Plan Review Details - Permit 21041689
Plan Review Stops For Permit 21041689
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-07-12 Cont ID  
Sent By jwitmer Date 2021-07-12 Time 14:14 Rev Time 0.00
Received By jwitmer Date 2021-07-12 Time 13:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-06-03 Time 09:30 Rev Time 0.00
Received By jwitmer Date 2021-06-03 Time 09:00 Sent To  
Notes
2021-06-03 09:33:25WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21041689
 ADD: 5200 N FLAGLER DR. SUITE: 2401
 CONT: DOUGLAS M. PISARSKI, INC.
 TEL: 561-662-3818
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 03/2021
 ACTION: DENIED
 1) NO FLOOR PLAN WAS SUBMITTED. ON THE FLOOR PLAN
 PLEASE PROVIDE THE SQ. FOOTAGE OF FLOORING TO BE
 INSTALLED, AND WHAT TYPE OF MATERIAL IS BEING
 INSTALLED. 107.3.5 MINIMUM PLAN REVIEW CRITERIA. 2020
 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE
 CODE SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
 MISSING CODE DATA: FLOOR PLAN
  
 2) FLOOR PLANS DRAWN BY THE CONTRACTOR. CERTIFICATION
 BY CONTRACTOR. 107.3.4.3. THE CONTRACTOR (QUALIFIER)
 THAT CREATED / DREW THE SET OF PLANS WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS DRAWN.
  
 3) THE SUBMITTED TECHNICAL SHEETS ARE NOT TEST REPORTS.
 WITHOUT KNOWLEDGE OF THE FLOOR FINISH WE CAN NOT STATE
 FOR SURE IF
 THE CITY IS IN RECEIPT OF SUCH TEST REPORTS. WE DO HAVE
 THE TEST REPORTS FOR SUPER SAM 125 6 INCH CONCRETE SLAB
 FOR EITHER MARBLE OR TILE.
  
 FLOOR INSULATION (FBC-B 2020) FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-07-09 Cont ID  
Sent By pleduc Date 2021-07-09 Time   Rev Time 0.00
Received By pleduc Date 2021-07-09 Time 11:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-06-04 Cont ID  
Sent By pleduc Date 2021-06-04 Time   Rev Time 0.00
Received By pleduc Date 2021-06-04 Time 15:34 Sent To  
Notes
2021-06-04 15:38:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF FLOOR UNDERLAYMENT BUT NO
 SHEETS FOR THE FLOORING MATERIAL/PRODUCT.I.E. TILE,
 WOOD NOR SPECIFICATIONS SHEETS OF THAT PRODUCT.'
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
  
 30.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7.1 OR
 10.2.7.2, AS APPLICABLE
  
 10.2.1.1 CLASSIFICATION OF INTERIOR FINISH MATERIALS
 SHALL BE IN
 ACCORDANCE WITH TESTS MADE UNDER CONDITIONS SIMULATING
 ACTUAL
 INSTALLATIONS, PROVIDED THAT THE AUTHORITY HAVING
 JURISDICTION IS
 PERMITTED TO ESTABLISH THE CLASSIFICATION OF ANY
 MATERIAL FOR WHICH
 CLASSIFICATION BY A STANDARD TEST IS NOT AVAILABLE,
 UNLESS OTHERWISE
 PROVIDED IN 10.2.1.2 OR 10.2.1.4.
 10.2.1.2 THE PROVISIONS OF 10.2.1.1 SHALL NOT APPLY TO
 MATERIALS HAVING
 A TOTAL THICKNESS OF LESS THAN 1?28 IN. (0.9 MM) THAT
 ARE APPLIED DIRECTLY
 TO THE SURFACE OF WALLS AND CEILINGS WHERE BOTH OF THE
 FOLLOWING
 CONDITIONS ARE MET:
 (1) THE WALL OR CEILING SURFACE IS A NONCOMBUSTIBLE OR
 LIMITED COMBUSTIBLE
 MATERIAL.
 (2) THE MATERIALS APPLIED MEET THE REQUIREMENTS OF
 CLASS A INTERIOR
 WALL OR CEILING FINISH WHEN TESTED IN ACCORDANCE WITH
 10.2.3,
 USING FIBER CEMENT BOARD AS THE SUBSTRATE MATERIAL.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS.
  
  
 2) IN THE APPLICATION THERE IS A INDICATION OF FLOORING
 THROUGHOUT, DOES THIS INCLUDE THE KITCHENS AND
 BATHROOMS.
  
 IS THE FLOORING PRODUCT THE SAME IN ALL LOCATIONS?
  
 PLEASE PROVIDE A FLOOR PLAN INDICATING WHAT FLOORING
 MATIERAIL IS BEING USED IN EACH LOCATION/ROOM OR THAT
 NO WORK IN CERTAIN ROOMS.
  
 PLEASE BE SPECIFIC AND PROVIDE THE UNIT NUMBER AND THE
 FLOOR PLAN.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-07-12 Time 14:14 Rev Time 0.00
Received By aoliver Date 2021-07-08 Time 13:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-06-07 Time 09:31 Rev Time 0.00
Received By cdecoeur Date 2021-05-11 Time 06:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-07-12 Cont ID  
Sent By jwitmer Date 2021-07-12 Time 14:14 Rev Time 0.00
Received By jwitmer Date 2021-07-12 Time 13:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-06-03 Time 09:31 Rev Time 0.00
Received By jwitmer Date 2021-06-03 Time 09:00 Sent To  
Notes
2021-06-03 09:34:28SEE BUILDING REVIEW.