| 2021-05-13 08:09:08 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-21050129 |
| | 5/13/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS LS.1.1, A1.1.1 & A3.01: THE DETAILS ON SHEET |
| | A3.01 APPEAR TO INDICATE FIXTURE GRAB BAR |
| | REINFORCEMENTS TO BE INSTALLED HOWEVER NOT THE GRAB |
| | BARS. THE EXCEPTIONS FOR NOT INSTALLING THE GRAB BARS |
| | UNDER SECTIONS 604.5 & 608.3 APPLY TO PRIVATE BATHROOMS |
| | THAT ARE ACCESSED THROUGH A PRIVATE OFFICE. THE ACCESS |
| | TO THE NEW BATHROOM IS FROM A CORRIDOR. PLEASE REVISE |
| | THE DRAWINGS TO SHOW COMPLIANCE WITH THE FBC ACC |
| | SECTIONS BELOW: |
| | A) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604 |
| | B) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOOR TO |
| | THE REFLECTIVE SURFACE- SECTION 603.3 |
| | C) LOCATION OF THE WATER CLOSET FLUSH CONTROL - SECTION |
| | 604.6. |
| | D) CENTERLINES OF THE TOILET PAPER DISPENSER MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | E) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE |
| | SHOWER- SECTION 608.2.2 & 608.2.2.1 |
| | F) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3.2. |
| | G) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE |
| | SHOWER- SECTION 608.5.2. |
| | H) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6. |
| | |
| | 2) A1.1.1 & A3.0.1: SHOW THE CLEAR FLOOR SPACE DIAGRAM |
| | AND DIMENSION FOR THE BREAK ROOM SINK AND COFFEE |
| | DISPENSER- SECTIONS 305.1 & 606.2 FBC ACC. |
| | |
| | 3) A3.0.1: PROVIDE AN ELEVATION VIEW OF THE BREAKROOM |
| | SINK AND COUNTER SHOWING THE HEIGHT OF THE SINK FROM |
| | THE FINISHED FLOOR AND KNEE AND TOE CLEARANCES- |
| | SECTIONS 606.3 & 306.1 FBC ACC. PLEASE INCLUDE THE |
| | HEIGHT OF THE COFFEE DISPENSER CONTROLS TO VERIFY |
| | COMPLIANCE WITH REACH RANGES- SECTION 308.1 FBC ACC. |
| | |
| | 4) P0-1: PVC HAS BEEN SPECIFIED FOR ABOVE AND BELOW |
| | SLAB. PLEASE NOTE IF THE BELOW SLAB AREA IS A PLENUM |
| | SPACE THEN THE COMBUSTIBLE PVC IS A NON-COMPLIANT |
| | INSTALLATION- SECTION 303.2 FBC P. |
| | |
| | 5) P1.1: INSTALLATION OF THE NEW SINK AND HUB DRAIN MAY |
| | REQUIRE THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE |
| | REINFORCING STEEL OR POST STRESSED FLOOR TENDONS. |
| | PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE |
| | WILL BE MET- SECTION 107.2.1 WPB. |
| | |
| | 6) P1.1: THE NEW DRAIN PIPE PENETRATIONS OF THE |
| | EXISTING SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE |
| | ANNULAR SPACE AROUND THE PIPING. PROVIDE A UL TESTED |
| | AND APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- |
| | SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B. |
| | |
| | 7) P2.1 & P3.1: SHUT OFF VALVES FOR INDIVIDUAL FIXTURES |
| | AND APPLIANCES NOT SHOWN OR NOTED- SECTION 606.2 FBC P. |
| | |
| | 8) P2.1 & P3.1: WATER HAMMER ARRESTORS WHERE REQUIRED |
| | FOR FIXTURES AND APPLIANCES NOT SHOWN OR NOTED- SECTION |
| | 604.9 FBC P. |
| | |
| | 9) P4.1: THE COLD-WATER BRANCH LINE SERVING THE WATER |
| | HEATER SHALL BE PROVIDED WITH A DEDICATED SHUT OFF |
| | VALVE- SECTION 503.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |