Plan Review Details - Permit 21050536
Plan Review Stops For Permit 21050536
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-08-11 Cont ID  
Sent By rmcphers Date 2021-08-11 Time 09:35 Rev Time 0.00
Received By rmcphers Date 2021-08-11 Time 09:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-24 Cont ID  
Sent By rmcphers Date 2021-06-24 Time 08:00 Rev Time 0.00
Received By rmcphers Date 2021-06-23 Time 15:37 Sent To  
Notes
2021-06-24 07:59:59REPLACE DOORS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED =
 1) PLEASE SHOW THE WIND DESIGN PRESSURES FOR THE
 OPENINGS FBC 1609.1.1
 2) PLEASE SHOW THE WIND DESIGN DATA USED FOR DESIGN FBC
 1603.1.4
 3) PRODUCT APPROVAL (15-0826.23) HAS EXPIRED - PLEASE
 PROVIDE AN UPDATED VERSION.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-06-25 Cont ID  
Sent By jleahy Date 2021-06-25 Time 09:57 Rev Time 0.00
Received By jleahy Date 2021-06-25 Time 07:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-05 Cont ID  
Sent By pleduc Date 2021-08-05 Time   Rev Time 0.00
Received By pleduc Date 2021-08-05 Time 09:34 Sent To  
Notes
2021-08-05 09:36:58FIRE PROVISO:
  
 ENSURE NEW TANK DOES NOT BLOCK EXISTING
 FIRE SPRINKLER HEAD PROTECTION.
  
 FIRE SPRINKLER WORK, INCLUDING DEMO, SHALL BE DONE
 UNDER SEPARATE PERMIT & SHOP DRAWINGS
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-06-25 Cont ID  
Sent By pleduc Date 2021-06-25 Time   Rev Time 0.00
Received By pleduc Date 2021-06-25 Time 12:02 Sent To  
Notes
2021-06-25 14:25:37FIRE PROVISO:
  
 ENSURE NEW TANK DOES NOT BLOCK EXISTING
 FIRE SPRINKLER HEAD PROTECTION.
  
 FIRE SPRINKLER WORK, INCLUDING DEMO, SHALL BE DONE
 UNDER SEPARATE PERMIT & SHOP DRAWINGS
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-11 Cont ID  
Sent By rmcphers Date 2021-08-11 Time 09:35 Rev Time 0.00
Received By rmcphers Date 2021-08-03 Time 11:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-28 Cont ID  
Sent By rmcphers Date 2021-06-28 Time 10:13 Rev Time 0.00
Received By rmcphers Date 2021-05-19 Time 15:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-06-25 Cont ID  
Sent By medwards Date 2021-06-25 Time 11:31 Rev Time 0.00
Received By medwards Date 2021-06-25 Time 11:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-11 Cont ID  
Sent By rmcphers Date 2021-08-11 Time 09:35 Rev Time 0.00
Received By rmcphers Date 2021-08-11 Time 09:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-06-24 Cont ID  
Sent By rmcphers Date 2021-06-24 Time 08:04 Rev Time 0.00
Received By rmcphers Date 2021-06-24 Time 08:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-08-06 Cont ID  
Sent By eschneid Date 2021-08-06 Time 15:32 Rev Time 0.25
Received By eschneid Date 2021-08-06 Time 15:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-05-27 Cont ID  
Sent By eschneid Date 2021-05-27 Time 13:35 Rev Time 0.25
Received By eschneid Date 2021-05-27 Time 13:35 Sent To  
Notes
***NONE***