Plan Review Details - Permit 21041585
Plan Review Stops For Permit 21041585
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-01-05 Cont ID  
Sent By cpuell Date 2022-01-05 Time 16:08 Rev Time 0.00
Received By cpuell Date 2022-01-05 Time 16:08 Sent To  
Notes
2022-01-05 16:09:03WORK BEING DONE ONE SUITE 102, UPDATED PERMIT

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-10-12 Cont ID  
Sent By rmcphers Date 2021-10-12 Time 13:09 Rev Time 0.00
Received By rmcphers Date 2021-10-12 Time 13:09 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-08-24 Cont ID  
Sent By rmcphers Date 2021-08-24 Time 12:47 Rev Time 0.00
Received By rmcphers Date 2021-08-24 Time 12:47 Sent To  
Notes
2021-08-24 12:48:10PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-06-29 Cont ID  
Sent By rmcphers Date 2021-06-29 Time 09:15 Rev Time 0.00
Received By rmcphers Date 2021-06-29 Time 09:15 Sent To  
Notes
2021-06-29 09:16:04PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-11-29 Cont ID  
Sent By rmcphers Date 2021-11-29 Time 08:07 Rev Time 0.00
Received By rmcphers Date 2021-11-29 Time 08:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-10-12 Cont ID  
Sent By rmcphers Date 2021-10-12 Time 13:09 Rev Time 0.00
Received By rmcphers Date 2021-10-12 Time 13:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-24 Cont ID  
Sent By rmcphers Date 2021-08-24 Time 12:42 Rev Time 0.00
Received By rmcphers Date 2021-08-24 Time 11:09 Sent To  
Notes
2021-08-24 11:18:50RESTAURANT RENO
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE LOCATION OF THE ACCESSIBLE SEATING
 SPACES (MAIN DINING, OUTSIDE DINING AND THE BAR) TO
 COMPLY WITH FBC ACCESSIBILITY 226.1 GENERAL.
 WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION
 OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING
 SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL
 COMPLY WITH 902. FBC A226.2DISPERSION.
 DINING SURFACES AND WORK SURFACES REQUIRED TO COMPLY
 WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE OR
 FACILITY CONTAINING DINING SURFACES AND WORK SURFACES.
 2) BAR COUNTER DETAILS SHALL INCLUDE THE ACCESSIBLE
 DETAILS - PLEASE PROVIDE DETAILS FOR THE ACCESSIBLE
 SEATING SPACE AT THE BAR TO COMPLY WITH FBC 902 - FBC
 ACCESSIBILITY 902.2 CLEAR FLOOR OR GROUND SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 (PROVIDE KNEE AND TOE CLEARANCE DETAILS)
 3) PLEASE SHOW THE HEIGHT OF THE ACCESSIBLE BAR SEATING
 TO COMPLY WITH FBC 902.3 HEIGHT.
 THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-29 Cont ID  
Sent By rmcphers Date 2021-06-29 Time 09:13 Rev Time 0.00
Received By rmcphers Date 2021-06-28 Time 15:16 Sent To  
Notes
2021-06-28 15:58:18RESTAURANT RENO
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW ANY NEW CEILING DETAILS -HEIGHT AND TYPE
 - FBC 1208.2
 2) PLEASE SHOW NEW RESTROOM FLOORING AND WALL BASE TO
 COMPLY WITH FBC 1210.2.1 FLOORS AND WALL BASES.
 IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND
 SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH
 FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE
 WALLS NOT LESS THAN 4 INCHES
 3) ON MULTIPLE DRAWINGS THE CODE USED FOR DESIGN IS THE
 2017 FBC ( CODE USED FOR THE DESIGN SHOULD BE 2020 FBC)
 - PLEASE REVISE THE DRAWINGS TO SHOW THE CORRECT CODE
 IN EFFECT.
 4) PLEASE SHOW THE ACCESSIBLE SEATING SPACES TO COMPLY
 WITH FBC ACCESSIBILITY 226.1 GENERAL.
 WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION
 OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING
 SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL
 COMPLY WITH 902.
 5) PLEASE SHOW THE ACCESSIBLE SEATING SPACE AT THE BAR
 TO COMPLY WITH FBC 902 - FBC ACCESSIBILITY 902.2 CLEAR
 FLOOR OR GROUND SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 (PROVIDE KNEE AND TOE CLEARANCE DETAILS)
 6) PLEASE SHOW THE HEIGHT OF THE ACCESSIBLE BAR SEATING
 TO COMPLY WITH FBC 902.3 HEIGHT.
 THE TOPS OF DINING SURFACES AND WORK SURFACES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-08-31 Cont ID  
Sent By fgiaquin Date 2021-08-31 Time 22:15 Rev Time 0.00
Received By fgiaquin Date 2021-08-31 Time 21:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-06-08 Cont ID  
Sent By fgiaquin Date 2021-06-08 Time 21:13 Rev Time 0.00
Received By fgiaquin Date 2021-06-08 Time 19:55 Sent To  
Notes
2021-06-08 21:13:07ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. EXISTING SERVICE NOT SHOWN, SHOW SERVICE SIZE AND
 RISER DIAGRAM. NEC 215.5; WPB FBC 107.2.1
  
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. SEVERAL APPLIANCES AND SPECFIC LOADS SHOWN IN
 PANEL SCHEDULE ARE NOT SHOWN IN "LOAD CALCULATION"
 PROVIDED. NEC 220 NEC 220.14A
  
 3. WHAT IS VOLTAGE OF SERVICE? PANEL B SHOWS 120/240V
 3PH 4W WHICH WOULD BE A DELTA SYSTEM WITH A "HI-LEG".
 PANEL A IS SHOWN AS 120/240V SINGLE-PHASE.
  
 4. NOTE 17 IN ELECTRICAL NOTES STATE LV TO BE INSTALLED
 FOR TV'S AND CAT 6 FOR DATA BUT NOT SHOWN ON PLAN???
 PROVIDE CORRECTION. FBC 107.2.1
  
 5. NOTE 21 STATES PRE-WIRE FOR SPEAKERS BUT NOTHING
 SHOWN ON PLAN??? PROVIDE CORRECTION FBC 107.2.1
  
 6. SHOW WINDOW RECEPTACES ARE ON PANEL SCHEDULE BUT NOT
 SHOWN ON PLAN? FBC 107.2.1 NEC 210.62
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2021-11-29 Cont ID  
Sent By rrossano Date 2021-11-29 Time   Rev Time 0.00
Received By rrossano Date 2021-11-29 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-10-13 Cont ID  
Sent By pleduc Date 2021-10-13 Time   Rev Time 0.00
Received By pleduc Date 2021-10-13 Time 09:59 Sent To  
Notes
2021-10-13 09:59:46FIRE PROVISO:
  
 ALL WORK ON THE FIRE SPRINKLER & FIRE ALARM SYSTEMS,
 INCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-06 Cont ID  
Sent By pleduc Date 2021-08-06 Time   Rev Time 0.00
Received By pleduc Date 2021-08-06 Time 12:44 Sent To  
Notes
2021-08-06 12:47:48FIRE PROVISO:
  
 ALL WORK ON THE FIRE SPRINKLER & FIRE ALARM SYSTEMS,
 INCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-06-07 Cont ID  
Sent By pleduc Date 2021-06-07 Time   Rev Time 0.00
Received By pleduc Date 2021-06-07 Time 12:31 Sent To  
Notes
2021-06-07 14:06:09FIRE PROVISO:
  
 ALL WORK ON THE FIRE SPRINKLER & FIRE ALARM SYSTEMS,
 INCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2022-01-05 Cont ID  
Sent By ccole Date 2022-01-05 Time 14:27 Rev Time 0.00
Received By ccole Date 2022-01-05 Time 08:07 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2021-11-30 Cont ID  
Sent By ccole Date 2021-11-30 Time 09:41 Rev Time 0.00
Received By ccole Date 2021-11-29 Time 16:51 Sent To  
Notes
2021-11-30 09:42:354TH REVIEW FBC-2020 FUEL GAS
 PERMIT- 21041585
 11/30/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST, 2ND, AND 3RD REVIEWS ARE LISTED BELOW WITH
 ADDITIONAL NOTES IN CAPS FOR FURTHER CLARIFICATION.
  
 1) FAILED- GAS ISOMETRIC- SHEET P2: IT APPEARS THAT AN
 1-1/4-INCH SCHEDULE 40 METALLIC PIPE WILL BE THE MAIN
 LOW PRESSURE SUPPLY PIPE HOWEVER IT IS MISLABELED AS A
 SCHEDULED 40 PVC SLEEVE- PLEASE CORRECT.
  
 2) FAILED. NEW MANUFACTURER'S SPECIFICATIONS HAVE BEEN
 SUBMITTED FOR A DIRECT VENT CONDENSING TANKLESS WATER
 HEATER. THE SPECS INDICATE A COMBUSTION AIR INTAKE DUCT
 AND A VENT DUCT TO RUN TO TRE EXTERIOR OF THE BUILDING.
 PLEASE INDICATE THE TYPE AND SIZE OF INTAKE DUCT AND
 SHOW THE DUCT TERMINATION LOCATIONS ON THE EXTERIOR OF
 THE BUILDING ON SHEETS P1 AND M1. PLEASE INCLUDE
 CLEARANCE DISTANCE MEASUREMENTS FROM THE WATER HEATER
 EXHAUST DUCT TO MECHANICAL AND GRAVITY AIR INTAKES INTO
 THE BUILDING INCLUDING THE NEW COMBUSTION AIR FAN INLET
 OPENING- SECTION 503.8 (5) FBC FG.
  
 2A) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW
 WATER HEATER- SHOW TYPE AND SIZE OF PIPE AND DISCHARGE
 LOCATION- SECTION 307.2 FBC FG.
  
 3) FAILED. SHEET M1: PLEASE PROVIDE COMBUSTION AIR
 CALCULATIONS FOR THE NEW FAN BASED ON SECTION 304.9 FBC
 FG- 0.35 CFMS PER 1000 BTUH OF THE APPLIANCES. A) SHOW
 MEANS OF PROVIDING APPLIANCE INTERLOCK WITH THE FAN-
 SECTION 304.9.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-10-19 Cont ID  
Sent By ccole Date 2021-10-19 Time 16:18 Rev Time 0.00
Received By ccole Date 2021-10-19 Time 16:18 Sent To  
Notes
2021-10-19 16:31:123RD REVIEW FBC-2020 FUEL GAS
 PERMIT- 21041585
 10/19/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST AND 2ND REVIEW ARE LISTED BELOW WITH ADDITIONAL
 NOTES IN CAPS FOR FURTHER CLARIFICATION.
  
 1) FAILED ITEMS 1C & G.
  
 C) FAILED. SHEET P2: USING PIPE SIZING TABLE 402.4(4)
 LISTED ON THE PLAN, THE 1-INCH LINE IS UNDERSIZED FOR
 THE 1,046,000 BTU LOAD AT A DEVELOPED LENGTH OF 68 FT.
 ACCORDING TO THE TABLE THE 1-INCH CAN SUPPLY MAXIMUM
 907,000 BTU'S.
  
 G) FAILED. ITEMS 2, 4 & 5. BASED ON THE MANUFACTURER'S
 SPECIFICATIONS REGULATORS ARE REQUIRED FOR THE
 INDIVIDUAL SUPPLY LINES TO THE WATER HEATER AND COOKING
 APPLIANCES. THE RISER SHOWS THE LOW PRESSURE SIDE OF
 THE REGULATOR TO BE 9.5 TO 13 IN.W.C., HOWEVER THE
 SUBMITTED SPECS FOR THE COOKING APPLIANCES ARE
 INDICATING INPUT PRESSURES OF 5 IN.W.C.
 2) FAILED. SHOW THE REQUIRED PIPE UNIONS AT THE
 REGULATORS.
 4) FAILED. REGULATORS ARE REQUIRED FOR THE SUPPLY LINES
 TO THE COOKING APPLIANCES BASED ON THE GAS INPUT
 PRESSURES REQUIRED BY THE APPLIANCE MANUFACTURERS. SHOW
 THE LOCATIONS OF THE REGULATORS IN THE ISOMETRIC
 DRAWING AND PROVIDE VENTING DETAILS IF REQUIRED BY THE
 MANUFACTURER- SECTION- 410.3 FBC FG.
 5) FAILED. THE GASTITE REGULATOR SPECIFIED IS LIMITED
 TO 2 PSI AND THE PLAN INDICATES A 5 PSI SYSTEM. PLEASE
 INDICATE THE MAKE AND MODEL OF THE LOW PRESSURE
 REGULATOR AND SUBMIT SPECS MARKED UP TO SHOW THE INLET
 AND OUTLET PRESSURES AND PIPE SIZES- SECTION 410.2. ON
 THE RISER, PLEASE SHOW THE REQUIRED PIPE UNIONS WITH
 ONE FT. OF EITHER SIDE OF THE REGULATOR- SECTION 410.2
 (7).
  
 2) FAILED. NEW DETAIL E ON P1: PLEASE INDICATE THE TYPE
 AND SIZE OF VENT DUCT AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE VENT AND TERMINATION CAP. THE
 SPECS SUBMITTED FOR THE WATER HEATER DO NOT PROVIDE
 VENTING INFORMATION.
  
 3) FAILED. THE SUBMITTED COMBUSTION CALCULATIONS BY
 PAUL ORR P.E. INDICATE A DEFICIENT AMOUNT OF INDOOR
 COMBUSTION AIR FOR THE WATER HEATER AND COOKING
 APPLIANCES, AND THAT ADDITIONAL AIR MUST BE PROVIDED.
 AT THIS TIME NO OTHER MEANS OF SUPPLYING THAT AIR HAS
 BEEN PROVIDED. THE CALC INDICATE 8442.67 CU. FT. OF
 ROOM VOLUME HOWEVER BASED ON THE 1,046,000 BTU LOAD-
 52,300 CU. FT. REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-09-08 Cont ID  
Sent By ccole Date 2021-09-08 Time 11:19 Rev Time 0.00
Received By ccole Date 2021-09-08 Time 08:09 Sent To  
Notes
2021-09-08 11:19:162ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21041585
 9/8/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BEOW WITH ADDITIONAL NOTES IN
 CAPS FOR FURTHER CLARIFICATION.
  
 1) FAILED. SHEET P2 GAS ISOMETRIC- FBC FG: FAILED ITEMS
 A, B, C, D, & G.
  
 A) FAILED. REMOVE OR CORRECT THE REFERENCE TO TABLE
 1216.2 WHICH IS A TABLE NOT CONTAINED IN THE FBC FG.
 THE CORRECT PIPE SIZING TABLE FOR THE 5 PSI SYSTEM WAS
 NOT PROVIDED. FOR THE PURPOSES OF THE REVIEW IT IS
 ASSUMED THE TABLE USED FOR THE HIGH PRESSURE 1-INCH
 GALVANIZED MAIN SUPPLY PIPE IS 402.4(7) 5.0 PSI. THE
 TABLE USED FOR THE LOW PRESSURE LINE HAS NOT BEEN
 PROVIDED. ACCORDING TO TABLE 402.4(7) THE 1-INCH HIGH
 PRESSURE PIPE IS SUFFICIENTLY SIZED.
  
 B) FAILED. SHOW THE LOCATION OF THE METER AND LABEL IT
 AS NEW OR EXISTING- SECTION 402.1. NO INFORMATION
 PROVIDED.
  
 C) FAILED. LIST THE PIPE SIZING TABLE(S) USED IN THE
 DESIGN OF THE SYSTEM- SECTION 402.3. SEE COMMENT #1A
 NOTES ABOVE. IN ORDER TO PERFORM A COMPLETE REVIEW, THE
 LOW PRESSURE SIZING TABLE USED FOR THE SYSTEM MUST BE
 PROVIDED. THE RISER IS INDICATING LOW PRESSURE OF 9.5-
 13 IN.W.C. DOWNSTREAM OF THE REGULATOR. PLEASE INDICATE
 THE SIZE OF THE SUPPLY PIPE FROM THE REGULATOR TO THE
 MOST REMOTE OUTLET. THE DRAWING SHOWS A 1-INCH SLEEVE
 BUT NO GAS PIPE SIZE. IT IS ASSUMED A ?-INCH PIPE IS IN
 THE SLEEVE WHICH IS UNDERSIZED FOR A TOTAL LOAD OF
 1,046,000 BTUS- SEE SCHED-40 METALLIC LOW PRESSURE
 TABLES 402.4(1), 402.4(2), 402.4(3), AND 402.4(4) FBC
 FG.
  
 D) FAILED. PROVIDE THE TOTAL DEVELOPED LENGTH OF THE
 SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET, AND
 THE INDIVIDUAL CUT PIPE AND BRANCH LENGTH MEASUREMENTS-
 SECTION 402.4.1. PROVIDE THE TOTAL AND INDIVIDUAL HIGH
 PRESSURE AND LOW PRESSURE RUN LENGTHS.
  
 G) FAILED. SHOW REQUIRED SHUTOFF VALVES, REGULATORS,
 AND PIPE UNIONS ON THE BRANCH LINES TO THE APPLIANCES-
 SECTIONS 409.1 & 410.1. 1) TYPICAL SHUTOFF VALVES ARE
 MISLABELED AS FV (FIRE VALVES)- PLEASE CORRECT. 2) SHOW
 THE REQUIRED PIPE UNIONS AT THE REGULATOR. 3) SHOW THE
 LOCATION OF THE REQUIRED AUTOMATIC GAS SHUTOFF VALVE
 FOR THE COOKING APPLIANCES TO BE CONNECTED TO THE FIRE
 SUPPRESSION SYSTEM- SEC. 10.4.1 NFPA 96. PLEASE NOTE
 THE VALVES SHALL BE BELOW THE CEILING AND ACCESSIBLE.
 4) PLEASE NOTE THAT REGULATORS MAY BE REQUIRED FOR THE
 SUPPLY LINES TO THE COOKING APPLIANCES BASED ON THE GAS
 INPUT PRESSURES REQUIRED BY THE APPLIANCE
 MANUFACTURERS. 5) PLEASE INDICATE THE MAKE AND MODEL OF
 THE LOW PRESSURE REGULATOR AND SUBMIT SPECS MARKED UP
 TO SHOW THE INLET AND OUTLET PRESSURES AND PIPE SIZES-
 SECTION 410.2. ON THE RISER, PLEASE SHOW THE REQUIRED
 PIPE UNIONS WITH ONE FT. OF EITHER SIDE OF THE
 REGULATOR- SECTION 410.2 (7).
  
 2) FAILED. PROVIDE THE MAKE AND MODEL OF THE NEW
 TANKLESS WATER HEATER ON THE PLAN AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS- SECTION 624.1 FBC FG.
 THE WATER HEATER LOCATED IN THE INDOORS WILL REQUIRE
 COMBUSTION AIR AND A VENTING SYSTEM. PLEASE PROVIDE
 COMBUSTION AIR CALCULATIONS IN COMPLIANCE WITH SECTION
 304.1 FBC FG, AND A VENTING DIAGRAM AND VENT
 SPECIFICATIONS- SECTION 503.1 FBC FG. VENTING DIAGRAM
 NOT PROVIDED. SEE COMBUSTION AIR COMMENT #3 BELOW.
  
 3) FAILED. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 COOKING APPLIANCES AND INDICATE HOW THE AIR IS BEING
 PROVIDED- SECTION 304.1 FBC FG. THE SUBMITTED
 COMBUSTION CALCULATIONS BY PAUL ORR P.E. INDICATE A
 DEFICIENT AMOUNT OF INDOOR COMBUSTION AIR FOR THE WATER
 HEATER AND COOKING APPLIANCES, AND THAT ADDITIONAL AIR
 MUST BE PROVIDED. AT THIS TIME NO OTHER MEANS OF
 SUPPLYING THAT AIR HAS BEEN PROVIDED.
  
 4) FAILED. SUBMIT MANUFACTURER'S FOR THE COOKING
 APPLIANCES- SECTION 623.1 FBC FG. NOT PROVIDED. THE
 SUBMITTALS MAY BE DEFERRED IN ACCORDANCE WITH SECTION
 107.3.4.1 WPB AMENDMENTS TO THE FBC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-06-15 Cont ID  
Sent By ccole Date 2021-06-15 Time 11:50 Rev Time 0.00
Received By ccole Date 2021-06-15 Time 09:26 Sent To  
Notes
2021-06-15 11:50:551ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21041585
 6/15/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P2 GAS ISOMETRIC- FBC FG:
 A) REMOVE OR CORRECT THE REFERENCE TO TABLE 1216.2
 WHICH IS A TABLE NOT CONTAINED IN THE FBC FG.
 B) SHOW THE LOCATION OF THE METER AND LABEL IT AS NEW
 OR EXISTING- SECTION 402.1
 C) LIST THE PIPE SIZING TABLE(S) USED IN THE DESIGN OF
 THE SYSTEM- SECTION 402.3.
 D) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM
 FROM THE METER TO THE MOST REMOTE OUTLET, AND THE
 INDIVIDUAL CUT PIPE AND BRANCH LENGTH MEASUREMENTS-
 SECTION 402.4.1.
 E) SHOW THE WATER HEATER AND THE BRANCH PIPE TO IT-
 SECTION 402.3.
 F) INDICATE THE TYPE AND SIZE OF PIPE SLEEVE- SECTION
 404.8.1.
 G) SHOW REQUIRED SHUTOFF VALVES, REGULATORS, AND PIPE
 UNIONS ON THE BRANCH LINES TO THE APPLIANCES- SECTIONS
 409.1 & 410.1.
  
 2) PROVIDE THE MAKE AND MODEL OF THE NEW TANKLESS WATER
 HEATER ON THE PLAN AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTION 624.1 FBC FG. THE WATER HEATER
 LOCATED IN THE INDOORS WILL REQUIRE COMBUSTION AIR AND
 A VENTING SYSTEM. PLEASE PROVIDE COMBUSTION AIR
 CALCULATIONS IN COMPLIANCE WITH SECTION 304.1 FBC FG,
 AND A VENTING DIAGRAM AND VENT SPECIFICATIONS- SECTION
 503.1 FBC FG.
  
 3) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOKING
 APPLIANCES AND INDICATE HOW THE AIR IS BEING PROVIDED-
 SECTION 304.1 FBC FG.
  
 4) SUBMIT MANUFACTURER'S FOR THE COOKING APPLIANCES-
 SECTION 623.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2022-01-05 Time   Rev Time 0.00
Received By aoliver Date 2021-12-20 Time 07:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-11-30 Time   Rev Time 0.00
Received By aoliver Date 2021-11-09 Time 07:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-10-19 Time   Rev Time 0.00
Received By aoliver Date 2021-09-21 Time 07:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-09-08 Time   Rev Time 0.00
Received By aoliver Date 2021-08-05 Time 11:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-29 Cont ID  
Sent By rmcphers Date 2021-06-29 Time 09:23 Rev Time 0.00
Received By rmcphers Date 2021-05-10 Time 10:27 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-06-29 Cont ID  
Sent By rmcphers Date 2021-06-29 Time 09:16 Rev Time 0.00
Received By rmcphers Date 2021-06-29 Time 09:16 Sent To  
Notes
2021-06-29 09:17:07NO NEW SPACE - SAME OCCUPANCY CLASSIFICATION

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2021-12-29 Cont ID  
Sent By medwards Date 2021-12-29 Time 16:48 Rev Time 0.00
Received By medwards Date 2021-12-29 Time 16:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-11-22 Cont ID  
Sent By medwards Date 2021-11-22 Time 14:56 Rev Time 0.00
Received By medwards Date 2021-11-22 Time 14:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-10-04 Cont ID  
Sent By medwards Date 2021-10-04 Time 10:34 Rev Time 0.00
Received By medwards Date 2021-10-04 Time 10:34 Sent To  
Notes
2021-10-04 10:35:113RD REVIEW FBC-2020 MECHANICAL
 PERMIT-21041585
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: THE KITCHEN OUTSIDE AIR CALCULATION MUST
 BE CALCULATED USING THE KITCHENS FIGURES UNDER THE FOOD
 AND BEVERAGE SERVICE OCCUPANCY CLASSIFICATION IN FBC M
 TABLE 403.3.1.1
 1029 CFM?S/1000 = 1.029 X 20 X 7.5 = 154.35; 1029 X .12
 = 123.48; 154.35 + 123.48 = 278 CFM?S OF REQUIRED
 OUTSIDE AIR. 1029 X .7 = 720 CFM?S OF REQUIRED EXHAUST
 AIR FOR THE KITCHEN.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-08-23 Cont ID  
Sent By medwards Date 2021-08-23 Time 08:07 Rev Time 0.00
Received By medwards Date 2021-08-23 Time 08:07 Sent To  
Notes
2021-08-23 08:08:47I DO NOT SEE ANY REVISED MECHANICAL SHEETS THAT ARE
 MENTIONED IN THE THIRSTY TURTLE REVIEW LETTER. PLEASE
 MAKE SURE ALL DOCUMENTS ARE SUBMITTED IN THE NEXT
 REVIEW CYCLE.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-06-11 Cont ID  
Sent By medwards Date 2021-06-11 Time 11:55 Rev Time 0.00
Received By medwards Date 2021-06-11 Time 11:55 Sent To  
Notes
2021-06-11 11:55:201ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21041585
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ACCORDING TO OUR RECORDS THIS APPEARS TO BE A CHANGE
 OF USE FROM RETAIL TO A-2. IF THIS IS NOT A CHANGE OF
 USE PLEASE PRESENT DOCUMENTATION THAT IT WAS CHANGED
 FROM RETAIL TO A-2.
  
 2) PLEASE PROVIDE A MECHANICAL DEMO DRAWING. WITHOUT
 THIS I CANNOT COMPLETE THE REVIEW AND THERE MAY BE
 ADDITIONAL COMMENTS ON THE NEXT CYCLE. FBC 107.2.1
  
 3) PLEASE PROVIDE AN OUTDOOR AIR CALCULATION FOR EACH
 USE OF SPACE IN ACCORDANCE WITH FBC M 403.3.1.1 AND
 TABLE 403.3.1.1 AND NOT BY THE ARCHITECTURAL OCCUPANT
 COUNT.
  
 4) PLEASE PUT A NOTE ON THE MECHANICAL DRAWING THAT
 STATES THE HOOD AND GREASE DUCT WILL NOT BE REVIEWED
 UNDER THIS PERMIT AS IT WILL REQUIRE A SEPARATE PERMIT
 AND MECHANICAL REVIEW.
  
 5) PLEASE PUT A NOTE ON THE MECHANICAL DRAWING THAT
 STATES THE REFRIGERATION WILL NOT BE REVIEWED UNDER
 THIS PERMIT AS IT WILL REQUIRE A SEPARATE PERMIT AND
 MECHANICAL REVIEW.
  
 6) PLEASE CORRECT THE SCOPE TO REPRESENT THE WORK BEING
 COMPLETED UNDER THIS PERMIT AS THERE IS NEW DUCTWORK
 BEING ADDED TO THE EXISTING TRUNK LINE.
  
 7) PLEASE PROVIDE AN EQUIPMENT SIZING CALCULATIONS. FBC
 EC 403.2.1
  
 8) PLEASE PROVIDE INFORMATION ON THE EXISTING
 MECHANICAL UNITS TO VERIFY THE CFM?S. FBC 107.2.1
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2022-01-05 Cont ID  
Sent By ccole Date 2022-01-05 Time 14:27 Rev Time 0.00
Received By ccole Date 2022-01-05 Time 08:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2021-11-30 Cont ID  
Sent By ccole Date 2021-11-30 Time 08:35 Rev Time 0.00
Received By ccole Date 2021-11-29 Time 16:51 Sent To  
Notes
2021-11-30 08:37:324TH REVIEW FBC-2020 PLUMBING
 PERMIT- 21041585
 11/30/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST, 2ND, AND 3RD REVIEWS ARE LISTED BELOW WITH
 ADDITIONAL NOTES IN CAPS FOR FURTHER CLARIFICATION.
  
 1) FAILED ITEMS C, E, & F- SEE BELOW.
  
 C) FAILED. SHOW THE WIDTH OF THE NEW COMPARTMENT DOORS-
 SECTION 404.2.3 FBC ACC. (SHEET S2 SHOWS COMPARTMENT
 DOORS AT 2'6' WIDTH, HOWEVER MINIMUM DOOR WIDTH IS 32"-
 SECTION- SECTIONS 604.8.1.2 & 404.2.3 FBC ACC. PLEASE
 UPDATE SHEET S1 WHICH STILL SHOWS THE DOORS SWINGING
 IN.)
  
 E) FAILED. PROVIDE THE WIDTH MEASUREMENT BETWEEN THE
 NEW MEN'S COMPARTMENT PARTION AND THE NEW URINAL
 PARTION- SECTION 405.3.5. (SHEET S2 SHOWS 1'11" CLEAR
 WIDTH FOR THE URINAL STALL, HOWEVER URINALS SHALL NOT
 BE CLOSER THAN 15 INCHES FROM CENTER TO SIDE WALL OR
 PARTITION- SECTION 405.3.1 FBC P. PLEASE NOTE THAT
 ACCESSIBLE URINALS SHALL HAVE 30X48-INCH CLEAR FLOOR
 SPACE APPROACHES- SECTION 605.3 FBC ACC. IS THE URINAL
 INTENDED TO BE ACCESSIBLE?).
  
 F) FAILED. REFER TO SECTION 604.8 AND PROVIDE THE MEN'S
 WATER CLOSET CLEAR FLOOR SPACE WIDTH DIMENSION IN THE
 DRAWING. (SHEET S2 SHOWS DEFICIENT CLEAR FLOOR SPACE-
 MINIMUM 60 INCHES MEASURED PERPENDICULAR FORM THE SIDE
 WALL AND 56 INCHES MEASURED PERPENDICULAR FROM THE REAR
 WALL ? SECTION 604.3.1 FBC ACC.
  
 2) FAILED. P1 & P2 GREASE WASTE AND INTERCEPTOR: ITEM
 D.
  
 D) SHEET P-2: THE REVISED CALCULATION IS INCORRECT. THE
 GPM FLOW RATE IS 150.3 AT 75% CAPACITY IN ACCORDANCE
 WITH THE PDI METHOD. THE DESIGNER HAS INCORRECTLY
 REDUCED THAT RATE BY 25% DOWN TO 112.7 GPM WHICH IS NOT
 IN COMPLIANCE. PLEASE SELECT A GREASE INTERCEPTOR THAT
 HAS THE REQUIRED CAPACITY AND INDICATE THE MAKE AND
 MODEL ON THE PLAN. PLEASE NOTE SHEET P1 SHOWS A
 REPLACED INTERCEPTOR AND P2 SHOWS AN EXISTING 50 GPM
 INTERCEPTOR. PLEASE NOTE MANUFACTURER'S SPECIFICATIONS
 FOR A "DRAIN-NET TECHNOLOGIES APGI SERIES INTERCEPTOR"
 HAVE BEEN SUBMITTED, HOWEVER THWE CUT SHEET DOES NOT
 INDICATE THE SELCTED MODEL TO BE INSTALLED AND DOES NOT
 INDICATE THE PRODUCT HAS BEEN DESIGNED AND TESTED IN
 ACCORDANCE WITH THE LISTING STANDARDS UNDER SECTION
 1003.3.4 FBC P- ASME A112.14.3, ASME A112.14.4, CSA
 B481.1, PDIG101, OR PDI G102.
  
 6) FAILED. P1 & P2: THE ISOMETRIC SHOWS TWO EXPANSION
 TANKS BOTH OF WHICH ARE NOT IN THE CORRECT LOCATIONS.
 IF INSTALLING AN EXPANSION TANK IT SHALL BE LOCATED ON
 THE COLD WATER INLET PIPE DOWNSTREAM OF ALL CHECK
 VALVES, OR PRV'S- SECTION 607.3 FBC P.
  
 8) FAILED. P1 & P2: WHERE HOT WATER IS SUPPLIED TO A
 LAVATORY, THE WATER SHALL BE TEMPERED IN ACCORDANCE
 WITH SECTIONS 419.5 & 607.1.2 FBC P. PLEASE PROVIDE A
 MIXING VALVE THAT CONFORMS TO ASSE 1070. PROVIDE A
 PIPING DETAIL ON THE PLAN FOR INSTALLATION. DUE TO THE
 INCONSISTENCY OF THE DETAILS IT IS NOT CLEAR HOW
 TEMPERED WATER WILL BE PROVIDED TO THE LAVATORIES-
 PLEASE COMPLY AND NOTE THE REVISED WATER ISOMETRIC
 SHOWS A MASTER MIXNG VALVE AND A MIXING VALVE AT THE
 3-COMPARTMENT SINK. PLEASE INDICATE THE TEMPERATURE OF
 THE HOT WATER BEING SUPPLIED TO THE 3-COMPARTMENT SINK
 AND MOP SINK- SEE SECTION 607.1 FBC P.
  
 NEW COMMENTS BASED ON REVISED SHEETS.
  
 1) SHEET S2: PLEASE SHOW THE CENTERLINE OF THE TOILET
 PAPER DISPENSER AT 7-9 INCHES MEASURED FROM THE FRONT
 OF THE WATER CLOSET- SECTION AND FIGURE 604.7 FBC ACC.
  
 2) P-1: THE INDIRECT WASTE DETAIL FOR THE 3-COMPARTMENT
 SINK IS INCORRECT. EACH WELL OF THE SINK SHALL
 DISCHARGE INDEPENDENTLY TO THE FLOOR SINK- SECTION
 802.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-10-19 Cont ID  
Sent By ccole Date 2021-10-19 Time 15:05 Rev Time 0.00
Received By ccole Date 2021-10-19 Time 15:05 Sent To  
Notes
2021-10-19 15:07:523RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21041585
 10/19/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST AND 2ND REVIEWS ARE LISTED BELOW WITH ADDITIONAL
 NOTES IN CAPS FOR FURTHER CLARIFICATION.
  
 1) FAILED. SHEET P1: PLEASE PROVIDE A CLEAR SCOPE OF
 WORK FOR THE MEN'S AND WOMEN'S RESTROOMS. CLARIFY IF
 THE FIXTURES, COMPARTMENT WALLS, LAVATORY COUNTERS,
 MIRRORS, DISPENSERS ETC. ARE TO BE REPLACED OR
 RELOCATED. PLEASE NOTE THAT THE ENLARGED DIMENSIONED
 DRAWINGS WILL BE REQUIRED FOR RECONFIGURED BATHROOMS
 AND REPLACEMENT OF COMPARTMENT WALLS. THE CURRENT
 CONFIGURATION IN THE MEN'S RESTROOM IS NOT IN
 COMPLIANCE WITH SECTION 405.3.4 FBC P- THE WATER CLOSET
 BY THE LAVATORY SHALL BE ENCLOSED IN A COMPARTMENT. IN
 RESPONSE TO THE COMMENT NEW PLAN SHEET S-2 HAS BEEN
 PROVIDED. PLEASE COMPLY WITH ITEMS A- I BELOW.
 A) DESIGN CRITERIA: PLEASE INDICATE THE PLANS ARE
 DESIGNED IN ACCORDANCE WITH THE FBC- 2020 SEVENTH
 EDITION ACCESSIBILITY CODE.
 B) THE NEW COMPARTMENT DOORS SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACES FOR THE LAVATORIES- SECTION 603.2.3
 FBC ACC. PLEASE SEE EXCEPTION 2 WHICH MAY BE
 APPLICABLE.
 C) SHOW THE WIDTH OF THE NEW COMPARTMENT DOORS- SECTION
 404.2.3 FBC ACC.
 D) PROVIDE THE DIMENSIONS OF THE STANDARD WOMEN'S
 COMPARTMENT- SECTION 405.3.1 FBC P.
 E) PROVIDE THE WIDTH MEASUREMENT BETWEEN THE NEW MEN'S
 COMPARTMENT PARTION AND THE NEW URINAL PARTION- SECTION
 405.3.5
 F) REFER TO SECTION 604.8 AND PROVIDE THE MEN'S WATER
 CLOSET CLEAR FLOOR SPACE WIDTH DIMENSION IN THE
 DRAWING.
 G) DETAIL B- CORRECT THE 1'3" MEASUREMENT TO THE TOP OF
 THE LAVATORY, AND THE 1'6" MEASUREMENT TO THE MIRROR-
 SECTIONS 606.3 & 606.3.
 H) DETAIL C- REFER TO SECTION AND FIGURE 604.5.2 AND
 SHOW THE GRAB BAR WILL EXTEND FROM THE CENTERLINE OF
 THE WATER CLOSET 12 INCHES MINIMUM ON THE SIDE ADJACENT
 TO THE WALL AND 24 INCHES MINIMUM ON THE OTHER SIDE.
 I) PLEASE PROVIDE EITHER DETAILS OR NOTES INDICATING
 THE MAXIMUM MOUNTING HEIGHTS FOR SOAP. PAPER TOWEL AND
 OTHER SANITARY DISPENSERS- SECTION 308.
  
 2) FAILED. P1 & P2 GREASE WASTE AND INTERCEPTOR: ITEMS
 A, B, & C BELOW. IN RESPONSE TO THE COMMENTS NEW
 PLUMBING PLAN SHEETS HAVE BEEN PROVIDED FOR THE GREASE
 INTERCEPTOR. PLEASE COMPLY WITH ITEMS A- D BELOW
 A) SHEET P-2: INDICATE THE DESIGN STANDARD USED FOR THE
 CALCULATIONS- SECTION 1003.3.4 FBC P.
 B) P-2: IT APPEARS THAT ONLY ONE SINK FROM EACH
 3-COMPARTMENT SINK HAS BEEN USED TO DETERMINE TOTAL CU.
 IN CALCULATION. BASED ON THE SIZES SHOWN THE SINKS HAVE
 A TOTAL CAPACITY OF 16,856 CU. INCHES.
 C) P-2: THE CALCULATIONS DO NOT INCLUDE THE MOP SINK.
 PLEASE CORRECT THE RISER DRAWING SHOWING THE MOP SINK
 DRAIN CONNECTING TO THE SANITARY DRAIN.
 D) P-2: PLEASE REFER TO SECTION 8.3.2 OF THE PDI-G101.
 THE PDI METHOD OF CALCULATION ALLOWS THE DRAINAGE LOAD
 TO BE 75% OF FIXTURE CAPACITY BECAUSE OF THE ITEMS
 BEING WASHED DISPLACING ABOUT 25% OF FIXTURE CAPACITY.
 BASED ON THE FIXTURES AND DATA SHOWN IN THE
 CALCULATIONS (N.I. MOP SINK) I AM CALCULATING 104 GPM
 FLOW RATE. THE PLAN SHOWS AN EXISTING 50 GPM
 INTERCEPTOR WHICH IS UNDERSIZED FOR THE NEW LOAD.
  
 6) FAILED. P1 & P2: PROVIDE AN ENLARGED PIPING DRAWING
 FOR THE WATER HEATERS SHOWING LOCATIONS OF THERMAL
 EXPANSION TANKS, RECIRCULATION PUMPS, SHUTOFF VALVES,
 CHECK VALVES, ETC.- SECTIONS 607.2.1.2, 607.3 FBC P.
 THREE DIFFERENT DRAWINGS ARE NOW SHOWN IN RESPONSE TO
 THE COMMENT BUT THE NEW DRAWINGS DO NOT MATCH. DETAIL F
 ON SHEET P1 SHOWS A MASTER MIXING VALVE, DETAIL ON P3
 DOES NOT SHOW A MIXING VALVE, AND DETAIL A ON P2 DOES
 NOT SHOW THE RECIRCULATION PUMP. DETAIL A ON P2 ALSO
 SHOWS THE HWR LINE CONNECTING ONLY TO THE HW LINE AND
 NOT THE COLD WATER INLET AND MIXING VALVE- SEE SECTION
 607.2.2 FBCP AND CORRECT THE DRAWINGS.
  
 8) FAILED. P1 & P2: WHERE HOT WATER IS SUPPLIED TO A
 LAVATORY, THE WATER SHALL BE TEMPERED IN ACCORDANCE
 WITH SECTIONS 419.5 & 607.1.2 FBC P. PLEASE PROVIDE A
 MIXING VALVE THAT CONFORMS TO ASSE 1070. PROVIDE A
 PIPING DETAIL ON THE PLAN FOR INSTALLATION. PLEASE SEE
 NOTE UNDER COMMENT #8 ABOVE. DUE TO THE INCONSISTENCY
 OF THE DETAILS IT IS NOT CLEAR HOW TEMPERED WATER WILL
 BE PROVIDED TO THE LAVATORIES. PLEASE NOTE THAT DETAIL
 F ON P1 APPEARS TO SHOW TEMPERED WATER TO ALL OF THE
 FIXTURES WHICH IS NON-COMPLAINT FOR FIXTURES REQUIRING
 HOT WATER SUCH AS THE 3-COMPARTMENT SINKS AND MOP SINK-
 SECTION 607.1 FBC P.
  
 10) FAILED P1 & P2: PLEASE PROVIDE A COMPLETE PLUMBING
 FIXTURE SCHEDULE THAT INCLUDES THE DISHWASHER, HUB
 DRAINS, FLOOR DRAINS, AND THE REPLACED RESTROOM
 FIXTURES- (IF APPLICABLE TO THE SCOPE)- SECTION 107.2.1
 WPB. PLEASE RELOCATE THE BATHROOM FIXTURE SCHEDULE ON
 S2 TO THE PLUMBING PLANS- SECTION 107.2.1 WPB.
  
 13) FAILED P2: PROVIDE A WATER HAMMER ARRESTOR AND
 BACKFLOW PREVENTER FOR THE WATER SUPPLY LINE TO THE ICE
 MAKER. PLEASE NOTE THAT THIS COMMENT IS APPLICABLE TO
 ANY OTHER REQUIRED WATER SUPPLY LINES TO APPLIANCES AND
 EQUIPMENT- SECTIONS 604.9 & 608.3 FBC P. THE SUPPLY
 LINES TO ICE MAKERS, DISHWASHER AND OTHER FIXTURES AND
 APPLIANCES WITH QUICK-CLOSING VALVES REQUIRE WATER
 HAMMER ARRESTORS- SECTION 604.9 FBC P. THE SUPPLY LINES
 TO ICE MAKERS, DISHWASHER, FILTERS, DISPENSERS REQUIRE
 BACKFLOW PREVENTERS- SECTION 608.3 PLEASE CLEARLY SHOW
 THE LOCATIONS OF THE REQUIRED DEVICES.
  
 15) FAILED P1 & P2: PROVIDE HOT WATER PIPE INSULATION
 SPECIFICATIONS- TABLE C403.2.10 FBC EC. NO INFORMATION
 PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-09-08 Cont ID  
Sent By ccole Date 2021-09-08 Time 10:00 Rev Time 0.00
Received By ccole Date 2021-09-08 Time 08:09 Sent To  
Notes
2021-09-08 10:00:242ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21041585
 9/8/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN
 CAPS FOR FURTHER CLARIFICATION.
  
 1) FAILED. SHEET P1: PLEASE PROVIDE A CLEAR SCOPE OF
 WORK FOR THE MEN'S AND WOMEN'S RESTROOMS. CLARIFY IF
 THE FIXTURES, COMPARTMENT WALLS, LAVATORY COUNTERS,
 MIRRORS, DISPENSERS ETC. ARE TO BE REPLACED OR
 RELOCATED. PLEASE NOTE THAT THE ENLARGED DIMENSIONED
 DRAWINGS WILL BE REQUIRED FOR RECONFIGURED BATHROOMS
 AND REPLACEMENT OF COMPARTMENT WALLS. THE CURRENT
 CONFIGURATION IN THE MEN'S RESTROOM IS NOT IN
 COMPLIANCE WITH SECTION 405.3.4 FBC P- THE WATER CLOSET
 BY THE LAVATORY SHALL BE ENCLOSED IN A COMPARTMENT. NEW
 ACCESSIBLE PLUMBING FIXTURES ARE BEING INSTALLED IN THE
 BATHROOMS WHICH SHALL BE IN COMPLIANCE WITH THE FBC
 ACC. PLEASE PROVIDE ENLARGED DRAWINGS AND DETAILS
 SHOWING:
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
  
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
  
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
  
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
  
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
  
 F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOORS- SECTION 606.3.
  
 G) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2
  
 IF ACCESSORIES ARE BEING REPLACED PLEASE SHOW:
  
 H) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3.
  
 I) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
  
 J) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
  
 K) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
  
 AS REQUESTED IN COMMENT #10 BELOW, PROVIDE FIXTURE
 SCHEDULES INDICATING MAKES AND MODELS.
  
 2) FAILED. P1 & P2 GREASE WASTE AND INTERCEPTOR: ITEMS
 A, B, & C BELOW
  
 A) FAILED- P1 & P2: PROVIDE GREASE WASTE CALCULATIONS
 IN ACCORDANCE WITH SECTION 1003.3.5 OR 1003.3.7 FBC P.
 CLEAR WATER WASTE FROM THE HANDSINKS SHALL NOT DRAIN
 INTO THE GREASE WASTE LINE AND INTERCEPTOR. PLEASE
 REMOVE THE SINKS FROM THE CALCULATIONS- SECTION
 1003.3.1 FBC P.
  
 B) FAILED- P1 & P2. INDICATE THE SIZE AND TYPE OF
 EXISTING GREASE INTERCEPTOR- GRAVITY OR
 HYDROMECHANICAL? (1003.3.5 & 1003.3.7) CAPACITY AND
 LOCATION OF THE EXISTING GREASE INTERCEPTOR NOT SHOWN.
  
 C) FAILED- P1 & P2:. THE HAND SINKS AND FLOOR DRAIN IN
 THE BEER COOLER SHALL NOT DRAIN INTO THE GREASE WASTE
 LINE- SECTION 1003.3.1 FBC P. HANDSINKS ARE NOT
 SIGNIFICANT GREASE CONTRIBUTORS, AND THE FLOOR DRAIN IN
 THE COOLER SHOULD ONLY BE DRAINING CLEAR WATER WASTE.
 THE HANDSINK DRAINAGE HAS BEEN CORRECTED ON THE
 DRAWINGS, BUT THE CALCULATIONS NEED TO BE CORRECTED TO
 REMOVE THE HANDSINKS. PLEASE NOTE THAT THE FLOOR DRAINS
 IN THE COOKING KITCHEN AREA SHALL DRAIN INTO THE GREASE
 WASTE LINE AND INTERCEPTOR- SECTION 1003.3.1 FBC P.
  
 3) FAILED. P1 & P2: THE HUB DRAIN FOR THE DISHWASHER
 SHOWN IN THE ISO IS NOT SHOWN IN THE PLUMBING FLOOR
 PLAN-- SECTION 107.2.1 WPB. PLEASE LABEL THE HUB DRAINS
 CORRECTLY ON THE FLOOR PLAN- THEY ARE NOT FLOOR DRAINS.
 P1 SHOWS FLOOR SINKS AT THE 3-COMPARTMENT SINKS AND
 DISHWASHER, P2 SHOWS HUB DRAINS. PLEASE NOTE THAT FLOOR
 SINKS ARE INCLUDED IN THE SCHEDULE ON P1.
  
 3) FAILED P1 & P2: THE GREASE WASTE DRAIN LINE REQUIRES
 NOT LESS THAN ONE VENT PIPE THAT EXTENDS TO THE
 OUTDOORS- SECTIONS 904.1 & 918.7 FBC P. THE REVISED
 PLAN NOW SHOWS A VTR FOR THE GREASE WASTE LINE BUT NOT
 FOR THE SANITARY WHICH IS A SEPARATE SYSTEM AND
 REQUIRES THE VTR.
  
 4) FAILED. P1 & P2: THE FLOOR DRAINS ARE NOT PROPERLY
 VENTED. IT APPEARS A COMBINATION WASTE AND VENT SYSTEM
 IS BEING CREATED, HOWEVER THOSE SYSTEMS ARE NOT ALLOWED
 FOR GREASE WASTE DRAINS- SECTION 915.1 FBC P. PLEASE
 LOCATE VENTS IN THE LINE THAT DO NOT EXCEED THE 12 FT.
 MAXIMUM DISTANCE FROM THE FLOOR DRAIN TRAPS- TABLE
 909.1 FBC P. PLEASE NOTE THE AAV'S CAN ONLY BE USED AS
 INDIVIDUAL, BRANCH, OR CIRCUIT VENTS- SECTION 918.3 FBC
 P. THE FLOOR DRAINS IN THE COOKING AREA OF THE LITCEHN
 SHALL DRAIN INTO THE GREASE WASTE LINE AND INTERCEPTOR-
 SECTION 1003.3.1. THE CORRECTEDE PLAN SHALL ALSO SHOW
 HOW THE FIXTURES ARE TO BE VENTED.
  
 6) FAILED. P1 & P2: PROVIDE AN ENLARGED PIPING DRAWING
 FOR THE WATER HEATERS SHOWING LOCATIONS OF THERMAL
 EXPANSION TANKS, RECIRCULATION PUMPS, SHUTOFF VALVES,
 CHECK VALVES, ETC.- SECTIONS 607.2.1.2, 607.3 FBC P.
 THE REVISED PLAN SHOWS A NEW RECIRCULATION PUMP IST TO
 BE INSTALLED BUT IT IS NOT SHOWN IN THE CORRECT
 LOCATION AND NO RECIRCULATION LINE IS SHOWN IN THE
 WATER ISOMETRIC. PLEASE ADD THE PUMP TO THE SCHEDULE.
  
 7) FAILED. P1 & P2: IT APPEARS THE LENGTHS OF THE HOT
 WATER SUPPLY PIPES TO THE LAVATORIES FROM THE WATER
 HEATER IS EXCEEDING THE MAXIMUM ALLOWABLE LENGTH AS
 INDICATED IN TABLE C404.5.1 FBC EC. EITHER POINT OF USE
 WATER HEATERS AT THE LAVATORIES OR A RECIRCULATION PUMP
 FOR THE HOT WATER SYSTEM SHALL BE INSTALLED. SEE
 COMMENT #6 NOTES ABOVE.
  
 8) FAILED. P1 & P2: WHERE HOT WATER IS SUPPLIED TO A
 LAVATORY, THE WATER SHALL BE TEMPERED IN ACCORDANCE
 WITH SECTIONS 419.5 & 607.1.2 FBC P. PLEASE PROVIDE A
 MIXING VALVE THAT CONFORMS TO ASSE 1070. PROVIDE A
 PIPING DETAIL ON THE PLAN FOR INSTALLATION. PLEASE ADD
 THE WORD LAVATORIES TO NOTE #4 ON P1. CLARIFY IF THE
 MIXING VALVES ARE EXISTING OR NEW.
  
 9) FAILED P1 & P2: PROVIDE AN INDIRECT WASTE DETAIL FOR
 THE 3-COMPARTMENT SINKS- SECTION 802.1.1 FBC P. THE
 DETAIL DOES NOT SHOW THE EACH WELL OF THE 3-COMPARTMENT
 SINKS DRAINING SEPARATELY INTO THE RECEPTOR.
  
 10) FAILED P1 & P2: PLEASE PROVIDE A COMPLETE PLUMBING
 FIXTURE SCHEDULE THAT INCLUDES THE DISHWASHER, HUB
 DRAINS, FLOOR DRAINS, AND THE REPLACED RESTROOM
 FIXTURES- (IF APPLICABLE TO THE SCOPE)- SECTION 107.2.1
 WPB. DISHWASHER, FLOOR SINKS, AND RESTROOM FIXTURES NOT
 INCLUDED.
  
 11) FAILED. P1: THE PLAN SHOWS ICE MAKERS, ICE BINS,
 COOLERS, FROSTER, ETC. WITH NO DRAINS DIRECTLY BELOW
 THEM. PLEASE CLARIFY HOW DRAINAGE FROM THESE FIXTURES
 WILL BE CONVEYED INTO THE SANITARY SYSTEM. PLEASE NOTE
 THAT CLEAR WATER WASTE SHALL NOT DRAIN INTO THE GREASE
 WASTE LINE- SECTION 1003.3.1 FBC P. PLEASE REVISE THE
 SANITARY ISOMETRIC DRAWING TO MATCH WITH THE FLOOR
 PLAN. THERE ARE SEVERAL MISSING FLOOR DRAINS AND DRAIN
 LINES.
  
 12) FAILED P1 & P2: SHOW AN EXISTING OR NEW CLEANOUT AT
 THE JUNCTION OF THE GREASE WASTE LINE AND SEWER
 JUNCTION- SECTION 708.1.3 FBC P. LOCATION OF EXISTING
 GREASE INTERCEPTOR AND CLEANOUTS NOT SHOWN.
  
 13) FAILED P2: PROVIDE A WATER HAMMER ARRESTOR AND
 BACKFLOW PREVENTER FOR THE WATER SUPPLY LINE TO THE ICE
 MAKER. PLEASE NOTE THAT THIS COMMENT IS APPLICABLE TO
 ANY OTHER REQUIRED WATER SUPPLY LINES TO APPLIANCES AND
 EQUIPMENT- SECTIONS 604.9 & 608.3 FBC P. REVISE THE
 NOTE ON THE ISO TO INCLUDE THE OTHER FIXTURES AND
 APPLIANCESAND NOT JUST ON E OF THE ICE BINS.
  
 15) FAILED P1 & P2: PROVIDE HOT WATER PIPE INSULATION
 SPECIFICATIONS- TABLE C403.2.10 FBC EC. NO INFORMATION
 PROVIDED.
  
 16) FAILED P1 & P2: INDICATE THE TYPE OF FINISH WALL
 AND FLOOR MATERIALS TO BE INSTALLED IN THE RESTROOMS
 AND AT THE MOP SINK- SEE SECTIONS 310.3 FBC P AND
 1210.2. FBC B. THE LOCTION OF THE REQUIRED MOP SINK AND
 WALL SURROUND MATERIAL NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-06-15 Cont ID  
Sent By ccole Date 2021-06-15 Time 11:10 Rev Time 0.00
Received By ccole Date 2021-06-15 Time 07:42 Sent To  
Notes
2021-06-15 11:11:091ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21041585
 6/15/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: PLEASE PROVIDE A CLEAR SCOPE OF WORK FOR
 THE MEN'S AND WOMEN'S RESTROOMS. CLARIFY IF THE
 FIXTURES, COMPARTMENT WALLS, LAVATORY COUNTERS,
 MIRRORS, DISPENSERS ETC. ARE TO BE REPLACED OR
 RELOCATED. PLEASE NOTE THAT THE ENLARGED DIMENSIONED
 DRAWINGS WILL BE REQUIRED FOR RECONFIGURED BATHROOMS
 AND REPLACEMENT OF COMPARTMENT WALLS. THE CURRENT
 CONFIGURATION IN THE MEN'S RESTROOM IS NOT IN
 COMPLIANCE WITH SECTION 405.3.4 FBC P- THE WATER CLOSET
 BY THE LAVATORY SHALL BE ENCLOSED IN A COMPARTMENT.
  
 2) P1 & P2 GREASE WASTE AND INTERCEPTOR:
 A) PROVIDE GREASE WASTE CALCULATIONS IN ACCORDANCE WITH
 SECTION 1003.3.5 OR 1003.3.7 FBC P.
 B) INDICATE THE SIZE AND TYPE OF EXISTING GREASE
 INTERCEPTOR- GRAVITY OR HYDROMECHANICAL? (1003.3.5 &
 1003.3.7)
 C) THE HAND SINKS AND FLOOR DRAIN IN THE BEER COOLER
 SHALL NOT DRAIN INTO THE GREASE WASTE LINE- SECTION
 1003.3.1 FBC P. HANDSINKS ARE NOT SIGNIFICANT GREASE
 CONTRIBUTORS, AND THE FLOOR DRAIN IN THE COOLER SHOULD
 ONLY BE DRAINING CLEAR WATER WASTE.
  
 3) P1 & P2: THE HUB DRAIN FOR THE DISHWASHER SHOWN IN
 THE ISO IS NOT SHOWN IN THE PLUMBING FLOOR PLAN--
 SECTION 107.2.1 WPB. PLEASE LABEL THE HUB DRAINS
 CORRECTLY ON THE FLOOR PLAN- THEY ARE NOT FLOOR DRAINS.
  
 3) P1 & P2: THE GREASE WASTE DRAIN LINE REQUIRES NOT
 LESS THAN ONE VENT PIPE THAT EXTENDS TO THE OUTDOORS-
 SECTIONS 904.1 & 918.7 FBC P.
  
 4) P1 & P2: THE FLOOR DRAINS ARE NOT PROPERLY VENTED.
 IT APPEARS A COMBINATION WASTE AND VENT SYSTEM IS BEING
 CREATED, HOWEVER THOSE SYSTEMS ARE NOT ALLOWED FOR
 GREASE WASTE DRAINS- SECTION 915.1 FBC P. PLEASE LOCATE
 VENTS IN THE LINE THAT DO NOT EXCEED THE 12 FT. MAXIMUM
 DISTANCE FROM THE FLOOR DRAIN TRAPS- TABLE 909.1 FBC P.
 PLEASE NOTE THE AAV'S CAN ONLY BE USED AS INDIVIDUAL,
 BRANCH, OR CIRCUIT VENTS- SECTION 918.3 FBC P.
  
 5) P1 & P2: PLEASE PROVIDE AN EQUIPMENT SCHEDULE FOR
 THE NEW TANKLESS WATER HEATER SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTION 624.1 FBC FG ( SEE SEPARATE
 FUEL GAS REVIEW COMMENTS).
  
 6) P1 & P2: PROVIDE AN ENLARGED PIPING DRAWING FOR THE
 WATER HEATERS SHOWING LOCATIONS OF THERMAL EXPANSION
 TANKS, RECIRCULATION PUMPS, SHUTOFF VALVES, CHECK
 VALVES, ETC.- SECTIONS 607.2.1.2, 607.3 FBC P.
  
 7) P1 & P2: IT APPEARS THE LENGTHS OF THE HOT WATER
 SUPPLY PIPES TO THE LAVATORIES FROM THE WATER HEATER IS
 EXCEEDING THE MAXIMUM ALLOWABLE LENGTH AS INDICATED IN
 TABLE C404.5.1 FBC EC. EITHER POINT OF USE WATER
 HEATERS AT THE LAVATORIES OR A RECIRCULATION PUMP FOR
 THE HOT WATER SYSTEM SHALL BE INSTALLED.
  
 8) P1 & P2: WHERE HOT WATER IS SUPPLIED TO A LAVATORY,
 THE WATER SHALL BE TEMPERED IN ACCORDANCE WITH SECTIONS
 419.5 & 607.1.2 FBC P. PLEASE PROVIDE A MIXING VALVE
 THAT CONFORMS TO ASSE 1070. PROVIDE A PIPING DETAIL ON
 THE PLAN FOR INSTALLATION.
  
 9) P1 & P2: PROVIDE AN INDIRECT WASTE DETAIL FOR THE
 3-COMPARTMENT SINKS- SECTION 802.1.1 FBC P.
  
 10) P1 & P2: PLEASE PROVIDE A COMPLETE PLUMBING FIXTURE
 SCHEDULE THAT INCLUDES THE DISHWASHER, HUB DRAINS,
 FLOOR DRAINS, AND THE REPLACED RESTROOM FIXTURES- (IF
 APPLICABLE TO THE SCOPE)- SECTION 107.2.1 WPB.
  
 11) P1: THE PLAN SHOWS ICE MAKERS, ICE BINS, COOLERS,
 FROSTER, ETC. WITH NO DRAINS DIRECTLY BELOW THEM.
 PLEASE CLARIFY HOW DRAINAGE FROM THESE FIXTURES WILL BE
 CONVEYED INTO THE SANITARY SYSTEM. PLEASE NOTE THAT
 CLEAR WATER WASTE SHALL NOT DRAIN INTO THE GREASE WASTE
 LINE- SECTION 1003.3.1 FBC P.
  
 12) P1 & P2: SHOW AN EXISTING OR NEW CLEANOUT AT THE
 JUNCTION OF THE GREASE WASTE LINE AND SEWER JUNCTION-
 SECTION 708.1.3 FBC P.
  
 13) P2: PROVIDE A WATER HAMMER ARRESTOR AND BACKFLOW
 PREVENTER FOR THE WATER SUPPLY LINE TO THE ICE MAKER.
 PLEASE NOTE THAT THIS COMMENT IS APPLICABLE TO ANY
 OTHER REQUIRED WATER SUPPLY LINES TO APPLIANCES AND
 EQUIPMENT- SECTIONS 604.9 & 608.3 FBC P.
  
 14) P1 & P2: PLEASE PROVIDE CODE DATA AND A SYMBOL
 LEGEND ON THE PLAN- SECTION 107.2.1 WPB.
  
 15) P1 & P2: PROVIDE HOT WATER PIPE INSULATION
 SPECIFICATIONS- TABLE C403.2.10 FBC EC.
  
 16) P1 & P2: INDICATE THE TYPE OF FINISH WALL AND FLOOR
 MATERIALS TO BE INSTALLED IN THE RESTROOMS AND AT THE
 MOP SINK- SEE SECTIONS 310.3 FBC P AND 1210.2. FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-01-05 Cont ID  
Sent By ccole Date 2022-01-05 Time 14:33 Rev Time 0.00
Received By ccole Date 2022-01-05 Time 08:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-11-29 Cont ID  
Sent By rmcphers Date 2021-11-29 Time 08:11 Rev Time 0.00
Received By rmcphers Date 2021-11-29 Time 08:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-10-12 Cont ID  
Sent By rmcphers Date 2021-10-12 Time 13:38 Rev Time 0.00
Received By rmcphers Date 2021-10-12 Time 13:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-09-08 Cont ID  
Sent By ccole Date 2021-09-08 Time 11:38 Rev Time 0.00
Received By ccole Date 2021-09-08 Time 08:09 Sent To  
Notes
2021-09-08 11:40:52SIGNATURE REVIEW
 PERMIT- 21041585
 9/8/21
  
 1) THE PLANS AND COMBUSTION AIR CALCULATIONS ARE NOT
 DIGITALLY SIGNED AND SEALED. ELECTRONICALLY TRANSMITTED
 PLANS AND DOCUMENTS PREPARED BY A FL. REGISTERED
 ENGINEER SHALL BEAR THE ENGINEER?S DIGITAL SIGNATURE
 AND SEAL OF- FL. STATUTE 471.025 AND SECTION
 61G15-23.005 FAC.
  
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 2) AS AN ALTERNATE TO PROVIDING ELECTRONICALLY
 TRANSMITTED DIGITALLY SIGNED AND SEALED CALCULATIONS,
 ORIGINAL SIGNED AND SEALED PAPER PLANS AND CALCULATIONS
 CAN BE DROPPED OFF OR MAILED TO THE WPB BUILDING DEPT.
 WITH A PLAN REVIEW REQUEST FORM.
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-06-29 Cont ID  
Sent By rmcphers Date 2021-06-29 Time 09:23 Rev Time 0.00
Received By rmcphers Date 2021-06-29 Time 09:22 Sent To  
Notes
***NONE***