Plan Review Details - Permit 21050400
Plan Review Stops For Permit 21050400
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-07-22 Cont ID  
Sent By lcrespo Date 2021-07-22 Time 14:57 Rev Time 0.00
Received By lcrespo Date 2021-07-22 Time 14:57 Sent To  
Notes
2021-07-22 14:58:1107/22/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-07-12 Cont ID  
Sent By lcrespo Date 2021-07-12 Time 14:11 Rev Time 0.00
Received By lcrespo Date 2021-07-12 Time 14:11 Sent To  
Notes
2021-07-13 09:11:1207/12/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 THE ISOMETRIC SUBMITTED STATES AN EXISTING TANK-LESS,
 POOL HEATER, AND BBQ, BUT THE CITY OF WEST PALM BEACH
 DOES NOT HAVE ANY RECORD OF PERMIT OR INSPECTIONS ON
 THE GAS SYSTEM NOTED AS EXISTING. A FULL EVALUATION OF
 ALL GAS EQUIPMENT WILL BE DONE AT THE FIELD. IF NOT TO
 CODE, IT MAY NEED TO BE BROUGHT UP TO CODE COMPLIANCE.
 IT IS UP TO THE HOMEOWNER TO MAKE AN APPLICATION TO THE
 BUILDING OFFICIAL AND OBTAIN THE REQUIRED PERMIT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 1. THE ISOMETRIC DRAWING INDICATES AN EXISTING GAS
 METER. THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE
 ADDED TO THE SYSTEM'S TOTAL BTU LOAD TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES
 PER THE 2020 FBC RES. SECS. G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 2. PLEASE SHOW THE LOCATION OF ALL REGULATORS. A LISTED
 SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF
 EACH MP REGULATOR PER THE 2020 FBC RES. SEC. G2420.4.
  
 3. BBQ HAS NOT BTU?S. WOULD YOU PLEASE LIST THE BTU
 LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE
 SYSTEM? REFER TO THE 2020 FBC RES. SEC. G2413.
  
  
 4. PLEASE SHOW THE DISTANCE FROM THE POINT OF DELIVERY
 (GAS METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC
 RES. SEC. G2413.4.1.
  
 5. PLEASE INDICATE THE SYSTEM'S DELIVERY PRESSURE (PSI)
 ON THE PLAN PER THE 2020 FBC RES. SEC. G2413.2.
  
 6. PLEASE SHOW THE TYPE OF GAS (LP OR NATURAL) PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 7. PLEASE LABEL AND SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1? OF EITHER SIDE PER THE 2020 FBC RES. SEC
 G2421.
  
 8. PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON GAS
 ISOMERIC PER THE 2020 FBC RES. SEC. G2420.5.
  
 9. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-22 Cont ID  
Sent By lcrespo Date 2021-07-22 Time 14:58 Rev Time 0.00
Received By lcrespo Date 2021-07-21 Time 14:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-07-13 Cont ID  
Sent By lcrespo Date 2021-07-13 Time 09:11 Rev Time 0.00
Received By lcrespo Date 2021-07-02 Time 11:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-07-22 Cont ID  
Sent By lcrespo Date 2021-07-22 Time 14:57 Rev Time 0.00
Received By lcrespo Date 2021-07-22 Time 14:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-07-13 Cont ID  
Sent By lcrespo Date 2021-07-13 Time 07:50 Rev Time 0.00
Received By lcrespo Date 2021-07-13 Time 07:50 Sent To  
Notes
***NONE***