| 2021-05-23 16:46:43 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21050016 |
| | ADD: 1400 VILLAGE BLVD. #920 |
| | CONT: BELFOR USA GROUP |
| | TEL: 954-271-2549 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SUN. MAY 23RD/ 2021 |
| | ACTION: DENIED |
| | 1) SHEET A-1: |
| | 1A) PLEASE NOTE THE CODE REFERENCE TO THE |
| | FBC-RESIDENTIAL PER R101.2 (R-3) WOULD BE A REFERENCE |
| | TO A SINGLE FAMILY DWELLING NOT A MULTI-FAMILY |
| | APARTMENT BUILDING OR CONDOMINIUM. PLEASE REFER TO THE |
| | 2020 FBC-BUILDING CODE SECTION 310.4. ON ALL SHEETS |
| | PLEASE CORRECT YOUR CODE SECTIONS TO THE 2020 |
| | FBC-BUILDING THE 7TH EDITION AND APPROPRIATE CODE |
| | SECTIONS WITHIN. |
| | |
| | 1B) THE DESIGNER OF RECORD ALSO MAKES REFERENCE TO THE |
| | EXISTING BUILDING CODE AND SECTION ON REPAIRS. THE |
| | DOLLAR VALUE FOR THE WORK UNDER THIS PERMIT IS |
| | $145,600.00 DOLLARS IN VALUE. THAT WOULD APPEAR TO BE |
| | MORE THAN JUST SIMPLE REPAIRS. THE PLANS ARE SILENT AS |
| | TO IF THERE IS ANY STRUCTURAL DAMAGE TO BEARING WALLS |
| | AND OR TO FLOOR FRAMING MEMBERS. THE REPLACEMENT VALUE |
| | FOR THIS APARTMENT FOR 656 SQ. FT. X $120.00 = |
| | $78,780.00 DOLLARS IN VALUE. PLEASE PROVIDE COMPLIANCE |
| | WITH SECTION 606.2.2.1 EVALUATION REPORT. THE PERMIT |
| | REPLACEMENT VALUE IS ALSO DOUBLE WHAT OUR 2020 ICC |
| | TABLES FOR NEW CONSTRUCTION ARE FOR TYPE VI |
| | CONSTRUCTION/ R2 OCCUPANCY. |
| | |
| | 1C) SHEET A-1 WALL KEYED NOTES LIST NOTE # 2 INTERIOR |
| | BEARING STUDS 2X4?S @ 16 O. C. W/ 5/8-INCH TYPE X GWB |
| | (1HR. RATED). PLEASE PROVIDE EITHER A UL OR GYPSUM |
| | ASSOC. LISTING AND DETAIL FOR ALL COMPONENTS OF THE |
| | WALL SYSTEM. IN THE 2020 FBC-B TABLE 721.1(2) /14-1.2 & |
| | 14-1.5 INDICATE 2 LAYERS OF EITHER ? INCH OR 5/8-INCH |
| | FIRE RATED (TYPE X) GWB. ALSO SEE SECTION 420.4. OF THE |
| | 2020 FBC-B. |
| | |
| | 1D) THE SAME TYPE NOTES FOR WOOD FRAME CEILING RAFTERS. |
| | FLOOR / CEILING 1 HR. RATED ASSEMBLY. PLEASE PROVIDE A |
| | FLOOR/ CEILING ASSEMBLY EITHER A UL LISTING OR GYPSUM |
| | ASSOCIATION DIAGRAM LISTING ALL OF THE COMPONENTS THAT |
| | MAKE UP THE FLOOR/ CEILING ASSEMBLY. 2020 FBC-B SECTION |
| | 420.3. |
| | |
| | 2) SHEET A2. PLEASE NOTE THE TERM CEILING RAFTERS |
| | REFERS TO SOLID WOOD FRAMING MEMBERS. WHEN THESE UNITS |
| | WERE BEING BUILT, ESPECIALLY WOOD FRAMED WALLS THE |
| | FLOOR FRAMING SYSTEM WAS NOT FLOOR JOIST (SOLID WOOD |
| | FRAMING) BUT OPEN WEB FLOOR TRUSSES. THERE IS A |
| | DIFFERENCE IN HOW FLOOR SYSTEMS ARE CONSTRUCTED. |
| | |
| | 2A) DETAIL # 3 ON SHEET A2 SHOWS A DOUBLE WALL SYSTEM |
| | COMMON AT TENANT SEPARATION WALLS WHERE THERE WOULD BE |
| | 3- OR 4-INCH PLUMBING PIPES. THE ISSUE WITH THIS DETAIL |
| | IS THERE IS NO FIRE STOPS OR FIRE BLOCKING IN THE |
| | DETAIL IN COMPLIANCE WITH SECTION 718.2.3 OF THE 2020 |
| | FBC-BUILDING CODE. |
| | |
| | 2B) THE FLOOR PLAN DETAIL 1/ A-2 SHOWS HATCHED CEILING |
| | & SOFFIT BELOW THE FIRE RATED CEILING BUT THERE IS NO |
| | DETAILS FOR THE FRAMING MEMBERS, SIZE OR SPACING OF THE |
| | HORIZONTAL FRAMING MEMBERS, IF MID-SPAN SUPPORTS ARE |
| | REQUIRED, ANCHOR TYPES NOR THE THICKNESS AND TYPE OF |
| | THE FINISHED CEILING MATERIAL. 107.2.1.2. ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 2E) NOTE OF INTEREST. IF THE SOFFIT BETWEEN THE AIR |
| | HANDLER CLOSET AND THE DROPPED CEILING IN THE KITCHEN |
| | IS ELIMINATED THEN RADIANT DAMPERS ARE REQUIRED WHERE |
| | THE DUCT WORK GOES ABOVE THE FIRE RATED CEILING OR |
| | RATING THE AREA REQUIRED FOR THE DUCTWORK ABOVE THE |
| | FIRE RATED CEILING FROM THE REST OF THE AREA WITHIN THE |
| | FLOOR TRUSS ASSEMBLY, THIS INCLUDES THE PLYWOOD FLOOR |
| | DECK OF THE UNIT ABOVE. SECTION 420.3 OF THE 2020 |
| | FBC-B. |
| | |
| | 3) SHEET M101 SHOWS A DETAIL IN THE LOWER RIGHT HAND |
| | CORNER WHERE THERE IS NO RATED CEILING, JUST A DROPPED |
| | CEILING. THE OTHER ISSUE WITH MECHANICAL DUCTWORK WHEN |
| | GOING THROUGH THE FIRE RATED CEILING IS THE REQUIREMENT |
| | FOR LISTED CEILING RADIATION DAMPERS SEE SECTION |
| | 717.6.2 (2) OF THE 2020 FBC-BUILDING. |
| | |
| | 4) SHEET A1 THE DOOR SCHEDULE NOTE # 1 INDICATES THE |
| | REMOVAL AND REPLACEMENT OF THE ENTRY DOOR. THE WIND |
| | LOAD PRESSURES ARE GIVEN AS +39.4 / -42.7 PSF. NOTE |
| | THESE PRESSURES DO NOT STATE IF THEY ARE VULT OR VASD. |
| | MISSING WIND DESIGN CRITERIA, 2020 FBC-B 1603.1.4 WIND |
| | DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | 4.2. RISK CATEGORY. |
| | 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1. |
| | 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| | THE DESIGN OF THE STRUCTURE, PSF. |
| | 4.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| | CONVERSION VULT TO VASD. |
| | |
| | 5) IN THE FILE DOCUMENT FOLDER WAS INFORMATIONAL SHEETS |
| | (1-3) FOR A MASONITE EXTERIOR DOOR. THE SUBMITTED |
| | SHEETS ARE NEITHER A MIAMI-DADE NOA NOR A FLORIDA |
| | APPROVAL. ALL PRODUCT APPROVALS IN FLORIDA MUST HAVE |
| | 3RD PARTY CERTIFICATION. 2020 FBC-B 1609.1.2 PROTECTION |
| | OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| | CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | |
| | 6) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| | DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | |
| | 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |