| 2021-05-21 13:06:49 | 05/21/21 2ND GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SECOND REQUEST; THE ADDRESS FOR THIS STRUCTURE HAS |
| | NO CHANGE OF OCCUPANCY IN THE CITY RECORDS AND NO |
| | BUILDING PERMIT ON FILE. ANY OWNER OR AGENT AUTHORIZED |
| | IN ACCORDANCE WITH FLORIDA STATUTE 489 WHO INTENDS TO |
| | CONSTRUCT, ENLARGE, ALTER, REPAIR, MOVE, DEMOLISH, OR |
| | CHANGE THE OCCUPANCY OF A BUILDING OR STRUCTURE, OR TO |
| | ERECT, INSTALL, ENLARGE, ALTER, REPAIR, REMOVE, CONVERT |
| | OR REPLACE ANY IMPACT-RESISTANT COVERINGS, ELECTRICAL, |
| | GAS, MECHANICAL, PLUMBING OR FIRE PROTECTION SYSTEM, OR |
| | ACCESSIBLE OR FLOOD-RESISTANT SITE ELEMENT, THE |
| | INSTALLATION OF WHICH IS REGULATED BY THIS CODE, OR TO |
| | CAUSE ANY SUCH WORK TO BE DONE, SHALL FIRST MAKE |
| | APPLICATION TO THE BUILDING OFFICIAL AND OBTAIN THE |
| | REQUIRED PERMIT PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 105.1. |
| | |
| | 2. SECOND REQUEST; PLEASE PROVIDE A DESCRIPTIVE SCOPE |
| | OF WORK THAT WILL BE PERFORMED ON THE PLANS, LIST |
| | FIXTURE APPURTENANCES BEING INSTALLED, AND THE EXTENT |
| | OF WORK YOU ARE DOING PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 101.2 SCOPE. |
| | |
| | 3. SECOND REQUEST; THE CLAIMED VALUE APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION. PLEASE PROVIDE A |
| | BONA FIDE SIGNED CONTRACT PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE |
| | OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION |
| | OF THE BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, |
| | GAS, MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED UNLESS THE APPLICANT CAN SHOW DETAILED, QUANTITY |
| | ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS (EXCLUDING |
| | LAND VALUE) TO MEET THE APPROVAL OF THE BUILDING |
| | OFFICIAL. FOR PERMITTING PURPOSES, THE VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE |
| | TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, |
| | INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND |
| | DESIGN FEES, MARKETING COSTS, OVERHEAD, AND PROFIT, |
| | EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY |
| | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. THE BUILDING OFFICIAL SHALL SET THE FINAL |
| | BUILDING PERMIT VALUATION. |
| | |
| | 4. PLEASE SHOW EMERGENCY HOOD SHUT DOWN SHUTOFF VALVE |
| | AND IT SHALL BE BELOW THE CEILING. THE MANUAL SHUTOFF |
| | VALVE SHALL BE UPSTREAM. UNION TO BE DOWNSTREAM OF |
| | MANUAL VALVE. SECS. 10.4, 10.5 OF NFPA 96-08. AT LEAST |
| | ONE MANUAL ACTUATION DEVICE SHALL BE LOCATED A MINIMUM |
| | OF 3 M (10 FT) AND A MAXIMUM OF 6 M (20 FT) FROM THE |
| | PROTECTED HOOD EXHAUST SYSTEM(S) WITHIN A PATH OF |
| | EGRESS OR AT AN ALTERNATIVE LOCATION ACCEPTABLE TO THE |
| | AHJ. |
| | |
| | 5. SECOND REQUEST; PLEASE SUBMIT AN ISOMETRIC DRAWING |
| | THAT CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF |
| | PIPE PER 2020 FBC FG SECS. 402.4.1, 402.4.2. |
| | |
| | 6. SECOND REQUEST; SHOW THE TYPE OF PIPE MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING EHD |
| | NUMBER OF THE CORRUGATED STAINLESS-STEEL TUBING (IF |
| | APPLICABLE) FOR EACH PIPE SIZE PER THE WPB AMENDMENTS |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 7. SECOND REQUEST; TYPE OF GAS (LP OR NATURAL) PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 8. SECOND REQUEST; INDICATE THE DELIVERY PRESSURE (PSI) |
| | OF THE SYSTEM ON THE PLAN PER THE 2020 FBC FG SEC. |
| | 402.2. |
| | |
| | 9. SECOND REQUEST; SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2020 FBC FG SEC.305.1. |
| | |
| | 10. SECOND REQUEST; GAS APPLIANCES SHALL BE LISTED AND |
| | LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION PER THE 2020 FBC FG SECS. 402.2 AND 301.3. |
| | |
| | 11. SECOND REQUEST; LIST THE BTU LOAD OF EACH APPLIANCE |
| | AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2020 |
| | FBC FG SECS. 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1) |
| | THROUGH 402.4 (37). |
| | |
| | 12. SECOND REQUEST; SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY (GAS METER / MP REGULATOR / LP TANK) TO THE |
| | MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | THE 2020 FBC FG SEC. 402.4.1. |
| | |
| | 13. SECOND REQUEST; PLEASE SUBMIT THE SIZING TABLE USED |
| | IN THE DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON |
| | BOTH SETS OF PLANS LISTING THE SIZING TABLES FROM GAS |
| | CODES OR ANOTHER STANDARD THAT WERE USED IN THE DESIGN |
| | OF THIS SYSTEM PER THE 2020 FBC FG SEC. 402.3. |
| | |
| | 14. PLEASE SUBMIT CALCULATIONS FOR COMBUSTION AIR PER |
| | THE 2020 FBC FG SEC. 304.1. WHERE IS COMBUSTION AIR |
| | PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION |
| | SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED |
| | COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED |
| | VENTILATION AIR PER THE 2020 FBC FG SEC. 304.9.3. |
| | COMBINED COMBUSTION AIR AND VENTILATION AIR SYSTEM. |
| | |
| | 15. SECOND REQUEST; PLEASE SUBMIT THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC FG |
| | SEC. 410.1. |
| | |
| | 16. SECOND REQUEST; PLEASE SHOW ALL UNIONS IN FRONT OF |
| | REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC FG SEC |
| | 410.2. |
| | |
| | 17. SECOND REQUEST; SHOW DRIP LEG ON EQUIPMENT |
| | INSTALLED, EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD |
| | GRILLS PER THE 2020 FBC FG 408.2. |
| | |
| | 18. SECOND REQUEST; PLEASE PROVIDE THE SIGNATURE OF ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA THAT SHALL BEAR THE PRINTED NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |