Plan Review Details - Permit 21050438
Plan Review Stops For Permit 21050438
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-12-27 Cont ID  
Sent By shill Date 2021-12-27 Time 12:41 Rev Time 0.00
Received By shill Date 2021-12-27 Time 12:41 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-06-11 Cont ID  
Sent By shill Date 2021-06-11 Time 15:03 Rev Time 0.00
Received By shill Date 2021-06-11 Time 15:03 Sent To  
Notes
2021-06-11 15:04:25PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-05-12 Cont ID  
Sent By pvalenti Date 2022-05-12 Time 05:46 Rev Time 0.00
Received By pvalenti Date 2022-05-12 Time 05:46 Sent To  
Notes
2022-05-12 05:48:04PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 NOTE: THE PERMIT TYPE AND DESCRIPTION HAS BEEN CHANGED
 FROM AN INTERIOR DEMO TO A DEMO.
 A PROVISO HAS BEEN ADDED TO SURVEY AS A LANDSCAPE
 PERMIT MAY BE REQUIRED FOR THE NEW CONSTRUCTION UNDER
 PERMIT # 21081431. PLEASE CONTACT THE LANDSCAPE
 PLANNER, RAY CARANCI AT 561 822 1462.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-04-29 Cont ID  
Sent By pvalenti Date 2022-04-29 Time 08:41 Rev Time 0.00
Received By pvalenti Date 2022-04-29 Time 08:30 Sent To  
Notes
2022-04-29 08:44:59PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
  
 NOTE: THE PERMIT TYPE AND DESCRIPTION HAS BEEN CHANGED
 FROM AN INTERIOR DEMO TO A DEMO.
 A PROVISO HAS BEEN ADDED TO SURVEY AS A LANDSCAPE
 PERMIT MAY BE REQUIRED FOR THE NEW CONSTRUCTION UNDER
 PERMIT # 21081431. PLEASE CONTACT THE LANDSCAPE
 PLANNER, RAY CARANCI AT 561 822 1462.
 BUILDING REVIEW DENIED:
  
 3.) WATERDOWN METHOD:
 IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED
 INFPRMATION OF THE WATER TRUCK SUCH AS: THE
 GALLON CAPACITY OF THE WATER TANK AND A LETTER
 INCLUDING A STATEMENT THAT THE WATER
 USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY
 AND WILL BE ON-SITE AT ALL TIMES
 DURING DEMOLITION.
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED
 ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS
 SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE
 SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE
 BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY
 THE CITY?S UTILITIES DEPT, 561-822-2244. FAX THE
 COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
  
 8.) PROVIDE A STORMWATER POLLUTION PREVENTION PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-12-27 Cont ID  
Sent By shill Date 2021-12-27 Time 12:41 Rev Time 0.00
Received By shill Date 2021-12-27 Time 12:41 Sent To  
Notes
2021-12-27 12:47:10YOU CANNOT DO EXTERIOR DEMO ON AN INTERIOR DEMO PERMIT.
 A NEW APPLICATION WAS SUBMITTED THAT IS FOR DEMO OF AN
 ADDITION. THE FIRST APPLICATION WAS FOR "INTERIOR DEMO
 AND EXTERIOR DEMO".
  
 IS INTERIOR DEMO STILL PROPOSED? IF YES PROVIDE A PLAN.
  
 THE PLANS SUBMITTED SHOWS SCOPE AS:
  
 1 DEMO SCREEN ENCLOSURE
 3 DEMO 1 STORY ADDITION
  
 NOTHING ON THE PLAN IS MARKED AS 3. IT IS NOT CLEAR
 WHAT IS PROPOSED UNDER THIS APPLICATION.
  
  
 PREVIOUS LIST:
  
  
 ****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301, FBC 107, PLAN IS NOT CLEAR AS TO SCOPE.
 INDICATE THE INTERIOR AREA TO BE DEMOLISHED.
  
 2. A NOTE STATES THAT THE REAR 1 STORY ADDITION IS TO
 BE DEMOLISHED. YOU CANNOT INCLUDE DEMOLITION OF A
 SUBSTANTIAL PORTION OF A BUILDING ON A RENOVATION
 PERMIT OR AN INTERIOR DEMO PERMIT; THAT IS A SEPARATE
 PERMIT. SUBMIT A SEAPRATE PERMIT, ADVISE OF VALUE, AND
 THE FEES PAID ON THIS PERMIT WILL BE MOVED TO THE NEW
 PERMIT. NEW PERMIT WILL BE REVIEWED AS A DEMO WHICH HAS
 REQUIREMENTS (RELEASE FROM FPL OR ELEC PERMIT SAFING
 OFF STRUCTURE, RELEASE FROM WPB UTILITIES, DEMO DEBRIS
 FORM, ETC.).
  
 THE SCOPE OF DEMO OF THE SCREEN ENCLOSURE AND DEMO OF
 THE REAR 1 STORY ADDITION WILL BE UNDER THE NEW PERMIT.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-11 Cont ID  
Sent By shill Date 2021-06-11 Time 15:04 Rev Time 0.00
Received By shill Date 2021-06-11 Time 15:04 Sent To  
Notes
2021-06-11 15:04:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301, FBC 107, PLAN IS NOT CLEAR AS TO SCOPE.
 INDICATE THE INTERIOR AREA TO BE DEMOLISHED.
  
 2. A NOTE STATES THAT THE REAR 1 STORY ADDITION IS TO
 BE DEMOLISHED. YOU CANNOT INCLUDE DEMOLITION OF A
 SUBSTANTIAL PORTION OF A BUILDING ON A RENOVATION
 PERMIT OR AN INTERIOR DEMO PERMIT; THAT IS A SEPARATE
 PERMIT. SUBMIT A SEAPRATE PERMIT, ADVISE OF VALUE, AND
 THE FEES PAID ON THIS PERMIT WILL BE MOVED TO THE NEW
 PERMIT. NEW PERMIT WILL BE REVIEWED AS A DEMO WHICH HAS
 REQUIREMENTS (RELEASE FROM FPL OR ELEC PERMIT SAFING
 OFF STRUCTURE, RELEASE FROM WPB UTILITIES, DEMO DEBRIS
 FORM, ETC.).
  
 THE SCOPE OF DEMO OF THE SCREEN ENCLOSURE AND DEMO OF
 THE REAR 1 STORY ADDITION WILL BE UNDER THE NEW PERMIT.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-11-08 Cont ID  
Sent By jleahy Date 2021-11-08 Time 11:32 Rev Time 0.00
Received By jleahy Date 2021-11-08 Time 11:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-06-14 Cont ID  
Sent By jleahy Date 2021-06-14 Time 14:32 Rev Time 0.00
Received By jleahy Date 2021-06-14 Time 14:31 Sent To  
Notes
2021-06-14 14:33:36ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ELECTRICAL PLAN REVIEW NEEDS AN ELECTRICAL PERMIT
 APPLICATION FOR APPROVAL. PLEASE EMAIL THE ELECTRICAL
 PERMIT APPLICATION TO [email protected] AND CC
 [email protected] SO I RECEIVE IT ALSO. WHEN THIS EMAIL
 IS RECEIVED ONE OF THE REVIEWERS WILL APPROVE THE PLAN
 REVIEW

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-01-06 Cont ID  
Sent By amhamilt Date 2022-01-06 Time 08:52 Rev Time 0.00
Received By amhamilt Date 2022-01-06 Time 08:52 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-06-10 Cont ID  
Sent By aborngra Date 2021-06-10 Time 13:59 Rev Time 0.00
Received By aborngra Date 2021-06-10 Time 12:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-29 Cont ID  
Sent By pvalenti Date 2022-04-29 Time 09:49 Rev Time 0.00
Received By pvalenti Date 2022-04-10 Time 08:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-07 Cont ID  
Sent By lmarchan Date 2022-01-07 Time 08:36 Rev Time 0.00
Received By lmarchan Date 2021-11-23 Time 07:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-14 Cont ID  
Sent By jleahy Date 2021-06-14 Time 14:33 Rev Time 0.00
Received By jleahy Date 2021-05-27 Time 11:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-27 Cont ID  
Sent By shill Date 2021-12-27 Time 12:49 Rev Time 0.00
Received By shill Date 2021-12-27 Time 12:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-06-11 Cont ID  
Sent By shill Date 2021-06-11 Time 14:48 Rev Time 0.00
Received By shill Date 2021-06-11 Time 14:48 Sent To  
Notes
2021-06-11 15:03:44SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
  
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL (OR DROP OFF) ONE ORIGINAL
 SIGNED AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE
 TO:
  
  
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6724.
  
  