Plan Review Details - Permit 21041392
Plan Review Stops For Permit 21041392
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-07-02 Cont ID  
Sent By rmcphers Date 2021-07-02 Time 11:08 Rev Time 0.00
Received By rmcphers Date 2021-07-02 Time 11:08 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-06-24 Cont ID  
Sent By rmcphers Date 2021-06-24 Time 08:31 Rev Time 0.00
Received By rmcphers Date 2021-06-24 Time 08:31 Sent To  
Notes
2021-06-24 08:33:14PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-05-20 Cont ID  
Sent By rmcphers Date 2021-05-20 Time 15:32 Rev Time 0.00
Received By rmcphers Date 2021-05-20 Time 15:32 Sent To  
Notes
2021-05-20 15:33:35PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-07-22 Cont ID  
Sent By rmcphers Date 2021-07-22 Time 12:58 Rev Time 0.00
Received By rmcphers Date 2021-07-22 Time 12:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-06-24 Cont ID  
Sent By rmcphers Date 2021-06-24 Time 08:29 Rev Time 0.00
Received By rmcphers Date 2021-06-24 Time 08:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-05-20 Cont ID  
Sent By rmcphers Date 2021-05-20 Time 15:37 Rev Time 0.00
Received By rmcphers Date 2021-05-20 Time 12:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-06-08 Cont ID  
Sent By equinone Date 2021-05-11 Time 14:15 Rev Time 0.00
Received By equinone Date 2021-05-11 Time 07:23 Sent To  
Notes
2021-05-11 14:15:57CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: APPROVED. SEE NEW COMMENTS BELOW
  
 CUSTOMER CALLED AND CLARIFIED. STATUS IS NOW APPROVED
 (06/8/2021) EQ
  
  
 ENRIQUE QUINONEZ PE
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2021-05-13 Cont ID  
Sent By lcrespo Date 2021-05-13 Time 13:34 Rev Time 0.00
Received By lcrespo Date 2021-05-13 Time 13:34 Sent To  
Notes
2021-05-13 13:35:35NOT REQUIRED AS THE GREASE INTERCEPTOR IS INSIDE, LAC.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-07-14 Cont ID  
Sent By cwalker Date 2021-07-14 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-06-15 Cont ID  
Sent By pleduc Date 2021-06-15 Time   Rev Time 0.00
Received By pleduc Date 2021-06-15 Time 11:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-04-30 Cont ID  
Sent By cwalker Date 2021-04-30 Time   Rev Time 0.00
Received By cwalker Date 2021-04-30 Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-05-13 Cont ID  
Sent By lcrespo Date 2021-05-13 Time 16:37 Rev Time 0.00
Received By lcrespo Date 2021-05-13 Time 16:30 Sent To  
Notes
2021-05-13 16:31:0405/13/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-08-02 Cont ID  
Sent By pvalenti Date 2021-08-02 Time 09:15 Rev Time 0.00
Received By pvalenti Date 2021-07-30 Time 11:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-07-22 Cont ID  
Sent By rmcphers Date 2021-07-22 Time 12:59 Rev Time 0.00
Received By rmcphers Date 2021-07-12 Time 10:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-07-02 Cont ID  
Sent By rmcphers Date 2021-07-02 Time 11:08 Rev Time 0.00
Received By rmcphers Date 2021-07-01 Time 10:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-24 Cont ID  
Sent By lcrespo Date 2021-06-24 Time 16:22 Rev Time 0.00
Received By lcrespo Date 2021-06-14 Time 15:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-20 Cont ID  
Sent By rmcphers Date 2021-05-20 Time 15:40 Rev Time 0.00
Received By rmcphers Date 2021-04-28 Time 11:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-06-21 Cont ID  
Sent By medwards Date 2021-06-21 Time 15:05 Rev Time 0.00
Received By medwards Date 2021-06-21 Time 15:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-05-07 Cont ID  
Sent By medwards Date 2021-05-07 Time 10:57 Rev Time 0.00
Received By medwards Date 2021-05-07 Time 09:50 Sent To  
Notes
2021-05-07 10:57:441ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21041392
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW THAT THE RETURN AIR GRILLE FOR RTU-2 AND
 RTU-1 MEETS FBC M 601.5
 601.5 RETURN AIR OPENINGS. RETURN AIR OPENINGS FOR
 HEATING, VENTILATION AND AIR-CONDITIONING SYSTEMS SHALL
 COMPLY WITH ALL
 OF THE FOLLOWING:
  
 1. OPENINGS SHALL NOT BE LOCATED LESS THAN 10 FEET
 (3048 MM) MEASURED IN ANY DIRECTION FROM AN OPEN
 COMBUSTION CHAMBER OR DRAFT HOOD OF ANOTHER APPLIANCE
 LOCATED IN THE SAME ROOM OR SPACE.
  
 7. RETURN AIR SHALL NOT BE TAKEN FROM A CLOSET, TOILET
 ROOM, KITCHEN, GARAGE, BOILER ROOM, FURNACE ROOM OR
 UNCONDITIONED ATTIC.
  
 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE
 OF SPACE I.E. KITCHEN, DINING ROOM OR FAST FOOD. THE
 OUTDOOR AIR SUBMITTED SEEMS LOW. WE DO NOT USE THE
 ARCHITECTURAL OCCUPANCY NUMBERS WHEN WORKING THE
 CALCULATIONS. FBC M 403.3.1.1 & TABLE 403.3.1.1
  
 3) PLEASE PROVIDE A NOTE ON THE DRAWINGS INDICATING
 THAT THE REFRIGERATION EQUIPMENT MUST BE SUBMITTED
 SEPARATELY FOR A PERMIT AND REVIEW.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-06-24 Cont ID  
Sent By lcrespo Date 2021-06-24 Time 16:22 Rev Time 0.00
Received By lcrespo Date 2021-06-24 Time 15:55 Sent To  
Notes
2021-06-24 16:28:0806/24/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-05-13 Cont ID  
Sent By lcrespo Date 2021-05-13 Time 13:24 Rev Time 0.00
Received By lcrespo Date 2021-05-06 Time 13:46 Sent To  
Notes
2021-05-13 13:25:1605/13/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. ON SHEET A-0.0, UNDER SUBMITTAL NOTES ITEM #1, THE
 CODE REFERENCE USED REFERS TO THE 2017 6TH EDITION.
 PLEASE CORRECT THE CURRENT ADDITION PER THE WPB
 AMENDMENTS TO THE FBC SEC.102.3 APPLICATION OF
 REFERENCES.
  
 2. ON SHEET A-0.4, FOR FIGURE 604.2, THE WATER CLOSET
 LOCATION IS MISSING THE 16" PER THE 2020 ACCESSIBILITY
 CODE SECTION 604.2.
  
 3. ON SHEET A-2.3;
 A. THE TOILET FROM THE WALL HAS A 1'-6," AND PER THE
 2020 FBC ACC 604.2, IT IS ALLOWED TO BE 1'-4" PLEASE
 ADD ON BOTH TYPICAL ADA, KEYNOTE A, DETAIL ONE AND R.R.
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THE HORIZONTAL GRAB BARS NEED TO BE MEASURED TO THE
 CENTER OF THE BAR PER THE 2020 FBC ACC SEC. 604.5.1
 SIDE WALL AND 604.5.2 REAR WALL.
  
 C. PLEASE SHOW THE DIMENSIONS FOR THE WATER CLOSET,
 LAVATORY, AND TURNING RADIUS PER THE 2020 FBC ACC SEC.
 606.2. 2 CLEAR FLOOR SPACE.
  
 D. THE TOP OF THE TOILET SET IS MISSING MIN 15" PER THE
 2020 FBC ACC SEC. 604.4 SEATS.
  
 4. ON SHEET P-1.0, SAMPLING PORT NOT APPROVED, PLEASE
 PROVIDE A SHIER APPROVED SPECS AS A DEFERED SUBMITAL OR
 USE A 4" TWO-WAY CLEAN-OUT AS IT IS AN APPROVED
 PRODUCT. ADDITIONALLY, I WILL CROSS OUT SAMPLING POINT
 DETAIL AND VERBIAGE THAT PERTAIN TO ITS USE AND
 INSTALLATION PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. 5. ON SHEET P-2.0;
 A. THE THREE-COMPARTMENT SINK IS SHOWN CONNECTED INLINE
 TO ONE DRAIN. PLEASE INDICATE AS EACH INDIVIDUAL AS
 EACH WELL OF A MULTIPLE-COMPARTMENT SINK SHALL
 DISCHARGE INDEPENDENTLY TO A WASTE RECEPTOR PER THE
 2020 FBC SEC. P 802.1.1 FOOD HANDLING.
  
 B. THE RECIRCULATING PUMP HAS A PUMP. THE VALVE SHOULD
 BE ON EACH SIDE PER MOST MANUFACTURES' SPECIFICATIONS;
 PLEASE SHOW OR PROVIDE SPECS FOR THE UNIT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. ON THE ISOMERIC FOR THE RECIRCULATING SYSTEM, PLEASE
 FOLLOW TABLE C404.5.1 PIPING VOLUME AND MAXIMUM PIPING
 LENGTHS FOR COMPLIANCE.
  
 C. PLEASE PROVIDE A LEGEND FOR PLUMBING THAT SHOWS LINE
 TYPES, VALVE, PUMP, ETC., PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. PLEASE PROVIDE VERBIAGE THAT THE ICE MACHINE SHALL
 BE PROTECTED WITH A BACKFLOW DEVICE THAT CONFORMS WITH
 ASSE 1024 PER THE 2020 FBC P608.17.1.2.
  
 7. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2021-05-13 Cont ID  
Sent By lcrespo Date 2021-05-13 Time 13:36 Rev Time 0.00
Received By lcrespo Date 2021-05-13 Time 13:36 Sent To  
Notes
2021-05-13 13:37:55SAMPLING PORT NOT APPROVED, PLEASE PROVIDE A SHIER
 APPROVED SPECS AS A DEFERED SUBMITAL OR USE A 4"
 TWO-WAY CLEAN-OUT AS IT IS AN APPROVED PRODUCT.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-08-02 Cont ID  
Sent By pvalenti Date 2021-08-02 Time 09:15 Rev Time 0.00
Received By pvalenti Date 2021-08-02 Time 09:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-07-22 Cont ID  
Sent By rmcphers Date 2021-07-22 Time 12:54 Rev Time 0.00
Received By rmcphers Date 2021-07-22 Time 12:54 Sent To  
Notes
2021-07-22 12:58:50SIGNATURE REVIEW
 DRAWINGS LABLED - 005-A0.4 (ADA -2)--.PDF / 009-A2.2
 (EQ PLAN)--.PDF / 010-A2.3 (ENLARGED FLOOR PLAN)--.PDF
 IN PROJECTDOX DO NOT SHOW AS ELECTRONICALLY SIGNED IN
 ADOBE READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX
 NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE
 ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC PLAN
 REVIEW. - OR - IF YOUR ARCHITECT OR ENGINEER DOES NOT
 HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP
 OFF THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 TO THE FRONT DESK IN THE BUILDING DIVISION AT THE CITY
 HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-07-02 Cont ID  
Sent By rmcphers Date 2021-07-02 Time 11:07 Rev Time 0.00
Received By rmcphers Date 2021-07-02 Time 11:07 Sent To  
Notes
2021-07-02 11:08:24AS NOTED ON THE LAST REVIEW
 IT APPERAS THAT THE REVISED ARCHITECTURAL SHEETS HAVE A
 COPY OF THE ORIGINAL DIGITAL SIGNATURE. PLEASE SUBMIT
 THE ORIGINAL DIGITALLY SIGNED DOCUMENTS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-06-21 Cont ID  
Sent By medwards Date 2021-06-21 Time 15:13 Rev Time 0.00
Received By medwards Date 2021-06-21 Time 15:05 Sent To  
Notes
2021-06-21 15:15:09IT APPERAS THAT THE REVISED ARCHITECTURAL SHEETS HAVE A
 COPY OF THE ORIGINAL DIGITAL SIGNATURE. PLEASE SUBMIT
 THE ORIGINAL DIGITALLY SIGNED DOCUMENTS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-05-20 Cont ID  
Sent By rmcphers Date 2021-05-20 Time 15:38 Rev Time 0.00
Received By rmcphers Date 2021-05-20 Time 15:38 Sent To  
Notes
***NONE***