Plan Review Details - Permit 21041113
| Plan Review Stops For Permit 21041113 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-05-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-05-19 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-05-19 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2021-05-19 15:54:18 | REVISION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) DRAWING GA-1 SHOWS THE DWELLING EGRESS THROUGH THE | | | GARAGE - CANNOT HAVE EGRESS THROUGH A GARAGE - FBC | | | R311.1 MEANS OF EGRESS. | | | DWELLINGS SHALL BE PROVIDED WITH A MEANS OF EGRESS IN | | | ACCORDANCE WITH THIS SECTION. THE MEANS OF EGRESS SHALL | | | PROVIDE A CONTINUOUS AND UNOBSTRUCTED PATH OF VERTICAL | | | AND HORIZONTAL EGRESS TRAVEL FROM ALL PORTIONS OF THE | | | DWELLING TO THE REQUIRED EGRESS DOOR WITHOUT REQUIRING | | | TRAVEL THROUGH A GARAGE. THE REQUIRED EGRESS DOOR SHALL | | | OPEN DIRECTLY INTO A PUBLIC WAY OR TO A YARD OR COURT | | | THAT OPENS TO A PUBLIC WAY. | | | | | | NO DRAWINGS ATTACHED TO THIS PERMIT NUMBER - SEE | | | 21041112 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-05-19 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-05-19 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-05-19 |
Time |
16:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-02-24 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-02-24 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-02-24 |
Time |
16:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-02-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-02-24 |
Time |
06:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-02-19 |
Time |
15:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-05-20 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-05-20 |
Time |
17:13 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-05-20 |
Time |
17:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-05-19 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-05-19 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-05-19 |
Time |
17:02 |
Sent To |
|
|
| Notes |
| 2021-05-19 17:04:23 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | MECHANICAL REVIEW DENIED: | | | | | | FBC B 107.2.1, PROVIDE MORE MECHANICAL INFORMATION FOR | | | THE A/C & ENERGY CALCS. ALSO NEED MORE DETAILS FOR THE | | | DRYER EXHAUST AND TERMINATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2021-05-19 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-05-19 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-05-19 |
Time |
15:46 |
Sent To |
|
|
| Notes |
| 2021-05-19 15:49:34 | 05/19/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2021-05-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-05-19 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-05-19 |
Time |
15:54 |
Sent To |
|
|
| Notes |
| 2021-05-19 15:57:34 | SEE REVIEWS UNDER 21041112. THIS REVIEW WILL BE PASSED | | | AFTER ALL REVIEWS HAVE PASSED FOR BOTH REVISIONS | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2021-05-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-05-19 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-05-19 |
Time |
15:54 |
Sent To |
|
|
| Notes |
| 2021-05-19 15:55:54 | NO DRAWINGS ATTACHED TO THIS PERMIT NUMBER - SEE | | | 21041112 |
|
|
|