| 2021-07-09 14:59:45 | SINGLE FAMILY RESIDENCE (R3), GARAGE CONVERSION, |
| | BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21050089. |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 1- ACCORDING TO CITY RECORDS AND PAM BEACH COUNTY |
| | PROPERTY APPRAISER THE REAR STRUCTURE IS A |
| | CARPORT/GARAGE. THERE ARE NO PERMITS FOR THE GARAGE |
| | CONVERSION. |
| | THIS IS CONSIDERED A CHANGE OF OCCUPANCY AND ALTERATION |
| | LEVEL 3. NEED TO PROVIDE PLANS PREPARED BY LICENSED |
| | DESIGN PROFESSIONAL SHOWING COMPLIANCE WITH SEC. 605 |
| | FBC-EXISTING BUILDING. SEC. 1001.2.1 FBC-EXISTING |
| | BUILDING. SEC. 604 FBC-EXISTING BUILDING AND SEC. 801.3 |
| | EXISTING BUILDING. |
| | |
| | 2- DESIGN PROFESSIONAL TO PROVIDE EVALUATION AND |
| | ANALYSIS SHOWING THAT EXISTING STRUCTURE WILL RESIST |
| | THE LATERAL FORCE LOADS AS REQUIRED BY SEC 907.4.1 |
| | FBC-EXISTING BUILDING. |
| | SEC. 605 FBC-EXISTING BUILDING. SEC. 604 FBC-EXISTING |
| | BUILDING. |
| | |
| | 3- PLANS SUBMITTED DON'T SPECIFY THE USE OF THE SPACE. |
| | DESIGNER OF RECORD PREPARING THE NEW PLANS TO CLEARLY |
| | SPACE THE USE OF THE NEW SPACE. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 4-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1013 |
| | FBC-EXISTING BUILDING AND SEC. R101.5.1 FBC-ENERGY |
| | CONSERVATION. |
| | NOTE: COORDINATE WITH ITEM #5 BELOW AND MAKE SURE |
| | CALCULATIONS ARE SIGNED BY ALL THE REQUIRED PARTIES, |
| | INCLUDING THE OWNER OR AUTHORIZED AGENT TO AVOID |
| | CONFLICT/DELAYS. |
| | |
| | 5- DESIGN PROFESSIONAL TO SPECIFY WALL AND CEILING |
| | INSULATION. |
| | SEC. 1013 FBC-EXISTING BUILDING AND SEC. R103.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | 6- PLANS TO SHOW COMPLIANCE WITH THE REQUIRED HEATING |
| | AS REQUIRED BY SEC. 605 FBC-EXISTING BUILDING AND SEC. |
| | R303.10 FBC-RESIDENTIAL. |
| | |
| | 7- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW. |
| | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S |
| | OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS |
| | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. |
| | REVISE VALUATION TO INCLUDE ALL THE SCOPE OF WORK, |
| | INCLUDING ELECTRICAL, MECHANICAL, PLUMBING AND BUILDING |
| | WORK. NONE OF THIS WORK WAS PERMITTED. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |