Plan Review Details - Permit 21050131
Plan Review Stops For Permit 21050131
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-05-06 Cont ID  
Sent By cpuell Date 2021-05-06 Time 16:33 Rev Time 0.00
Received By cpuell Date 2021-05-06 Time 16:33 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-05-06 Cont ID  
Sent By cpuell Date 2021-05-06 Time 10:22 Rev Time 0.00
Received By cpuell Date 2021-05-06 Time 10:22 Sent To  
Notes
2021-05-06 10:23:18WORKING WITH MIKE IZZO ON THE SUITE NUMBERS, PROPOSED
 SUITE NUMBERS WAITING TO HEAR BACK FROM HIM.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-06-05 Cont ID  
Sent By jwitmer Date 2021-06-05 Time 16:57 Rev Time 0.00
Received By jwitmer Date 2021-06-05 Time 16:25 Sent To  
Notes
2021-06-05 16:51:28WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21050131
 ADD: 360 S. ROSEMARY AVE. # 1420
 CONT: TBD / TO BE DETERMINED
 TEL:
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. JUNE 05/ 2021
 ACTION: BUILDING PROVISO
  
 1) ASBESTOS LETTER FROM THE GENERAL CONTRACTOR REQUIRED
 PRIOR TO PERMIT ISSUANCE ( HOLD PLACED ON PERMIT
 ISSUANCE).
 .
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-05-12 Cont ID  
Sent By jwitmer Date 2021-05-12 Time 11:27 Rev Time 0.00
Received By jwitmer Date 2021-05-12 Time 10:13 Sent To  
Notes
2021-05-12 11:23:55COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-05 Cont ID  
Sent By jwitmer Date 2021-06-05 Time 16:57 Rev Time 0.00
Received By jwitmer Date 2021-06-05 Time 16:25 Sent To  
Notes
2021-06-05 16:52:41WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21050131
 ADD: 360 S. ROSEMARY AVE. # 1420
 CONT: TBD / TO BE DETERMINED
 TEL:
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. JUNE 05/ 2021
 ACTION: BUILDING PROVISO
  
 1) ASBESTOS LETTER FROM THE GENERAL CONTRACTOR REQUIRED
 PRIOR TO PERMIT ISSUANCE ( HOLD PLACED ON PERMIT
 ISSUANCE).
 .
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-12 Cont ID  
Sent By jwitmer Date 2021-05-12 Time 11:28 Rev Time 0.00
Received By jwitmer Date 2021-05-12 Time 10:13 Sent To  
Notes
2021-05-12 11:22:52WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21050131
 ADD: 360 S. ROSEMARY AVE. # 1420
 CONT: TBD / TO BE DETERMINED
 TEL:
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 12, 2021
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET ASSUMED THAT SUITE 1420 IS ON
 THE 14TH LEVEL AND NOT THE 1ST FLOOR:
  
 1A) OCCUPANT LOAD THAT IS SHOWN 49 OCCUPANTS, THE
 OCCUPANT LOAD TAKEN IS FROM TABLE 1004.5 OF THE 2020
 FBC-B. IS 21. IF YOU ARE ONLY GOING TO HAVE THE 21
 OCCUPANTS YOU USE THE TABLE 1004.5, IF YOU EXCEED THAT
 AMOUNT OF OCCUPANTS THEN YOU SHOULD SHOW COMPLIANCE
 WITH SECTION 1004.2 INCREASED OCCUPANT LOAD.
  
 1B) THE SIZING OF THE MEANS OF EGRESS IS TAKEN AT20
 OCCUPANTS WHEREAS THE ACTUAL OCCUPANT LOAD OF 49 IS
 WHAT IS REQUIRED. 49 X 0.2= 9.8 INCHES REQUIRED. TABLE
 1004.5 OF THE 2020 FBC-BUILDING.
  
 1C) NOT APPLICABLE. 5/20/2021.
  
 1D) NOT APPLICABLE. 5/20/2021.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-06-04 Cont ID  
Sent By jleahy Date 2021-06-04 Time 06:26 Rev Time 0.00
Received By jleahy Date 2021-06-04 Time 06:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-05-07 Cont ID  
Sent By jleahy Date 2021-05-07 Time 12:08 Rev Time 0.00
Received By jleahy Date 2021-05-07 Time 07:19 Sent To  
Notes
2021-05-07 12:12:58ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 CONFERENCE ROOM NEEDS ADDITIONAL OUTLETS PER 210.71
  
 210.71 MEETING ROOMS (B) RECEPTACLE OUTLETS REQUIRED.
 THE TOTAL NUMBER OF RECEPTACLE OUTLETS, INCLUDING FLOOR
 OUTLETS AND RECEPTACLE OUTLETS IN FIXED FURNITURE,
 SHALL NOT BE LESS THAN AS DETERMINED IN (1) AND (2).
 THESE RECEPTACLE OUTLETS SHALL BE PERMITTED TO BE
 LOCATED AS DETERMINED BY THE DESIGNER OR BUILDING
 OWNER.
 (1) RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE
 OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH
 210.52(A)(1) THROUGH (A)(4).
 (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM THAT IS AT
 LEAST 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF
 AT LEAST 20 M2 (215 FT2) SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET LOCATED IN THE FLOOR AT A DISTANCE
 NOT LESS THAN 1.8 M (6 FT) FROM ANY FIXED WALL FOR EACH
 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR SPACE.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-06-03 Cont ID  
Sent By pleduc Date 2021-06-03 Time   Rev Time 0.00
Received By pleduc Date 2021-06-03 Time 11:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-05-07 Cont ID  
Sent By pleduc Date 2021-05-07 Time   Rev Time 0.00
Received By pleduc Date 2021-05-07 Time 09:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-18 Cont ID  
Sent By medwards Date 2021-06-18 Time 06:19 Rev Time 0.00
Received By medwards Date 2021-06-17 Time 09:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-06-07 Time   Rev Time 0.00
Received By aoliver Date 2021-06-02 Time 11:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-13 Cont ID  
Sent By jleahy Date 2021-05-13 Time 17:20 Rev Time 0.00
Received By jleahy Date 2021-05-05 Time 09:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-06-18 Cont ID  
Sent By medwards Date 2021-06-18 Time 06:18 Rev Time 0.00
Received By medwards Date 2021-06-18 Time 06:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-06-03 Cont ID  
Sent By medwards Date 2021-06-03 Time 06:41 Rev Time 0.00
Received By medwards Date 2021-06-03 Time 06:41 Sent To  
Notes
2021-06-03 07:46:47THE REVISED M-3.1 VENTILATION CALCULATIONS HAVE BEEN
 ALTERED FROM THE ORIGINAL CALCULATIONS. THE REVISED
 CALCULATIONS FOR CFM'S OF OUTDOOR AIR HAVE BEEN CUT.
 THE ORIGINAL CALCULATIONS WERE CORRECT. PLEASE CHANGE
 THE REVISED CALCULATIONS BACK TO THE ORIGINAL
 CALCULATIONS (CFM'S ONLY) EXAMPLE: OFFICE SPACE WAS 150
 CFM, REVISED SHEET SHOWS 44 CFM'S.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-05-08 Cont ID  
Sent By medwards Date 2021-05-08 Time 12:06 Rev Time 0.00
Received By medwards Date 2021-05-08 Time 12:06 Sent To  
Notes
2021-05-08 12:07:311ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21050131
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-3.1 VENTILATION CALCULATIONS- NOTE 2: PLEASE
 REFERENCE THE FBC M 7TH EDITION AS THIS IS THE CURRENT
 CODE EDITION. AND IS THE ONE MENTIONED ON SHEET LS-1.1.
 FBC 107.2.1
  
 2) SHEET M-3.1 VENTILATION CALCULATIONS- NOTE 2: PLEASE
 PROVIDE CORRECT CODE REFERENCE AS THERE IS NOT A
 403.3.2.3.3.
  
 3) SHEET M-3.1: VENTILATION CALCULATIONS- PLEASE ALSO
 INCLUDE THE ZONE AIR DISTRIBUTION EFFECTIVENESS TABLE
 403.3.1.1.1.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-06-07 Cont ID  
Sent By ccole Date 2021-06-07 Time 07:27 Rev Time 0.00
Received By ccole Date 2021-06-07 Time 07:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-05-12 Cont ID  
Sent By ccole Date 2021-05-12 Time 08:55 Rev Time 0.00
Received By ccole Date 2021-05-12 Time 07:06 Sent To  
Notes
2021-05-12 08:56:031ST REVIEW FBC-2020 PLUMBING
 PERMIT-21050131
 5/12/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A3.01: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS AT THE BEER AND KOMBUCHA BEVERAGE
 DISPENSERS- SECTION 305.1 FBC ACC.
  
 2) A3.01: PROVIDE AN ELEVATION VIEW OF THE BEVERAGE
 DISPENSERS TO VERIFY COMPLIANCE WITH REQUIRED REACH
 RANGES- SECTIONS 904.5.1 AND 308.1 FBC ACC.
  
 3) P1.2 & P1.3: SHUT OFF VALVES FOR INDIVIDUAL FIXTURES
 AND APPLIANCES NOT SHOWN- SECTION 606.2 FBC P.
  
 4) P1.4: THE COLD-WATER BRANCH LINE SERVING THE WATER
 HEATER SHALL BE PROVIDED WITH A DEDICATED SHUT OFF
 VALVE- SECTION 503.1 FBC P.
  
 5) P1.1: INSTALLATION OF THE NEW SINK AND HUB DRAIN MAY
 REQUIRE THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE
 REINFORCING STEEL OR POST STRESSED FLOOR TENDONS.
 PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE
 WILL BE MET- SECTION 107.2.1 WPB.
  
 6) THE NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACES
 AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1
 FBC P AND SECTION 714.4.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-18 Cont ID  
Sent By medwards Date 2021-06-18 Time 06:19 Rev Time 0.00
Received By medwards Date 2021-06-18 Time 06:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-07 Cont ID  
Sent By ccole Date 2021-06-07 Time 07:27 Rev Time 0.00
Received By ccole Date 2021-06-07 Time 07:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-05-08 Cont ID  
Sent By medwards Date 2021-05-08 Time 12:15 Rev Time 0.00
Received By medwards Date 2021-05-08 Time 12:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2021-05-12 Cont ID  
Sent By aaponte Date 2021-05-12 Time 13:36 Rev Time 0.00
Received By aaponte Date 2021-05-12 Time 13:36 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy