| 2021-05-24 08:13:33 | PLAN REVIEW BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE SITE SPECIFIC DESIGN WIND LOADS PER FBC CHPT |
| | 16 AND ASCE 7-16. CALCULATIONS SHALL BE PREPARED BY |
| | FLORIDA LICENSED DESIGN PROFESSIONAL. |
| | 1609.1.1DETERMINATION OF WIND LOADS. |
| | WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE |
| | DETERMINED IN ACCORDANCE WITH CHAPTERS 26 TO 30 OF ASCE |
| | 7. WIND SHALL BE ASSUMED TO COME FROM ANY HORIZONTAL |
| | DIRECTION AND WIND PRESSURES SHALL BE ASSUMED TO ACT |
| | NORMAL TO THE SURFACE CONSIDERED. |
| | |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | 1. 1.ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | 2. 2.RISK CATEGORY. |
| | 3. 3.WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | 4. 4.APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | 5. 5.DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF |
| | (KN/M2). |
| | |
| | 2. PROVIDE SCHEDULE FOR INSTALLATION OF OPENING |
| | PROTECTIVE DEVICES OR ASSEMBLIES. |
| | 1609.1.2PROTECTION OF OPENINGS. |
| | |
| | NOTICE: I HAVE UPLOADED A COPY OF THE CITY'S SHUTTER |
| | SCHEDULE FOR YOUR REVIEW AND USE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |