Plan Review Details - Permit 21041230
Plan Review Stops For Permit 21041230
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-06-22 Cont ID  
Sent By jgomez Date 2021-06-22 Time 18:15 Rev Time 0.00
Received By jgomez Date 2021-06-22 Time 17:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-06-21 Cont ID  
Sent By jgomez Date 2021-06-21 Time 15:30 Rev Time 0.00
Received By jgomez Date 2021-06-21 Time 13:47 Sent To  
Notes
2021-06-21 15:30:47WINDOWS/DOORS SUBMITTAL, THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 SUBMITTAL #21041230
  
 ORIGINAL COMMENT:
 1- WINDOW PRODUCT APPROVAL WAS CHANGED TO DOUBLE HUNG
 FLORIDA PRODUCT APPROVAL FL14477-R5. THIS PRODUCT
 APPROVAL DOESN'T INCLUDE A WINDOW SIZE SCHEDULE. PLANS
 SPECIFY SH25 EGRESS WINDOWS FOR THE SECOND FLOOR
 BEDROOMS.
 TYPICALLY, A SH25 SINGLE HUNG HAS A SIZE OF +/-37"
 WIDTH BY +/-63" HEIGHT. BASED ON THE KOLBE & KOLBE
 MILLWORK COMPANY WEBSITE IT LOOKS LIKE THIS SIZE OF
 WINDOW MAY NOT COMPLY WITH THE EGRESS REQUIREMENTS FOR
 THE SECOND FLOOR BEDROOMS.
 PROVIDE MANUFACTURER'S CUT SHEETS SHOWING THAT THE
 SPECIFIED WINDOW SIZE COMPLIES WITH THE EGRESS
 REQUIREMENTS. CLEARLY SHOW SIZE OF WINDOW AND ALL CLEAR
 OPENINGS: WIDTH, HEIGHT AND TOTAL CLEAR OPENING. IF
 SIZE OF WINDOW NEEDS TO BE REVISED, THEN REVISE PLANS
 ACCORDINGLY.
 SEC. R310.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 SOFIA FROM RJS BUILDERS SPECIFIED WINDOW "O" SIZE IS:
 37.5"W X 64 7/16"H.
 BASED ON THE KOLBE & KOLBE MILLWORK COMPANY WEBSITE
 THIS SIZE OF WINDOW DOESN'T COMPLY WITH THE EGRESS
 REQUIREMENTS FOR THE SECOND FLOOR BEDROOMS.
 THE CLEAR HEIGHT FOR THIS WINDOW IS 20-7/16" AND THE
 TOTAL CLEAR OPENING IS 4.82S.F. (SEE ATTACHED
 SCREENSHOT). NEED MINIMUM OF 24 CLEAR HEIGHT OPENING
 AND MINIMUM CLEAR OPENING OF 5.7S.F.
 ENGINEER OF RECORD NEEDS TO REVISE PLANS SPECIFYING
 SIZE OF WINDOW COMPLYING WITH ALL THE EGRESS
 REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL.
 NOTE: CLEARLY SPECIFY SIZE OF WINDOW (WIDTH AND HEIGHT)
 THAT MATCHES WINDOW MANUFACTURER?S PUBLISHED SIZES.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-14 Cont ID  
Sent By jgomez Date 2021-06-14 Time 10:49 Rev Time 0.00
Received By jgomez Date 2021-06-14 Time 10:49 Sent To  
Notes
2021-06-14 10:50:40WINDOWS/DOORS SUBMITTAL, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 SUBMITTAL #21041230
  
 ORIGINAL COMMENT:
 1- WINDOW PRODUCT APPROVAL WAS CHANGED TO DOUBLE HUNG
 FLORIDA PRODUCT APPROVAL FL14477-R5. THIS PRODUCT
 APPROVAL DOESN'T INCLUDE A WINDOW SIZE SCHEDULE. PLANS
 SPECIFY SH25 EGRESS WINDOWS FOR THE SECOND FLOOR
 BEDROOMS.
 TYPICALLY, A SH25 SINGLE HUNG HAS A SIZE OF +/-37"
 WIDTH BY +/-63" HEIGHT. BASED ON THE KOLBE & KOLBE
 MILLWORK COMPANY WEBSITE IT LOOKS LIKE THIS SIZE OF
 WINDOW MAY NOT COMPLY WITH THE EGRESS REQUIREMENTS FOR
 THE SECOND FLOOR BEDROOMS.
 PROVIDE MANUFACTURER'S CUT SHEETS SHOWING THAT THE
 SPECIFIED WINDOW SIZE COMPLIES WITH THE EGRESS
 REQUIREMENTS. CLEARLY SHOW SIZE OF WINDOW AND ALL CLEAR
 OPENINGS: WIDTH, HEIGHT AND TOTAL CLEAR OPENING. IF
 SIZE OF WINDOW NEEDS TO BE REVISED, THEN REVISE PLANS
 ACCORDINGLY.
 SEC. R310.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. INFORMATION NOT
 PROVIDED.
  
 2- OK.
  
 ORIGINAL COMMENT:
 3- NEED TO SUBMIT ALL THE PRODUCT APPROVALS REQUIRED
 FOR THIS HOUSE. ONLY THE ROOFING PRODUCT APPROVALS ARE
 ALREADY APPROVED. NOTE: PRODUCT APPROVALS WERE NOT
 APPROVED WHEN THE BUILDING PERMIT WAS ISSUED BECAUSE IT
 WAS AGREED WITH MRS. SOFIA SCIALLA THAT IN ORDER TO
 EXPEDITE THE BUILDING REVIEW APPROVAL ALL PRODUCT
 APPROVALS WERE GOING TO BE SUBMITTED LATER. THIS WAS
 BECAUSE THE PRODUCT APPROVAL SCHEDULE ON SHEET 3 OF 10
 DIDN'T MATCH PRODUCT APPROVALS SUBMITTED.
 SUBMIT PRODUCT APPROVAL FOR: ENTRY DOORS, OVERHEAD
 GARAGE DOORS, GARAGE EXTERIOR SIDE SWING DOORS.
  
 RESPONSE:
 3(A)-ENTRY DOOR: PROVIDE EITHER FLORIDA PRODUCT
 APPROVAL COVER PAGE THAT CORRESPONDS TO DRAWINGS
 SUBMITTED. IF DOOR DOESN'T HAVE A FLORIDA PRODUCT
 APPROVAL OR MIAMI-DADE NOA, THEN DOOR MANUFACTURER MAY
 SUBMIT COMPLETE ENGINEERING PACKAGE FOR REVIEW FOR
 LOCAL PRODUCT APPROVAL.
 NOTE: PLANS NEED TO HAVE THE ORIGINAL SEAL AND
 SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-23.001 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 3(B) MISSING PRODUCT APPROVAL FOR GARAGE EXTERIOR SIDE
 SWING DOOR.
  
 ORIGINAL COMMENT:
 4- CLARIFY WHY SUBMITTING MULLION PRODUCT APPROVAL.
 ACCORDING TO PLANS THERE ARE NOT MULLIONS.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 NOT ADDRESSED. PLANS DON'T SHOW MULLIONS. IF THERE ARE
 ANY MULLIONS, THEN REVISE PLANS ACCORDINGLY AND SPECIFY
 MULLION SIZE AND FASTENING. REVISION FEES APPLY.
 SEC. R301 FBC-RESIDENTIAL.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-07 Cont ID  
Sent By JGOMEZ Date 2021-05-07 Time 13:52 Rev Time 0.00
Received By jgomez Date 2021-05-07 Time 10:01 Sent To  
Notes
2021-05-07 13:53:08WINDOWS/DOORS SUBMITTAL BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 SUBMITTAL #21041230
  
 1- WINDOW PRODUCT APPROVAL WAS CHANGED TO DOUBLE HUNG
 FLORIDA PRODUCT APPROVAL FL14477-R5. THIS PRODUCT
 APPROVAL DOESN'T INCLUDE A WINDOW SIZE SCHEDULE. PLANS
 SPECIFY SH25 EGRESS WINDOWS FOR THE SECOND FLOOR
 BEDROOMS.
 TYPICALLY, A SH25 SINGLE HUNG HAS A SIZE OF +/-37"
 WIDTH BY +/-63" HEIGHT. BASED ON THE KOLBE & KOLBE
 MILLWORK COMPANY WEBSITE IT LOOKS LIKE THIS SIZE OF
 WINDOW MAY NOT COMPLY WITH THE EGRESS REQUIREMENTS FOR
 THE SECOND FLOOR BEDROOMS.
 PROVIDE MANUFACTURER'S CUT SHEETS SHOWING THAT THE
 SPECIFIED WINDOW SIZE COMPLIES WITH THE EGRESS
 REQUIREMENTS. CLEARLY SHOW SIZE OF WINDOW AND ALL CLEAR
 OPENINGS: WIDTH, HEIGHT AND TOTAL CLEAR OPENING. IF
 SIZE OF WINDOW NEEDS TO BE REVISED, THEN REVISE PLANS
 ACCORDINGLY.
 SEC. R310.2.1 FBC-RESIDENTIAL.
  
 2- DOUBLE HUNG WINDOW FLORIDA PRODUCT APPROVAL NUMBER
 LISTED IN THE ENGINEER'S PRODUCT APPROVAL LETTER
 DOESN'T MATCH ONE SUBMITTED. REVISE AS REQUIRED TO
 MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- NEED TO SUBMIT ALL THE PRODUCT APPROVALS REQUIRED
 FOR THIS HOUSE. ONLY THE ROOFING PRODUCT APPROVALS ARE
 ALREADY APPROVED. NOTE: PRODUCT APPROVALS WERE NOT
 APPROVED WHEN THE BUILDING PERMIT WAS ISSUED BECAUSE IT
 WAS AGREED WITH MRS. SOFIA SCIALLA THAT IN ORDER TO
 EXPEDITE THE BUILDING REVIEW APPROVAL ALL PRODUCT
 APPROVALS WERE GOING TO BE SUBMITTED LATER. THIS WAS
 BECAUSE THE PRODUCT APPROVAL SCHEDULE ON SHEET 3 OF 10
 DIDN'T MATCH PRODUCT APPROVALS SUBMITTED.
 SUBMIT PRODUCT APPROVAL FOR: ENTRY DOORS, OVERHEAD
 GARAGE DOORS, GARAGE EXTERIOR SIDE DOORS.
  
 4- CLARIFY WHY SUBMITTING MULLION PRODUCT APPROVAL.
 ACCORDING TO PLANS THERE ARE NOT MULLIONS.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: TO EXPEDITE THE REVIEW PROCESS AND AVOID
 CONFLICTS/DELAYS PLEASE PROVIDE A SINGLE PRODUCT
 APPROVAL REVIEW LETTER LISTING ALL THE PRODUCT
 APPROVALS.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-06-22 Cont ID  
Sent By jgomez Date 2021-06-22 Time 18:16 Rev Time 0.00
Received By jgomez Date 2021-06-22 Time 17:49 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-21 Cont ID  
Sent By jgomez Date 2021-06-21 Time 15:31 Rev Time 0.00
Received By jgomez Date 2021-06-21 Time 15:31 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-14 Cont ID  
Sent By jgomez Date 2021-06-14 Time 10:55 Rev Time 0.00
Received By jgomez Date 2021-06-04 Time 13:20 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-07 Cont ID  
Sent By jgomez Date 2021-05-07 Time 13:53 Rev Time 0.00
Received By jgomez Date 2021-04-26 Time 07:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-14 Cont ID  
Sent By jgomez Date 2021-06-14 Time 10:51 Rev Time 0.00
Received By jgomez Date 2021-06-14 Time 10:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-05-07 Cont ID  
Sent By jgomez Date 2021-05-07 Time 14:14 Rev Time 0.00
Received By jgomez Date 2021-05-07 Time 14:14 Sent To  
Notes
***NONE***