Plan Review Details - Permit 21050468
Plan Review Stops For Permit 21050468
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-06-29 Cont ID  
Sent By jwitmer Date 2021-06-29 Time 08:14 Rev Time 0.00
Received By jwitmer Date 2021-06-29 Time 07:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-22 Cont ID  
Sent By jwitmer Date 2021-06-22 Time 09:46 Rev Time 0.00
Received By jwitmer Date 2021-06-22 Time 09:27 Sent To  
Notes
2021-06-22 09:45:56WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21050468
 ADD: 1100 S. FLAGLER DR. # 1702
 CONT: ED?S ISLAND TIME SERVICES, INC.
 TEL: 561-541-0004
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JUNE 22ND/ 2021
 ACTION: DENIED
  
 1) 2ND REQUEST. SHEET A1 NOTE # 12 IS RESTATED TO SAY,
 PROVIDE IMPACT INSULATION/ UNDERLAYMENT AT NEW FLOOR
 FINISHES OR REPAIRS (50 IIC MIN.) FBC CHAPTER 12. THE
 CONTRACTOR HAS FAILED TO SUBMIT ANY TEST REPORTS TO
 ANSWER THIS CODE REQUIREMENT. SEE SECTIONS 1A, 1B, & 1C
 ALL THREE (3) REQUIREMENTS MUST BE MET.
 1ST SET OF COMMENTS. THE INTERIOR DEMO PLAN THERE WERE
 NO NOTES ABOUT FLOOR FINISHES BEING REMOVED. SHEET A1
 THE PROPOSED FLOOR PLAN NOTE # 12 INDICATES PROVIDE
 IMPACT INSULATION/ UNDERLAYMENT AT NEW FINISHES (50
 IIC) MIN) PER FBC. CHAPTER 12. THE PROPOSED FLOOR PLAN
 DOES NOT INDICATE ANY FLOOR FINISHES BEING REMOVED AND
 REPLACED.
 FLOOR INSULATION (FBC-B 2020) FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A ( THIS BUILDING ONLY 8 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B.
  
 2) COMPLIED.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-03 Cont ID  
Sent By jwitmer Date 2021-06-03 Time 19:58 Rev Time 0.00
Received By jwitmer Date 2021-06-03 Time 16:14 Sent To  
Notes
2021-06-03 17:12:30WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21050468
 ADD: 1100 S. FLAGLER DR. # 1702
 CONT: ED?S ISLAND TIME SERVICES, INC.
 TEL: 561-541-0004
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 03RD/ 2021
 ACTION: DENIED
  
 1) THE INTERIOR DEMO PLAN THERE WERE NO NOTES ABOUT
 FLOOR FINISHES BEING REMOVED. SHEET A1 THE PROPOSED
 FLOOR PLAN
 NOTE # 12 INDICATES PROVIDE IMPACT INSULATION/
 UNDERLAYMENT AT NEW FINISHES (50 IIC) MIN) PER FBC.
 CHAPTER 12. THE PROPOSED FLOOR PLAN DOES NOT INDICATE
 ANY FLOOR FINISHES BEING REMOVED AND REPLACED.
 FLOOR INSULATION (FBC-B 2020) FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A ( THIS BUILDING ONLY 8 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B.
  
 2A) PLEASE BE AWARE THIS BUILDING WAS DESIGNED AND
 BUILT UNDER THE FAIR HOUSING GUIDELINES. SECTION 3 FAIR
 HOUSING ACT DESIGN AND CONSTRUCTION REQUIREMENT. FOR
 THE PURPOSE OF THIS SECTION, A COVERED MULTIFAMILY
 DWELLING SHALL BE DEEMED TO BE DESIGNED AND CONSTRUCTED
 FOR THE FIRST OCCUPANCY ON OR BEFORE MARCH 13, 1991.
 THE INTERIOR DOORS WIC# 2 & WIC# 4 BOTH ARE LABELED AS
 2680 OR 2 FEET 6 INCHES IN WIDTH OR 30-INCH-WIDE DOORS.
 PLEASE REVIEW REQUIREMENT # 3 USEABLE DOORS (INTERIOR
 DOORS) CLOSETS LESS THAN 24 INCHES IN DEPTH ARE NOT
 CONSIDERED USEABLE DOORS. WHERE THIS CODE SECTION (FAIR
 HOUSING) REQUIRES A MINIMUM CLEAR WIDTH OF 32 INCHES,
 THE ACTUAL DOOR MINIMUM IS A 32 INCH WIDE DOOR THEY DO
 NOT WORRY ABOUT THE DOOR STOP. THE MINIMUM SIZE OF A
 SWING DOORS IS MEASURED CLEAR OPENING OF THE DOORWAY
 WITH THE SWINGING DOORS SHALL BE MEASURED BETWEEN THE
 FACE OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90
 DEGREES.
  
 2B) AS AN ALTERNATE TO THE DESIGN. FAIR HOUSING
 GUIDELINES. FAIR HOUSING ACT DESIGN AND CONSTRUCTION
 REQUIREMENTS. FOR PURPOSES OF THIS SECTION, A COVERED
 MULTIFAMILY DWELLING SHALL BE DEEMED TO BE DESIGNED AND
 CONSTRUCTED FOR FIRST OCCUPANCY ON OR BEFORE MARCH 13,
 1991, IF THEY ARE OCCUPIED BY THAT DATE OR IF THE LAST
 BUILDING PERMIT OR RENEWAL THEREOF FOR THE COVERED
 MULTIFAMILY DWELLINGS IS ISSUED BY A STATE, COUNTY OR
 LOCAL GOVERNMENT ON OR BEFORE JANUARY 13, 1990.
 FAIR HOUSING LETTER AS AN ALTERNATE METHOD. SEE LETTER:
 PROJECT ADDRESS: ______________________________________
 _____________________
 PERMIT NUMBER: ________________________
 THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE THAT THE
 PROPOSED WALK IN CLOSET DESIGN FOR CLOSETS 2 & 4 DOES
 NOT MEET THE REQUIREMENTS OF THE FAIR HOUSING
 ACCESSIBILITY GUIDELINES. THE OWNER AGREES TO REVERT
 THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF SO
 REQUESTED BY THE BUYER.
  
 SIGNATURE OF DESIGNER: ______________________________
 PRINTED NAME OF DESIGNER: ___________________________
  
 SIGNATURE OF OWNER: ________________________________
 PRINTED NAME OF OWNER: _____________________________
 NOTARY FOR OWNER?S SIGNATURE:
 STATE OF FLORIDA, COUNTY OF PALM BEACH
 THE FOREGOING INSTRUMENT WAS ACKNOWLEDGED BEFORE ME
 THIS _____ DAY OF ________, 20__ BY
 ___________________________ WHO IS PERSONALLY KNOWN TO
 ME OR WHO HAS PRODUCED: ___________________________ AS
 IDENTIFICATION AND WHO DID / DID NOT TAKE AN OATH.
 NOTARY SIGNATURE ___________________________________
 NOTARY PRINTED NAME ________________________________
  
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-06-22 Cont ID  
Sent By jleahy Date 2021-06-22 Time 07:35 Rev Time 0.00
Received By jleahy Date 2021-06-22 Time 07:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-05-26 Cont ID  
Sent By equinone Date 2021-05-26 Time 14:54 Rev Time 0.00
Received By equinone Date 2021-05-26 Time 11:55 Sent To  
Notes
2021-05-26 15:12:50CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) NEW WALLS IN KITCHEN SEEM TO NEED ADDITIONAL
 RECEPTACLES TO COMPLY WITH NEC 210.52
 2) THERE SHOULD BE AT LEAST ONE RECEPTACLE IN HALLWAY
 (FOYER AREA) NEC 210.52
 2) PLEASE SHOW ALL EXISTING AND NEW SMOKE DETECTORS
 3) ELECTRICAL PERMIT APPLICATION ONLY LISTS RELOCATING
 HIG HATS AND EXHAUST FAN. PLEASE INCLUDE NEW
 RECEPTACLES AS WELL. FBC 107
 4) PLEASE PROVIDE UPDATED PANEL SCHEDULES FBC 107
  
 ENRIQUE QUINONEZ PE
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By bdolan Date 2021-05-14 Time   Rev Time 0.00
Received By bdolan Date 2021-05-14 Time 15:48 Sent To  
Notes
2021-05-14 15:53:06THIS PLAN HAS BEEN REVIEWED AND APPROVED BY THE
 DIVISION OF FIRE PREVENTION WITH THE FOLLOWING
 COMMENTS:
  
 ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS MAY REQUIRE AN EVALUATION OF THE FIRE ALARM
 SYSTEM OR DEVICES FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED CONTRACTORS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-06-30 Cont ID  
Sent By medwards Date 2021-06-30 Time 06:26 Rev Time 0.00
Received By medwards Date 2021-06-29 Time 13:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-29 Cont ID  
Sent By jwitmer Date 2021-06-29 Time 08:15 Rev Time 0.00
Received By jwitmer Date 2021-06-28 Time 08:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-23 Cont ID  
Sent By lcrespo Date 2021-06-23 Time 17:19 Rev Time 0.00
Received By lcrespo Date 2021-06-21 Time 08:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-03 Cont ID  
Sent By jwitmer Date 2021-06-03 Time 19:59 Rev Time 0.00
Received By jwitmer Date 2021-05-13 Time 11:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-06-30 Cont ID  
Sent By medwards Date 2021-06-30 Time 06:26 Rev Time 0.00
Received By medwards Date 2021-06-30 Time 06:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-06-29 Cont ID  
Sent By medwards Date 2021-06-29 Time 07:39 Rev Time 0.00
Received By medwards Date 2021-06-29 Time 07:39 Sent To  
Notes
2021-06-29 07:39:52PLEASE PROVIDE INFORMATION REQUESTED BELOW ON THE 2ND
 CYCLE PLAN REVIEW.
  
 PLEASE HAVE THE MECHANICAL CONTRACTOR TO PRINT AND SIGN
 THEIR NAME ON THE MECHANICAL DRAWING.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-06-22 Cont ID  
Sent By medwards Date 2021-06-22 Time 13:10 Rev Time 0.00
Received By medwards Date 2021-06-22 Time 13:04 Sent To  
Notes
2021-06-22 13:12:31PLEASE HAVE THE MECHANICAL CONTRACTOR TO PRINTAND SIGN
 THEIR NAME ON THE MECHANICAL DRAWING.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-05-26 Cont ID  
Sent By medwards Date 2021-05-26 Time 11:04 Rev Time 0.00
Received By medwards Date 2021-05-26 Time 10:03 Sent To  
Notes
2021-05-26 11:04:561ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21050468
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE DUCT
 WORK THAT WILL BE MOVED, SHOWING THE EXISTING LOCATION
 AND THE NEW LOCATION. ALSO YOU MUST SHOW THE EXHAUST
 FAN LOCATION AND DETAILS OF TYING THE BATH EXHAUST DUCT
 WORK TO THE EXISTING SHAFT. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-06-23 Cont ID  
Sent By lcrespo Date 2021-06-23 Time 17:15 Rev Time 0.00
Received By lcrespo Date 2021-06-23 Time 17:15 Sent To  
Notes
2021-06-23 17:19:4506/23/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-06-01 Cont ID  
Sent By lcrespo Date 2021-06-01 Time 14:59 Rev Time 0.00
Received By lcrespo Date 2021-06-01 Time 14:59 Sent To  
Notes
2021-06-01 15:00:1506/01/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM
 FOR SANITARY AND WATER PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 2. SUBMIT FIRE STOPPING DETAILS FOR ANY NEW PLUMBING
 PENETRATIONS THAT WILL BE MADE THROUGH THE EXISTING
 SLAB PER THE WPB AMENDMENTS TO FBC SEC. 107.3.5.1.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2021-08-20 Cont ID  
Sent By rgathrig Date 2021-08-20 Time 10:36 Rev Time 0.00
Received By rgathrig Date 2021-08-20 Time 10:36 Sent To  
Notes
2021-08-20 10:38:05PRIVATE PROVIDER INSPECTIONS ONLY
 PLANNING AND BUILDING CONSULTANTS, LLC STEVE KENNDEY
 APPROVED
 RICHARD GATHRIGHT
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-22 Cont ID  
Sent By medwards Date 2021-06-22 Time 13:12 Rev Time 0.00
Received By medwards Date 2021-06-22 Time 13:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-06-03 Cont ID  
Sent By jwitmer Date 2021-06-03 Time 18:34 Rev Time 0.00
Received By jwitmer Date 2021-06-03 Time 16:14 Sent To  
Notes
***NONE***