Plan Review Details - Permit 21050208
Plan Review Stops For Permit 21050208
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-12-20 Cont ID  
Sent By cpuell Date 2021-12-20 Time 12:57 Rev Time 0.00
Received By cpuell Date 2021-12-20 Time 12:57 Sent To  
Notes
2021-12-20 12:58:15HALF ADDRESS READDRESSED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-05-10 Cont ID  
Sent By cpuell Date 2021-05-10 Time 08:27 Rev Time 0.00
Received By cpuell Date 2021-05-10 Time 08:27 Sent To  
Notes
2021-05-10 08:28:58WORK TO BE DONE ON FRONT UNIT ONLY, BACK UNIT HAS A
 HALF ADDRESS WHICH WILL NEED TO BE READDRESSED. PLEASE
 EMAIL [email protected] TO DISCUSS ADDRESSING OPTIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-22 Cont ID  
Sent By cthroop Date 2021-05-22 Time 07:51 Rev Time 0.00
Received By cthroop Date 2021-05-22 Time 07:12 Sent To  
Notes
2021-05-22 08:05:46PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. VALUE
  
 CITY OF WPB CHPT109.3 BUILDING PERMIT VALUATIONS.
  
 1A. VALUE APPEARS LOW FOR THE PROPOSED SCOPE OF WORK.
 1B. THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. THIS INCLUDES ALL LABOR,
 MATERIALS AND RENTALS OF EQUIPMENT TO PERFORM THE SCOPE
 OF WORK.
 1C. YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY
 THE OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL
  
 2. NOC SUBMITTED WITH THIS SUBMITTAL IS FOR ROOFING.
 PLEASE REMOVE FROM DOCUMENTS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. WINDOW LAYOUT DOES NOT MATCH PHOTO (GOOGLE MAPS).
 MULTIPLE WINDOWS ARE MISSING FROM THE WINDOW LAYOUT FOR
 THE FRONT ELEVATION.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4. PROVIDE A WINDOW SCHEDULE. (SEE BELOW)
  
 1. LOCATION ? REFERENCE TO OPENING NUMBER ON PLAN.
 2. WINDOW TYPE
 3. ROUGH OPENING ? WXH (AREA ? SF)
 4. DESIGN PRESSURE OF OPENING (TABLE R301.1.(2) OR ASCE
 7-16
 5. NOA OR FL NUMBER
 6. MAX DESIGN PRESSURE FROM NOA OF FL
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 5. PROVIDE A CURRENT FLORIDA PRODUCT APPROVAL OR NOA
 FOR WINDOW MULLIONS AND EACH TYPE OF WINDOW TO BE
 INSTALLEED.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-05-17 Cont ID  
Sent By aborngra Date 2021-05-17 Time 11:00 Rev Time 0.00
Received By aborngra Date 2021-05-14 Time 15:56 Sent To  
Notes
2021-05-17 10:58:37PERMIT HAS BEEN APPROVED WITH THE FOLLOWING
 CONDITION(S):
 1. ALL REPLACEMENT WINDOWS SHALL BE SIZED TO FIT THE
 ORIGINAL WINDOW FRAME OPENING (X-AXIS AND Y-AXIS) AND
 MATCH THE LOCATION/DEPTH (Z-AXIS) OF THE ORIGINAL
 WINDOWS.
  
 CLARIFICATION:
 THE EXTERIOR WINDOW CASING SHALL NOT EXTEND BEYOND THE
 WOOD FRAMING.
  
 2. THE EXISTING MULLION SHALL REMAIN OR BE REPLACED
 WITH A MULLION OF MATCHING WIDTH AND PLACEMENT.
 3. ALL STREET OR SIDEWALK FACING GLASS SHALL BE CLEAR.
 ALL NON-STREET FACING GLASS SHALL BE CLEAR OR CLEAR
 WITH LOW-E COATING. NO TINT. OBSCURED TEXTURED GLASS
 MAY BE USED ON NON-STREET FACING BATHROOMS ONLY.
 4. ALL WINDOWS SHALL HAVE EXTERNAL DIMENSIONAL OGEE
 MUNTINS.
  
 AARON BORNGRABER, AICP
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-22 Cont ID  
Sent By cthroop Date 2021-05-22 Time 08:05 Rev Time 0.00
Received By cthroop Date 2021-05-06 Time 11:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-05-22 Cont ID  
Sent By cthroop Date 2021-05-22 Time 08:06 Rev Time 0.00
Received By cthroop Date 2021-05-22 Time 07:12 Sent To  
Notes
***NONE***