| 2022-04-08 10:14:13 | RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21050508 |
| | |
| | ORIGINAL COMMENT: |
| | 1- SHUTTERS PRODUCT APPROVAL SUBMITTED: |
| | NEED TO PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE |
| | AS REQUIRED BY CITY IMPLEMENTATION STANDARD FOR |
| | WIND-BORNE DEBRIS IMPACT PROTECTION FOR THE FLORIDA |
| | BUILDING CODE. SEE CITY SAMPLE. ALL THE COLUMNS NEED TO |
| | BE COMPLETED. |
| | ALTERNATIVELY, YOU MAY PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE IN ANY OTHER FORMAT AS LONG AS ALL THE |
| | REQUIRED INFORMATION IS PROVIDED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | RESPONSE: |
| | A) SHUTTERS INSTALLATION SCHEDULE SUBMITTED SPECIFY |
| | POURED CONCRETE AS THE SUBSTRATE WHERE SHUTTERS ARE |
| | GOING TO BE INSTALLED (TOP AND BOTTOM). TYPICALLY THE |
| | BOTTOM OF WINDOW OPENINGS IS CONCRETE BLOCK (FILLED OR |
| | NOT). REVISE INSTALLATION SCHEDULE USING THE ANCHOR FOR |
| | CONCRETE BLOCK SUBSTRATE OR PROVIDE PROOF SHOWING |
| | BOTTOM OF OPENINGS HAS POURED CONCRETE WITH THE |
| | STRENGTH SPECIFIED ON ANCHOR SCHEDULE ON SHEET 12 OF 17 |
| | OF PRODUCT APPROVAL SUBMITTED. |
| | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | B) REVISE SHUTTERS INSTALLATION SCHEDULE. ACCORDION |
| | SHUTTERS ARE INSTALLED VERTICALLY NOT HORIZONTALLY. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- OK. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |