Plan Review Details - Permit 21050313
Plan Review Stops For Permit 21050313
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-06-30 Cont ID  
Sent By rmcphers Date 2021-06-30 Time 13:25 Rev Time 0.00
Received By rmcphers Date 2021-06-30 Time 13:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-23 Cont ID  
Sent By rmcphers Date 2021-06-23 Time 13:51 Rev Time 0.00
Received By rmcphers Date 2021-06-23 Time 13:51 Sent To  
Notes
2021-06-23 13:56:46ADDED WINDOWS AND DOORS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE REVISE THE FLOOR PLAN (A-1) TO SHOW THE
 LOCATION OF THE ADDED WINDOWS AND DOORS.
 2) PLEASE SHOW THE ADDITIONAL JOB COST FOR THE ADDED
 WINDOWS AND DOORS FBC WPB 109.3 BUILDING PERMIT
 VALUATIONS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-27 Cont ID  
Sent By mcphers Date 2021-05-27 Time 16:07 Rev Time 0.00
Received By rmcphers Date 2021-05-27 Time 16:07 Sent To  
Notes
2021-05-27 16:13:58PRODUCT APPROVALS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE DESIGNER OF RECORD FBC WPB 107.3.4.1
 2) YOU HAVE PROVIDE PRODUCT APPROVALS FOR SINGLE HUNG
 WINDOWS - DRAWING A-3 WINDOW SCHEDULE DOES NOT SHOW A
 SINGLE HUNG WINDOW - PLEASE REVISE DRAWINGS TO SHOW
 SINGLE HUNG WINDOW LOCATION AND SIZES. REVISE JOB VALUE
 IF ADDING MORE WINDOWS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-30 Cont ID  
Sent By rmcphers Date 2021-06-30 Time 13:26 Rev Time 0.00
Received By rmcphers Date 2021-06-25 Time 09:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-23 Cont ID  
Sent By rmcphers Date 2021-06-23 Time 13:56 Rev Time 0.00
Received By rmcphers Date 2021-06-15 Time 13:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-27 Cont ID  
Sent By rmcphers Date 2021-05-27 Time 16:14 Rev Time 0.00
Received By rmcphers Date 2021-05-10 Time 11:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-30 Cont ID  
Sent By rmcphers Date 2021-06-30 Time 13:26 Rev Time 0.00
Received By rmcphers Date 2021-06-30 Time 13:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-06-23 Cont ID  
Sent By rmcphers Date 2021-06-23 Time 13:58 Rev Time 0.00
Received By rmcphers Date 2021-06-23 Time 13:58 Sent To  
Notes
***NONE***