQUIRED PER SECTION 406.2 FBC P. (THE ISOMETRIC | | | DRAWING APPEARS TO SHOW A 3-INCH). | | | | | | 5) P2: THE EXPANSION TANK FOR THE WATER HEATER LOCATED | | | UPSTREAM OF THE CHECK VALVE APPEARS TO BE IN AN | | | INCORRECT LOCATION. PLEASE LOCATE THE TANK IN | | | ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION | | | GUIDELINES- SECTIONS P2801.3 & M2005.1 FBC RES. | | | | | | 6) P2: PROVIDE THE EFFICIENCY RATING OF THE WATER | | | HEATER IN THE SCHEDULE- TABLE C404.2 FBC EC. PLEASE | | | NOTE THAT THE EPL DISPLAY CARD DOES NOT PROVIDE A | | | RATING FOR THE WATER HEATER, ANC COMPLETE ENERGY | | | CALCULATIONS HAVE NOT BEEN SUBMITTED- SECTION R101.5 | | | FBC EC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
5 |
Status |
N |
Date |
2022-12-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-12-05 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-12-05 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2022-12-05 10:49:00 | ROOFING DEFERRED SUBMITTAL: | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: PROVIDE COMPLETE INFORMATION PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL): | | | | | | A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS ARE REQUIRED. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
N |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-08-29 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-08-29 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2022-08-29 13:44:35 | ROOFING DEFERRED SUBMITTAL: | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: PROVIDE COMPLETE INFORMATION PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL): | | | | | | A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS ARE REQUIRED. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2022-07-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-07-05 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-07-05 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2022-07-05 10:47:04 | ROOFING DEFERRED SUBMITTAL: | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: PROVIDE COMPLETE INFORMATION PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL): | | | | | | A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS ARE REQUIRED. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2022-02-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-02-23 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-02-23 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2022-02-23 13:47:09 | ROOFING REVIEW: | | | | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL): | | | | | | A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS ARE REQUIRED. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-07-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-07-09 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-07-09 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2021-07-09 09:23:48 | ROOFING REVIEW: | | | | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL): | | | | | | A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS ARE REQUIRED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
6 |
Status |
P |
Date |
2022-11-16 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-11-16 |
Time |
05:51 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-09-29 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-09-29 |
Time |
11:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
F |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-08-29 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-08-29 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2022-08-29 13:42:11 | SIGNATURE REVIEW COMMENTS. | | | | | | 1- THE GEOTECHNICAL REPORT NEEDS THE DESIGN | | | PROFESSIONAL ORIGINAL SEAL/SIGNATURE. CHAPTER 471 | | | FLORIDA STATUTES. | | | REPEAT COMMENT. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | | | | THE MECHANICAL DOCUMENTS HAVE A COPY OF THE DIGITAL | | | SIGNATURE OF THE DESIGNER.ME | | 2022-08-29 06:21:35 | MECHANICAL DIGITAL SIGNATURES APPROVED ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2022-07-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-07-05 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-07-05 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2022-07-05 13:01:24 | SIGNATURE REVIEW COMMENTS. | | | | | | 1- DRAWINGS M1, M2, E1 NEED ARCHITECT'S ORIGINAL | | | DIGITAL SIGNATURE. DRAWINGS S1 THRU S9 NEED ENGINEER'S | | | ORIGINAL DIGITAL SIGNATURE. | | | ALSO, THE GEOTECHNICAL REPORT AND SURVEY NEED THE | | | DESIGN PROFESSIONAL ORIGINAL SEAL/SIGNATURE. | | | CHAPTER 481, CHAPTER 471 FLORIDA STATUTES. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | | | 2022-05-20 15:32:29 | THE MECHANICAL DOCUMENTS HAVE A COPY OF THE DIGITAL | | | SIGNATURE OF THE DESIGNER.ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-02-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-02-23 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-02-23 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2022-02-23 13:58:50 | SIGNATURE REVIEW COMMENTS. | | | | | | 1- DOCUMENTS PREPARED BY AN ARCHITECT, ENGINEER OR | | | SURVEYOR AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A WET SEAL | | | AND SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A | | | DIGITAL SIGNATURE. | | | | | | ARCHITECTURAL, ELECTRICAL, PLUMBING, MECHANICAL AND | | | STRUCTURAL DRAWINGS NEED THE DESIGN PROFESSIONAL | | | ORIGINAL SEAL/SIGNATURE. | | | ALSO, THE GEOTECHNICAL REPORT AND SURVEY NEED THE | | | DESIGN PROFESSIONAL ORIGINAL SEAL/SIGNATURE. | | | CHAPTER 481, CHAPTER 471 AND CHAPTER 472 FLORIDA | | | STATUTES. | | | | | | 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR | | | DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL | | | WET SEAL AND SIGNATURE TO: | | | | | | BUILDING DIVISION, FIRST FLOOR | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS ST | | | WEST PALM BEACH, FL 33401 | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-07-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-07-09 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-07-09 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2021-07-09 09:37:54 | SIGNATURE REVIEW COMMENTS. | | | | | | 1- DOCUMENTS PREPARED BY AN ARCHITECT, ENGINEER OR | | | SURVEYOR AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A WET SEAL | | | AND SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A | | | DIGITAL SIGNATURE. | | | | | | ARCHITECTURAL, ELECTRICAL, PLUMBING, MECHANICAL AND | | | STRUCTURAL DRAWINGS NEED THE DESIGN PROFESSIONAL | | | ORIGINAL SEAL/SIGNATURE. | | | ALSO, THE GEOTECHNICAL REPORT AND SURVEY NEED THE | | | DESIGN PROFESSIONAL ORIGINAL SEAL/SIGNATURE. | | | CHAPTER 481, CHAPTER 471 AND CHAPTER 472 FLORIDA | | | STATUTES. | | | | | | 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR | | | DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL | | | WET SEAL AND SIGNATURE TO: | | | | | | BUILDING DIVISION, FIRST FLOOR | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS ST | | | WEST PALM BEACH, FL 33401 | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
P |
Date |
2022-12-05 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-12-05 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-12-05 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2022-12-05 13:03:16 | ZONING HAS PASSED, HOWEVER TREE ALTERATION PERMIT STILL | | | REQUIRED. PLEASE APPLY FOR PERMIT PRIOR TO ANY WORK | | | BEING DONE ON SITE. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
F |
Date |
2022-11-30 |
|
|
Cont ID |
|
| Sent By |
amhmilt |
Date |
2022-11-30 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-11-30 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2022-11-30 15:07:20 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | LANDSCAPE PERMIT COMMENT SATISFIED, HOWEVER, TREE | | | ALTERATION PERMIT STILL REQUIRED. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-08-29 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-08-29 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2022-08-29 16:28:37 | 8/29/2022 FAILED | | | | | | 1. PREVIOUS COMMENT NOT ADDRESSED-- PLEASE APPLY FOR | | | LANDSCAPE PERMIT | | | 2. TREE ALTERNATION PERMIT IS REQUIRED FOR THE MANGO | | | TRESS SHOWN ON SURVEY | | | | | | 3.DETACHED STRUCTURE IS TO FOLLOW PRIMARY STRUCTURE | | | SETBACKS DUE TO THE BUILDING SEPERATION REQUIREMENT NOT | | | MET | | | PER CODE SECTION 94-305 (B) | | | A. THE TOTAL FLOOR AREA OF ALL ROOFED ACCESSORY | | | BUILDINGS ON A PROPERTY SHALL NOT EXCEED 75 PERCENT OF | | | THE GROSS FLOOR AREA OF THE PRIMARY STRUCTURE WITH A | | | MAXIMUM FLOOR AREA OF 1,000 SQUARE FEET. | | | | | | B. SETBACKS: 25 FEET FROM FRONT PROPERTY LINE, 5 FEET | | | FROM THE SIDE LOT LINES, AND A 5 FEET MINIMUM FROM THE | | | REAR PROPERTY LINE | | | | | | C.ACCESSORY STRUCTURES COVERED WITH A SOLID ROOF SHALL | | | BE LOCATED NO CLOSER THAN SIX FEET TO THE PRINCIPAL | | | STRUCTURE. ACCESSORY STRUCTURES LESS THAN SIX FEET FROM | | | THE PRIMARY STRUCTURE MUST MEET THE PRIMARY STRUCTURE | | | SETBACKS | | | | | | 4. PLEASE SHOW FLOOR PLANS OF ACCESSORY STRUCTURE WITH | | | SQFT NOT EXCEEDING 75% OR PRIMARY BUILIDING OR | | | 1,000SQFT | | | | | | 5.PLEASE NOTE: | | | A. ACCESSORY STRUCTURE WILL NOT BE PERMITTED TO BE A | | | RENTAL UNIT PER THE ZONING SF7 | | | C. KITCHEN WITH STOVE/OVEN IS NOT PERMITTED. | | | | | | 6.SEPARATE PERMIT REQUIRED FOR: | | | FENCE/WALL, AWNINGST, GENERATOR, MECHANICAL/AC/POOL | | | EQUIPMENT, DRIVEWAY, POOL, IRRIGATION, LANDSCAPE, | | | OTHER. | | | | | | | | | PLEASE EMAIL ME WITH RESPONSE OR PROVIDE NOTE ON PLANS | | | TO WHAT ACCESSORY STRUCTURE WILL BE UTILIZED AS | | | | | | **** REVIEWD BY **** | | | VALENTINA BROGLIA | | | ASSOCIATE PLANNER | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2022-06-02 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-06-02 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-06-02 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2022-06-02 10:14:02 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | SEPARATE LANDSCAPE PERMIT IS REQUIRED AND MUST BE | | | SUBMITTED FOR ZONING APPROVAL TO MOVE FORWARD. | | | | | | DRIVEWAYS, MECHANICAL EQUIPMENT, FENCES AND LANDSCAPING | | | ALL APPROVED UNDER SEPARATE PERMITS. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-02-04 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-02-04 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-02-04 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2022-02-04 14:50:06 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | PLEASE FILE FOR A LANDSCAPE PERMIT (PLANS DO NOT NEED | | | TO BE COMPLETE TO FILE FOR PERMIT) | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2021-07-06 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2021-07-06 |
Time |
|
Rev Time |
|
| Received By |
rthermid |
Date |
2021-07-06 |
Time |
|
Sent To |
I |
|
| Notes |
| 2021-07-06 07:56:45 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 7/6/2021 | | | ________________________________________ | | | | | | REVIEW STATUS: PASSED WITH PROVISOS | | | ________________________________________ | | | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | | PROVISOS: | | | | | | 1. A SEPERATE PERMIT IS NEEDED FOR EACH ADDITIONAL | | | STRUCTURE ON THE PROPERTY SUBJECT TO ZONING APPROVAL. | | | 2. ADDITIONALLY, A RIGHT-OF-WAY PERMIT WILL NEED TO BE | | | ACQUIRED FROM THE CITY?S ENGINEERING DEPARTMENT | | | (561.494.1040), FOR THE PROPOSED APPROACH EXTENSION. | | | 3. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND | | | LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION | | | 94-442(2)(A): GENERAL LANDSCAPING STANDARDS FOR | | | SINGLE-FAMILY DWELLING UNITS SHALL BE AS FALLOWS: | | | | | | A. SINGLE-FAMILY DWELLING UNITS. FOR SINGLE-FAMILY | | | DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING OR FRUIT | | | TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF | | | OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY | | | DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR | | | EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF. | | | | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | RAFAELA THERMIDOR, ASSOCIATE PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561-822-1443 | | | TTY: 800.955.8771 | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|