Plan Review Details - Permit 21041212
Plan Review Stops For Permit 21041212
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-06-13 Cont ID  
Sent By jwitmer Date 2021-06-13 Time 15:43 Rev Time 0.00
Received By jwitmer Date 2021-06-13 Time 15:15 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-05-05 Cont ID  
Sent By jwitmer Date 2021-05-05 Time 11:06 Rev Time 0.00
Received By jwitmer Date 2021-05-05 Time 10:59 Sent To  
Notes
2021-05-05 11:05:51COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2021-06-13 Time 15:45 Rev Time 0.00
Received By jwitmer Date 2021-06-13 Time 15:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-05 Cont ID  
Sent By jwitmer Date 2021-05-05 Time 11:58 Rev Time 0.00
Received By jwitmer Date 2021-05-05 Time 10:59 Sent To  
Notes
2021-05-05 11:58:02WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:21041212
 ADD: 701 S. ROSEMARY AVE. # 101
 CONT: MARAND BUILDERS, INC.
 TEL: 904-247-3211
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 05TH/ 2021
 ACTION: DENIED
 1) THE SUBMITTED NOTICE OF COMMENCEMENT NEEDS TO BE
 RECORDED AT THE COUNTY COURTHOUSE BEFORE THE 1ST
 INSPECTION WILL OCCUR. 2020 FLORIDA STATUTE 713.
  
 2) THE DEMOLITION PLAN SHOWS A BOH CORRIDOR. CITY PLACE
 COMPLEX OF BUILDINGS THE SO CALLED BACK OF HOUSE
 CORRIDOR IS A EXIT PASSAGE WAY THE 2ND REQUIRED EXIT
 FROM THE TENANT SPACES. SEE IN THE 2020 FBC-B SECTION
 402.8.6.1 AND 402.8.7. IS THIS BACK OF HOUSE CORRIDOR
 BEING USED AS AN EXIT FROM OTHER TENANT SPACES.
  
 3) SHEET A-4-00 IN THE ELEVATIONS THE PLAN SHOWS THE
 GRAB BARS BEING MEASURED FROM THE FINISH FLOOR TO THE
 CENTER-LINE OF THE GRAB BAR. 2020 FBC-ACCESSIBILITY
 CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT
 CENTERLINE.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-06-17 Cont ID  
Sent By jleahy Date 2021-06-17 Time 12:10 Rev Time 0.00
Received By jleahy Date 2021-06-17 Time 11:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-05-14 Cont ID  
Sent By jleahy Date 2021-05-14 Time 14:57 Rev Time 0.00
Received By jleahy Date 2021-05-14 Time 14:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-06-11 Cont ID  
Sent By pleduc Date 2021-06-11 Time   Rev Time 0.00
Received By pleduc Date 2021-06-11 Time 08:32 Sent To  
Notes
2021-06-11 08:38:10FIRE PROVISO:
  
 ALL FIRE SPRINKLER WORK, INCLUDING DEMO, SHALL BE
 DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-05-05 Cont ID  
Sent By pleduc Date 2021-05-05 Time   Rev Time 0.00
Received By pleduc Date 2021-05-05 Time 10:38 Sent To  
Notes
2021-05-05 10:46:33FIRE PROVISO:
  
 THE FIRE SPRINKLER HEAD LOCATIONS IN AND AROUND THE
 PROPOSED WALL CHANGES REQUIRES A REVIEW BY A FIRE
 SPRINKLER CONTRACTOR FOR CODE COMPLIANT COVERAGE.
  
 ANY WORK ON THE FIRE SPRINKLER SYSTEM, NCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS BY A FIRE ALARM CONTRACTOR
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-29 Cont ID  
Sent By cthroop Date 2021-06-29 Time 16:15 Rev Time 0.00
Received By cthroop Date 2021-06-29 Time 08:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-22 Cont ID  
Sent By lmarchan Date 2021-06-22 Time 14:30 Rev Time 0.00
Received By lmarchan Date 2021-06-10 Time 14:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-26 Cont ID  
Sent By lmarchan Date 2021-05-26 Time 17:38 Rev Time 0.00
Received By lmarchan Date 2021-04-29 Time 09:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-06-16 Cont ID  
Sent By medwards Date 2021-06-16 Time 17:17 Rev Time 0.00
Received By medwards Date 2021-06-16 Time 17:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-05-12 Cont ID  
Sent By medwards Date 2021-05-12 Time 10:35 Rev Time 0.00
Received By medwards Date 2021-05-12 Time 10:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-06-15 Cont ID  
Sent By jesmith Date 2021-06-15 Time 14:47 Rev Time 0.00
Received By jesmith Date 2021-06-15 Time 14:46 Sent To  
Notes
2021-06-15 14:47:15PLUMBING APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 21041212 701 S ROSEMARY AVE # 101
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-05-11 Cont ID  
Sent By jesmith Date 2021-05-11 Time 11:53 Rev Time 0.00
Received By jesmith Date 2021-05-06 Time 16:20 Sent To  
Notes
2021-05-11 11:48:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.RE:A-400, A-001.02 AND A-001.03
 PER WPB FBC 107.2.1, COORDINATE AND RECONCILE A-400
 WITH A-001.02 AND A-001.03. PROVIDE A NOTE ON A-400 TO
 REFERENCE A-001.02 AND A-001.03 FOR ADA CLARIFICATIONS.
 A. A-001.02: THE WATER CLOSET SHALL BE POSITIONED WITH
 A WALL OR PARTITION TO THE REAR AND TO ONE SIDE. THE
 CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION PER FBC ACC 604.2. PER WPB FBC 107.2.1, NOTE
 MINIMUM AND MAXIMUM.
 B. A-001.02: THE REAR WALL GRAB BAR SHALL BE 36 INCHES
 LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF THE
 WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2.
 THIS IS THE REQUIREMENT. THE GRAB BAR SHALL BE 36
 INCHES MINIMUM. SHOW THE 12 INCHES MINIMUM ON ONE SIDE
 AND 24 INCHES MINIMUM ON THE OTHER SIDE. ADDITIONALLY,
 AS THE CENTER OF THE WATER CLOSET CAN FLUCTUATE 16
 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL
 THE SPACE BETWEEN THE SIDE WALL AND THE GRAB BAR SHALL
 BE 6 INCHES MAXIMUM, NOT 6 INCHES.
 C. A-400, DETAIL 1: THE SPACE BETWEEN THE SIDE WALL AND
 THE REAR GRAB BAR SHALL BE 6 INCHES MAXIMUM, NOT 6-1/2
 INCHES.
 D. A-400 AND A-001.01: PER FBC ACC 609.4, GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP (NOT THE CENTER) OF THE GRIPPING
 SURFACE
 E. A-400: PER FBC 606.5 EXPOSED PIPES AND SURFACES.
 WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT. THIS IS ADDRESSED ON A-001.03 BUT
 NEEDS TO BE CLARIFIED ON A-400. AS A-400 APPEARS TO BE
 THE FINISH SCHEDULE, THE ARCHITECT MAY WANT TO PROVIDE
 A PROTECTIVE PANEL.
 F. A-400: MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE "REFLECTING SURFACE" 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 603.3.
  
 2.PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL.
 SHOW THE WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF
 THE CONCRETE TO BE REPLACED, AND THE PSI OF THE
 CONCRETE. SHOW THE SIZE AND LENGTH OF THE DOWELS, THE
 MINIMUM EMBEDMENT DEPTH INTO THE EXISTING SLAB, THE
 ANCHORING MATERIAL FOR THE DOWELS AND THE SPACING OF
 THE DOWELS ON CENTER. THE REPAIR SHALL ALSO INCLUDE
 TERMITE TREATMENT OF THE SOIL AND THE REQUIRED VAPOR
 BARRIER OVER WELL-COMPACTED SOIL. A COPY OF THE TERMITE
 CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION.
  
 3.THERE IS NOT A LIFE SAFETY PLAN. PER WPB FBC 107.2.1,
 PROVIDE AND INDICATE SMOKE/FIRE RATED WALLS. IF
 PLUMBING PIPING PASSES THROUGH ANY RATED WALLS, THEN
 PROVIDE DETAILS/ASSEMBLIES FOR SAID PENETRATIONS
 COMPLYING WITH THE REQUIREMENTS OF FBC CHAPTER 7.
  
 4.PLAN SHEET M-000, PLUMBING SECTION 15400, B. DOMESTIC
 WATER, (2) PIPE MATERIAL; PER WPB FBC 107.2.1, REPLACE
 THE WORDS "FITTINGS, JOINTED WITH TIN-ANTIMONY (95/5)
 SOLDER" WITH THE WORDS "FITTINGS. PER FBC PL 605.12.3,
 A FLUX CONFORMING TO ASTM B813 SHALL BE APPLIED. THE
 JOINT SHALL BE SOLDERED WITH A SOLDER CONFORMING TO
 ASTM B32. THE JOINING OF WATER SUPPLY PIPING SHALL BE
 MADE WITH LEAD-FREE SOLDER AND FLUXES. ALL COMPONENTS
 IN THE SYSTEM SHALL BE LEAD FREE. LEAD FREE SHALL MEAN
 A CHEMICAL COMPOSITION EQUAL TO OR LESS THAN
 0.2-PERCENT LEAD."
  
 5.PER WPB FBC 107.2.1, PROVIDE DETAIL FOR TP-1 MOUNTED
 IN THE WALL WITH ACCESS PANEL (PROVIDE SPEC/DESCRIPTION
 FOR PANEL); INCLUDE PIPING AND VALVE(S).
  
 6.PER FBC PL 606.1(5) PROVIDE FULL OPEN VALVES ON THE
 TOP OF EVERY WATER DOWN-FEED PIPE IN OCCUPANCIES OTHER
 THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
 7.TO PROVIDE SUFFICIENT HOT WATER FLOW TO THE
 FIXTURE(S) AS REQUIRED BY FBC PL 604.1 AND 604.3,
 PROVIDE A BALANCING VALVE WITH CHECK VALVE IN THE NEW
 HOT WATER RETURN LINE. PER WPB FBC 107.2.1, PROVIDE A
 DETAIL, LOCATION, AND SPECIFICATION FOR BALANCING VALVE
 AND CHECK VALVE WHERE CONNECTING HOT WATER RETURN TO
 THE EXISTING RECIRCULATING SYSTEM. PROVIDE ACCESS PANEL
 IF LOCATED IN A HARD CEILING.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21041212 701 S ROSEMARY AVE # 101
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-29 Cont ID  
Sent By cthroop Date 2021-06-29 Time 16:15 Rev Time 0.00
Received By cthroop Date 2021-06-29 Time 16:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-06-16 Cont ID  
Sent By medwards Date 2021-06-16 Time 17:18 Rev Time 0.00
Received By medwards Date 2021-06-16 Time 17:18 Sent To  
Notes
2021-06-16 17:20:10PLANS WERE SUBMITTED DIGITALLY BUT THE PLANSONLY HAVE A
 COPY OF A WET SEAL FROM THE ENGINEER. PLEASE PROVIDE
 DRAWINGS WITH DIGITAL SIGNATURES FROM THE DESIGNER ON
 EACH SHEET.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-05-12 Cont ID  
Sent By medwards Date 2021-05-12 Time 10:35 Rev Time 0.00
Received By medwards Date 2021-05-12 Time 10:35 Sent To  
Notes
2021-05-12 10:36:26PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-06-22 Cont ID  
Sent By eschneid Date 2021-06-22 Time 11:56 Rev Time 0.25
Received By eschneid Date 2021-06-22 Time 11:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-05-26 Cont ID  
Sent By eschneid Date 2021-05-26 Time 16:51 Rev Time 0.25
Received By eschneid Date 2021-05-26 Time 16:43 Sent To  
Notes
***NONE***