| 2021-06-19 10:08:55 | PLAN REVIEW BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PRODUCT APPROVALS SUBMITTED FOR REVIEW DO NOT MATCH |
| | THE PRODUCT APPROVALS LISTED ON THE SITE PLAN. |
| | DESIGNER SHALL REVIEW AND APPROVE EACH PRODUCT |
| | APPROVAL. INDICATE WHICH MODEL OF DOOR WILL BE |
| | INSTALLED FROM THE LIST OF MODELS ON THE PRODUCT |
| | APPROVALS. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | |
| | 2. PROVIDE SITE SPECIFIC DESIGN WIND LOADS PER FBC CHPT |
| | 16 AND ASCE 7-16. CALCULATIONS SHALL BE PREPARED BY |
| | FLORIDA LICENSED DESIGN PROFESSIONAL. |
| | 1609.1.1DETERMINATION OF WIND LOADS. |
| | WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE |
| | DETERMINED IN ACCORDANCE WITH CHAPTERS 26 TO 30 OF ASCE |
| | 7. WIND SHALL BE ASSUMED TO COME FROM ANY HORIZONTAL |
| | DIRECTION AND WIND PRESSURES SHALL BE ASSUMED TO ACT |
| | NORMAL TO THE SURFACE CONSIDERED. |
| | |
| | FBC 107.3.5.1.(8) PROVIDE WIND DESIGN LOADS/DESIGN |
| | PRESSURES PURSUANT TO FBC-CHAPTER 16 FOR EACH OPENING. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |