Plan Review Details - Permit 21041255
Plan Review Stops For Permit 21041255
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-05-06 Cont ID  
Sent By cpuell Date 2021-05-06 Time 12:33 Rev Time 0.00
Received By cpuell Date 2021-05-06 Time 12:33 Sent To  
Notes
2021-05-06 12:34:25SUITE READDRESSED AS 1020

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-05-03 Cont ID  
Sent By cpuell Date 2021-05-03 Time 17:42 Rev Time 0.00
Received By cpuell Date 2021-05-03 Time 17:42 Sent To  
Notes
2021-05-03 17:42:25PLEASE PROVIDE AN OVERALL FLOOR PLAN, SHOWING WHERE THE
 SUITE IS IN COMPARISON TO THE REST OF THE SUITES ON THE
 FLOOR.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2021-05-04 Cont ID  
Sent By rmcphers Date 2021-05-03 Time 11:01 Rev Time 0.00
Received By rmcphers Date 2021-05-03 Time 11:01 Sent To  
Notes
2021-05-03 11:02:58NOT REQUIRED FOR A CHANGE IN NEW CONSTRUCTION

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-05-03 Cont ID  
Sent By rmcphers Date 2021-05-03 Time 11:01 Rev Time 0.00
Received By rmcphers Date 2021-05-03 Time 09:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-04-25 Cont ID  
Sent By jleahy Date 2021-04-25 Time 07:33 Rev Time 0.00
Received By jleahy Date 2021-04-25 Time 15:01 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-05-13 Cont ID  
Sent By jleahy Date 2021-05-13 Time 17:24 Rev Time 0.00
Received By jleahy Date 2021-04-25 Time 15:25 Sent To  
Notes
2021-05-13 17:25:38VOICE AND DATA JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-04-27 Cont ID  
Sent By pleduc Date 2021-04-27 Time   Rev Time 0.00
Received By pleduc Date 2021-04-27 Time 09:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-06-01 Time   Rev Time 0.00
Received By aoliver Date 2021-05-28 Time 10:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-13 Cont ID  
Sent By jleahy Date 2021-05-13 Time 17:25 Rev Time 0.00
Received By jleahy Date 2021-04-23 Time 17:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-06-01 Cont ID  
Sent By medwards Date 2021-06-01 Time 06:29 Rev Time 0.00
Received By medwards Date 2021-06-01 Time 06:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-30 Cont ID  
Sent By medwards Date 2021-04-30 Time 10:37 Rev Time 0.00
Received By medwards Date 2021-04-30 Time 10:13 Sent To  
Notes
2021-04-30 11:02:191ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21041255
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M3.01: PLEASE ADD THE CFM?S OF SUPPLY AIR IN
 OFFICES 109, 110 AND 111 FBC 107.2.1
  
 2) SHEET M6.01 INDICATES THAT VAV-11.10 DESIGN AIR FLOW
 IS 250 CFM. SHEET M3.01 INDICATES IT WILL SUPPLY 870
 CFM, PLEASE ADJUST THIS VAV TO THE REQUIRED SUPPLY AIR.
 FBC 107.2.1
  
 3) SHEET M6.01 INDICATES THAT VAV-11.9 DESIGN AIR FLOW
 IS 970 CFM. SHEET M3.01 INDICATES IT WILL SUPPLY ONLY
 250 CFM, I BELIEVE VAV-11.9 AND VAV-11.10 ARE CROSSED.
 PLEASE CORRECT. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2021-04-30 10:38:03 
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-06-01 Cont ID  
Sent By ccole Date 2021-06-01 Time 10:13 Rev Time 0.00
Received By ccole Date 2021-06-01 Time 08:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-27 Cont ID  
Sent By ccole Date 2021-04-27 Time 11:07 Rev Time 0.00
Received By ccole Date 2021-04-27 Time 09:43 Sent To  
Notes
2021-04-27 11:07:461ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21041255
 4/27/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P9.01 HAS A FLOOR DRAIN/TRAP PRIMER DETAIL.
 PLEASE CLARIFY IF A FLOOR DRAIN WILL BE INSTALLED BELOW
 THE ICE MAKER TO CONVEY CONDENSATION OR ICE MELT
 DRAINAGE FROM THE UNIT TO AN APPROVED PLACE OF
 DISPOSAL- SECTIONS 314.2.1 AND 701.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-01 Cont ID  
Sent By medwards Date 2021-06-01 Time 06:29 Rev Time 0.00
Received By medwards Date 2021-06-01 Time 06:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-04-30 Cont ID  
Sent By medwards Date 2021-04-30 Time 11:14 Rev Time 0.00
Received By medwards Date 2021-04-30 Time 11:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2021-05-12 Cont ID  
Sent By aaponte Date 2021-05-12 Time 13:36 Rev Time 0.00
Received By aaponte Date 2021-05-12 Time 13:36 Sent To  
Notes
***NONE***