| 2021-06-14 14:06:01 | 06/14/21 2ND LP GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. NOTE: THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| | EXISTING GAS. A COMPLETE EVALUATION OF ALL GAS |
| | EQUIPMENT WILL BE DONE AT THE FIELD, AND IF NOT TO |
| | CODE, IT MAY NEED TO BE BOUT UP TO CODE COMPLIANCE. I |
| | HAVE RESEARCHED CITY RECORDS BACK TO 2000, AND THERE IS |
| | NO RECORD OF A PERMIT FOR THE INSTALLATION OF AN LP |
| | TANK. WHAT THIS "EXISTING" TANK SUPPLIES OTHER |
| | APPLIANCES/EQUIPMENT? SINCE THERE IS NO RECORD OF A |
| | PERMIT FOR THE LP TANK, THE TANK MUST BE INCLUDED IN |
| | THIS PERMIT FOR THIS SCOPE OF WORK PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 2. DONE...PLEASE HAVE A SIGNATURE ON THE ISOMETRIC |
| | DRAWING OF THE PERSON DESIGNING THE SYSTEM, NOT |
| | ACCORDING TO FLORIDA ADMINISTRATIVE CODE 61G15-23.001, |
| | FLORIDA STATUTE 471 PER THE WPB AMENDMENTS FBC SEC. |
| | 107.1 GENERAL. |
| | |
| | 3. PLEASE PROVIDE A RISER DIAGRAM REQUIRED PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL |
| | GAS. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, |
| | ALL PIPE SIZES, AND). IN ADDITION, SHOW ON THE |
| | ISOMETRIC DRAWING THE LENGTH OF ALL CUT SECTIONS OF |
| | PIPE PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2. |
| | |
| | 4. SECOND REQUEST, PLEASE SUBMIT THE MANUFACTURER'S |
| | SPECIFICATION SHEETS/INSTALLATION MANUAL FOR THE |
| | GENERATORS TO VERIFY COMPLIANCE WITH 2017 FBC FG |
| | SEC.305.1 OR 2017 FBC RES. SEC. G2408.1. |
| | |
| | 5. SECOND REQUEST, PLEASE SUBMIT THE CORRECT BTU LOAD |
| | ON THE SYSTEM. THE 193 IS INCORRECT, AND IF THERE ARE |
| | ANY OTHER APPLIANCES CONNECTED TO THE SYSTEM, PLEASE |
| | PROVIDE THEM AS WELL. REFER TO THE 2020 FBC RES. SEC. |
| | G2413. |
| | |
| | 6. DONE...SHOW THE DISTANCE FROM THE POINT OF DELIVERY |
| | (GAS METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC |
| | RES. SEC. G2413.4.1. |
| | |
| | 7. SECOND REQUEST, PLEASE SHOW AND LABEL ALL UNIONS IN |
| | FRONT OF REGULATOR 1' OF EITHER SIDE, DRIP LEG, AND |
| | SHUTOFF VALVE PER THE 2020 FBC RES. SEC G2421.2. |
| | |
| | 8. THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET |
| | FROM OPENINGS INTO A BUILDING. FBC-R303.5.1 INTAKE |
| | OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE |
| | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET FROM |
| | ANY HAZARDOUS OR NOXIOUS CONTAMINANTS, SUCH AS VENTS, |
| | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING |
| | LOTS, AND LOADING DOCKS. PLEASE SHOW ON PLANS PERT THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 9. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP |
| | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF |
| | THE TANK FROM THE DRIVEWAY AND ADJACENT PROPERTY LINES, |
| | THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, |
| | OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY |
| | BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK |
| | PER THE NFPA 58, TABLE 3-2.2.2. PLEASE NOTE THAT IF THE |
| | TANK IS LESS TANK 10 FT. FROM THE DRIVEWAY, THE SHELL |
| | FOR THE TANK SHALL BE 18 IN. ABOVE GRADE, AND VEHICULAR |
| | BARRIER PROTECTION WILL BE REQUIRED. |
| | |
| | 10. SHOW THE DEPTH OF THE LP GAS CONTAINER BELOW GRADE |
| | TO COMPLY WITH NFPA 58 SEC. 6.6.6.1. |
| | |
| | 11. THE UG LP TANK SHALL BE PROTECTED AGAINST CORROSION |
| | BY INSTALLING A CATHODIC PROTECTION SYSTEM CONSISTING |
| | OF A SACRIFICIAL ANODE OR AN IMPRESSED CURRENT ANODE |
| | PER SECTIONS 5.2.1.11 & 6.6.6.1(I) NFPA 58. INDICATE |
| | THE TYPE OF PROTECTION AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS- SECTION 6.17.1. SUBMIT DETAILS ON THE |
| | TYPE OF CATHODIC PROTECTION, SIZE (LBS.) & THE NUMBER |
| | OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE AMOUNT |
| | OF WATER TO ACTIVATE IT. |
| | |
| | 12. THE ENGINEERED TIE-DOWN SUPPLIED SHEET FOR THE LP |
| | TANK TIE-DOWN METHOD, STRAPS, OR CABLE, AND HOW THE |
| | CABLE IS PROTECTED FOR THE LP TANK AND APPURTENANCES, |
| | DOES NOT HAVE THE CURRENT CODE YEAR AS IT SAYS 2017. |
| | THIS IS A SIGNED AND SEALED DOCUMENT. IT WILL REQUIRE |
| | THE ORIGINAL DROPPED OFF AT THE CITY OR AN ELECTRONIC |
| | SIGNATURE SUBMITTED PER NFPA 58 AND WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | PLEASE CONTACT ME FOR FURTHER ASSISTANT ON THIS REVIEW |
| | AS THE LOCATION OF THE TANK AND THE PAPERWORK SUBMITTED |
| | ARE UNCLEAR. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |