Plan Review Details - Permit 21050368
Plan Review Stops For Permit 21050368
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-09-01 Cont ID  
Sent By cthroop Date 2021-09-01 Time 13:09 Rev Time 0.00
Received By cthroop Date 2021-09-01 Time 12:51 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-06-21 Cont ID  
Sent By cthroop Date 2021-06-21 Time 10:29 Rev Time 0.00
Received By cthroop Date 2021-06-21 Time 08:56 Sent To  
Notes
2021-06-21 10:29:43SEE ASBESTOS COMMENTS UNDER BUILDING REVIEW C0MMENTS.
 CT

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-05-19 Cont ID  
Sent By cthroop Date 2021-05-19 Time 11:33 Rev Time 0.00
Received By cthroop Date 2021-05-19 Time 10:00 Sent To  
Notes
2021-05-19 11:36:34SEE ASBESTOS COMMENTS UNDER BUILDING REVIEW C0MMENTS.
 CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-09-01 Cont ID  
Sent By cthroop Date 2021-09-01 Time 13:26 Rev Time 0.00
Received By cthroop Date 2021-09-01 Time 12:51 Sent To  
Notes
2021-09-01 13:13:48PLAN REVIEW BUILDING DEMO
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 3RD REVIEW
  
 NOTICE: PERMIT TYPE CHANGED FROM DEMO-INT TO DEMO.
 REMOVAL OF ROOF APPROVED (SH/DB) FOR SAFE ACCESS OF
 ENGINEER.
  
  
 DEMO CHECKLIST
 COMMENTS THAT HAVE BEEN ADDRESSED SATISFACTORILY ARE
 MARKED AS CORRECTED.
  
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303:
  
 1. UTILITY RELEASE - FLORIDA POWER & LIGHT CORRECTED
  
 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS)
 CORRECTED
  
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, CORRECTED
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED. SEE
 COMMENTS ON PLAN PAGE D-1 FROM THE PLUMBING PLANS
 EXAMINER. (SEWER LATERAL CAP NOT REQUIRED. SEE PLUMBING
 COMMENT ON PG. D-1 BY LC)
  
 5. EXTERMINATION LETTER - CORRECTED
  
 6. COMPLETE THE DEMO DEBRIS FORM: CORRECTED
  
 7. PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF
 THE STRUCTURE(S) TO BE DEMOLISHED, FBC 107. SEE DEMO
 PLAN PAGE D-1 SUBMITTEED FOR REVIEW ON 5/17/2021. (NOT
 REQUIRED-INTERIOR WORK)
  
 8.PROVIDE A STORMWATER POLLUTION PREVENTION PLAN. (NOT
 REQUIRED-INTERIOR WORK)
  
  
 9.ASBESTOS CORRECTED
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-22 Cont ID  
Sent By cthroop Date 2021-06-22 Time 09:37 Rev Time 0.00
Received By cthroop Date 2021-06-21 Time 08:56 Sent To  
Notes
2021-06-21 10:13:32PLAN REVIEW BUILDING DEMO
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 NOTICE: PERMIT TYPE CHANGED FROM DEMO-INT TO DEMO.
 REMOVAL OF ROOF APPROVED (SH/DB) FOR SAFE ACCESS OF
 ENGINEER.
  
  
 DEMO CHECKLIST
 COMMENTS THAT HAVE BEEN ADDRESSED SATISFACTORILY ARE
 MARKED AS CORRECTED.
  
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303:
  
 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC)
 RELEASE OF SERVICE CONFIRMATION. SEE ELECTRICAL REVIEW
 COMMENTS.
  
 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS)
 RELEASE OF SERVICE CONFIRMATION.
  
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON THEIR FORM
 "DEMOLITION APPLICATION" FORM SUBMITTED ON 5/17/2021
 HAS NOT BEEN APPROVED BY CITY UTILITIES DEPT.
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM.
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED. SEE
 COMMENTS ON PLAN PAGE D-1 FROM THE PLUMBING PLANS
 EXAMINER.
 NEW COMMENT: (PLAN PAGE D-1 REPLACED ON 6/4/21,
 PLUMBING STAMP MISSING)
  
 5. EXTERMINATION LETTER - CORRECTED
  
 6. COMPLETE THE DEMO DEBRIS FORM: CORRECTED
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 7. PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF
 THE STRUCTURE(S) TO BE DEMOLISHED, FBC 107. SEE DEMO
 PLAN PAGE D-1 SUBMITTEED FOR REVIEW ON 5/17/2021.
  
 8.PROVIDE A STORMWATER POLLUTION PREVENTION PLAN. (NOT
 REQUIRED-INTERIOR WORK)
  
  
 9.ASBESTOS
  
 PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE CONTRACTOR,
 ON LETTERHEAD, STATING THAT:
  
 THE INSTRUCTIONS ON THE WEBSITE OF THE ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 IF YOU FEEL YOUR BUILDING IS EXEMPT, PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THE REASON WHY THE BUILDING IS EXEMPT.
  
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-19 Cont ID  
Sent By cthroop Date 2021-05-19 Time 13:51 Rev Time 0.00
Received By cthroop Date 2021-05-19 Time 10:00 Sent To  
Notes
2021-05-19 14:03:12PLAN REVIEW BUILDING DEMO
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 NOTICE: THE SOW FOR THIS INTERIOR DEMO PERMIT INCLUDES
 THE REMOVAL OF THE ROOF, WINDOWS AND EXTERIOR DOORS.
 CITY POLICY PROHIBITS OPENING THE BUILDING ENVELOPE
 WITHOUT A PERMIT TO RE-CONSTRUCT THE BUILDING.
 A DEMO PERMIT WILL NOT BE ISSUED UNTIL A PLAN TO
 RE-CONSTRUCT THE BUILDING HAS BEEN SUBMITTED, REVIEWED
 AND APPROVED BY THE BUILDING DEPARTMENT.
  
  
 DEMO CHECKLIST
 COMMENTS THAT HAVE BEEN ADDRESSED SATISFACTORILY ARE
 MARKED AS CORRECTED.
  
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303:
  
 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC)
 RELEASE OF SERVICE CONFIRMATION. SEE ELECTRICAL REVIEW
 COMMENTS.
  
 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS)
 RELEASE OF SERVICE CONFIRMATION.
  
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON THEIR FORM
 "DEMOLITION APPLICATION" FORM SUBMITTED ON 5/17/2021
 HAS NOT BEEN APPROVED BY CITY UTILITIES DEPT.
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM.
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED. SEE
 COMMENTS ON PLAN PAGE D-1 FROM THE PLUMBING PLANS
 EXAMINER.
  
 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST
 CONTROL COMPANY STATING THAT DEMOLITION ADDRESS HAS
 BEEN INSPECTED AND/OR TREATED FOR RODENTS. LETTER
 SUBMITTED FOR REVIEW ON 7/17/2021.
  
 6. COMPLETE THE DEMO DEBRIS FORM: ENTER THE ESTIMATED
 YARDAGE AND VALUE ON FORM SUBMITTED ON 5/17/2021.
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 7. PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF
 THE STRUCTURE(S) TO BE DEMOLISHED, FBC 107. SEE DEMO
 PLAN PAGE D-1 SUBMITTEED FOR REVIEW ON 5/17/2021.
  
 8.PROVIDE A STORMWATER POLLUTION PREVENTION PLAN.
 YOU MAY USE THE SITE PLAN OR SURVEY. SHOW SILT FENCEING
 OR OTHER APPROVED METHODS.
  
 9.ASBESTOS
  
 PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE CONTRACTOR,
 ON LETTERHEAD, STATING THAT:
  
 THE INSTRUCTIONS ON THE WEBSITE OF THE ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 IF YOU FEEL YOUR BUILDING IS EXEMPT, PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THE REASON WHY THE BUILDING IS EXEMPT.
  
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-09-01 Cont ID  
Sent By cthroop Date 2021-09-01 Time 13:27 Rev Time 0.00
Received By cthroop Date 2021-09-01 Time 13:27 Sent To  
Notes
2021-09-01 13:27:48RCV'D FPL LETTER. CT

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2021-05-19 Cont ID  
Sent By jleahy Date 2021-05-19 Time 08:02 Rev Time 0.00
Received By jleahy Date 2021-05-19 Time 07:55 Sent To  
Notes
2021-05-19 08:03:33ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 I WAS TOLD THAT THERE IS NO POWER TO THE BUILDING.

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2021-07-12 Cont ID  
Sent By fmittner Date 2021-07-12 Time 12:55 Rev Time 0.00
Received By fmittner Date 2021-07-12 Time 12:55 Sent To  
Notes
2021-07-12 12:55:38PASSED FOR ROOF DEMO ONLY.

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2021-06-23 Cont ID  
Sent By aborngra Date 2021-06-23 Time 15:50 Rev Time 0.00
Received By aborngra Date 2021-06-23 Time 15:50 Sent To  
Notes
2021-06-23 15:50:56THE PERMIT HAS FAILED. ADDRESS BUILDING COMMENTS.
  
 THE REMOVAL OF THE WINDOW AC UNITS WILL REQUIRE THE
 SPACES TO BE FILLED IN WITH BRICK TO MATCH EXISTING
 EXTERIOR FACE.
  
 REMOVAL OF EXTERIOR WALLS IS NOT PERMITTED.
  
 AARON BORNGRABER, AICP
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2021-05-26 Cont ID  
Sent By aborngra Date 2021-05-26 Time 15:45 Rev Time 0.00
Received By aborngra Date 2021-05-26 Time 15:44 Sent To  
Notes
2021-05-26 15:45:17THE PERMIT HAS FAILED. ADDRESS BUILDING COMMENTS.
  
 THE REMOVAL OF THE WINDOW AC UNITS WILL REQUIRE THE
 SPACES TO BE FILLED IN WITH BRICK TO MATCH EXISTING
 EXTERIOR FACE.
  
 AARON BORNGRABER, AICP
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-09-01 Cont ID  
Sent By cthroop Date 2021-09-01 Time 13:26 Rev Time 0.00
Received By cthroop Date 2021-08-09 Time 08:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-23 Cont ID  
Sent By lmarchan Date 2021-06-23 Time 15:55 Rev Time 0.00
Received By lmarchan Date 2021-06-04 Time 13:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-26 Cont ID  
Sent By lmarchan Date 2021-05-26 Time 17:42 Rev Time 0.00
Received By lmarchan Date 2021-05-10 Time 15:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-05-20 Cont ID  
Sent By medwards Date 2021-05-20 Time 08:06 Rev Time 0.00
Received By medwards Date 2021-05-20 Time 07:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-05-19 Cont ID  
Sent By lcrespo Date 2021-05-19 Time 10:13 Rev Time 0.00
Received By lcrespo Date 2021-05-19 Time 09:52 Sent To  
Notes
2021-05-19 10:14:3205/19/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-09-29 Cont ID  
Sent By cthroop Date 2021-09-29 Time 17:15 Rev Time 0.00
Received By cthroop Date 2021-09-29 Time 17:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-06-21 Cont ID  
Sent By cthroop Date 2021-06-21 Time 10:29 Rev Time 0.00
Received By cthroop Date 2021-06-21 Time 08:56 Sent To  
Notes
2021-06-21 10:31:51PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 2ND REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: CANNOT OPEN DIGITAL SIGNATURE. SIGNED BY HELLO
 SIGN PLATFORM.
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-05-19 Cont ID  
Sent By cthroop Date 2021-05-19 Time 13:51 Rev Time 0.00
Received By cthroop Date 2021-05-19 Time 10:01 Sent To  
Notes
***NONE***