| 2021-05-19 15:44:14 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21050282 |
| | 5/17/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A-2: FAIR HOUSING ACCESSIBILITY GUIDELINES: |
| | BECAUSE THE BUILDING WAS CONSTRUCTED IN ACCORDANCE WITH |
| | THE ACCESSIBILITY REQUIREMENTS OF THE FAIR HOUSING ACT |
| | AND THE DESIGN GUIDELINES FOR USABLE KITCHENS IN |
| | DWELLING UNITS, THE KITCHEN ALTERATIONS SHALL ALSO BE |
| | IN COMPLIANCE WITH THE FAIR HOUSING ACT. THE FAIR |
| | HOUSING ACCESSIBILITY GUIDELINES ARE INCLUDED IN THE |
| | FLORIDA ACCESSIBILITY CODE- 2020 SEVENTH EDITION. REFER |
| | TO REQUIREMENT 7 (1)(A) AND SHOW THE REQUIRED 30X48 |
| | INCH CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR A |
| | PARALLEL WHEELCHAIR APPROACH AT THE SINK, AND 30X48 |
| | INCH CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE |
| | PARALLEL OR FORWARD APPROACH TO THE DISHWASHER. PLEASE |
| | NOTE THAT THE REQUIRED CLEAR FLOOR SPACES FOR PARALLEL |
| | APPROACHES SHALL BE CENTERED ON THE SINK AND |
| | DISHWASHER- REFER TO PAGE 7.5 OF THE FAIR HOUSING ACT |
| | DESIGN MANUAL. |
| | |
| | PLEASE NOTE: AS AN ALTERNATIVE TO MEETING THE |
| | GUIDELINES FOR THE BATH ALTERATIONS, THE OWNER AND |
| | DESIGNER OF RECORD FOR THE PROPOSED PROJECT MAY PROVIDE |
| | A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE |
| | ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET |
| | THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY |
| | GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO |
| | REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF |
| | REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN, |
| | PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A |
| | COPY OF THE FAIR HOUSING AFFIDAVIT. |
| | |
| | 2) A-2: PROVIDE A SHOWER PAN DETAIL- SECTION 417.5.1- |
| | 417.5.2.6 FBC P. |
| | |
| | 3) A-2: IT APPEARS THE BATHTUB DRAIN IS BEING |
| | RELOCATED. PLEASE COMPLY WITH THE FOLLOWING ITEMS: |
| | A) REFER TO SECTION 1002.1: THE HORIZONTAL DISTANCE |
| | FROM THE CENTERLINE OF THE NEW BATHTUB DRAIN OUTLET TO |
| | THE CENTERLINE OF THE INLET OF THE EXISTING TRAPS SHALL |
| | NOT EXCEED 30". PLEASE PLACE A NOTE ON THE PLAN |
| | INDICATING COMPLIANCE. |
| | B) RELOCATING THE SHOWER DRAIN OUTLETS WILL REQUIRE THE |
| | FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE REINFORCING |
| | STEEL OR POST STRESSED FLOOR TENDONS. PLEASE PLACE A |
| | NOTE ON THE PLANS TO VERIFY COMPLIANCE WILL BE MET- |
| | SECTION 107.2.1 WPB. |
| | C) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB |
| | WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE |
| | AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED |
| | FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1 |
| | FBC P AND SECTION 714.4.1.2 FBC B. |
| | |
| | 4) DEFERRED SUBMITTALS- SECTION 107.3.4.1 WPB. |
| | MANUFACTURER'S SPECIFICATIONS ARE REQUIRED FOR THE |
| | SHOWER VALVE, BATHTUB VALVE AND TEMPERATURE LIMITING |
| | DEVICE- SECTIONS 412.3 & 412.5 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |