Plan Review Details - Permit 21041108
Plan Review Stops For Permit 21041108
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2021-08-16 Cont ID  
Sent By cpuell Date 2021-08-16 Time 12:18 Rev Time 0.00
Received By cpuell Date 2021-08-16 Time 12:18 Sent To  
Notes
2021-08-16 12:20:24ADDRESS CHANGED FROM 434 21ST ST TO 430 21ST ST
 (DOWNSTAIRS UNIT) AND 432 21ST ST (UPSTAIRS UNIT)

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-08-09 Cont ID  
Sent By cpuell Date 2021-08-09 Time 12:25 Rev Time 0.00
Received By cpuell Date 2021-08-09 Time 12:25 Sent To  
Notes
2021-08-09 12:26:39ADDRESSING COMMENTS NOT ADDRESSED IN RESPONSE LETTER.
 PLEASE CONTACT [email protected] OR CALL 561-805-6659 AS
 THE UNITS NEED TO BE GIVEN ADDRESSES.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-05-06 Cont ID  
Sent By cpuell Date 2021-05-06 Time 11:02 Rev Time 0.00
Received By cpuell Date 2021-05-06 Time 11:02 Sent To  
Notes
2021-05-06 11:03:07PLEASE REACH OUT TO [email protected] TO BE GIVEN THE
 ADDRESSES FOR THE DUPLEX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-09-23 Cont ID  
Sent By jgomez Date 2021-09-23 Time 15:21 Rev Time 0.00
Received By jgomez Date 2021-09-23 Time 14:16 Sent To  
Notes
2021-09-23 15:22:34BUILDING APPROVED WITH PROVISO:
 1- PROVIDE PRODUCT APPROVALS FOR REVIEW PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL:
 A)ENTRY DOOR. B)SLIDING GLASS DOORS. C)SINGLE HUNG
 WINDOWS. D)ROOF SHINGLES. E)ROOF RIDGE VENT. SEE ROOF
 RIDGE DETAIL ON SHEET A-5. F)SHUTTERS WITH COMPLETE
 INSTALLATION SCHEDULE IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-20 Cont ID  
Sent By jgomez Date 2021-08-20 Time 17:27 Rev Time 0.00
Received By jgomez Date 2021-08-20 Time 13:01 Sent To  
Notes
2021-08-20 17:27:44NEW DUPLEX (R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21041108
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 ***NOTE: PLANS NEED ARCHITECT'S SIGNATURE BEFORE
 APPROVING WITH PROVISO. SEE ITEM #1 BELOW.
  
 1- ARCHITECTURAL AND STRUCTURAL PLANS SUBMITTED DON'T
 HAVE THE ARCHITECT'S SEAL AND SIGNATURE. ALL DRAWINGS
 NEED ARCHITECT'S ORIGINAL SEAL/SIGNATURE AS REQUIRED BY
 SEC. 481 F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
 PLANS WERE SUBMITTED ELECTRONICALLY. NEED PLANS WITH
 ARCHITECT'S DIGITAL SIGNATURE OR PROVIDE HARD COPY
 PLANS WITH THE ORIGINAL SEAL AND SIGNATURE.
  
 2- PROVIDE DETAIL AND SPECIFICATIONS FOR MONOLITHIC
 BEAM SUPPORTING THE 7" CONCRETE SLAB SHOWN ON THE TWO
 STORY WALL SECTION AND BUILDING SECTION A-A.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- ENERGY CALCULATIONS (FIRST FLOOR):
 A)ITEM #2 IS INCORRECT. ITEM #2 IS ASKING IF "SINGLE
 FAMILY OR MULTIPLE FAMILY". WHAT IS "ATTACHED". REVISE
 AS REQUIRED. PROVIDE CORRECT ANSWER.
 NOTE: REVISE ITEM #3 ALSO. PROVIDE NUMBER OF UNITS.
 THIS IS A DUPLEX.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 B)ITEM #5 SPECIFIES NO WORST CASE SCENARIO, BUT TOP OF
 PAGE 2 SPECIFIES AN ANGLE ROTATION OF 270 DEGREES.
 REVISE AS REQUIRED. ENERGY CALCULATIONS NEED TO BE SITE
 SPECIFIC AS REQUIRED BY SEC. R405.4.2.1 (4) FBC- ENERGY
 CONSERVATION.
  
 C)CEILING INFORMATION ON ITEM #11 IS INCORRECT. REVISE
 THE AREA. THE CEILING OF THE FIRST FLOOR IS THE SECOND
 FLOOR ASSEMBLY AND IT IS NOT VENTED. ALSO,
 ARCHITECTURAL PLANS DON'T SPECIFY INSULATION. REVISE AS
 REQUIRED TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 D)CEILING INFORMATION ON PAGE 3 OF 6 IS INCORRECT. THE
 CEILING ON FIRST FLOOR IS NOT WOOD. SEE PLANS AND
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 E)DOORS INFORMATION ON PAGE 4 OF 6 IS INCORRECT.
 ACCORDING TO ARCHITECT'S EXTERIOR ELEVATIONS, ENTRY
 DOORS HAVE A LARGE GLASS PANEL. SEE PLANS. THIS DOOR
 SHOULD BE INCLUDED IN THE WINDOW/GLAZING AREA AS
 REQUIRED BY SEC. R405.5.3 FBC- ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 F) WINDOWS INFORMATION ON PAGE 4 OF 6 DOESN'T MATCH
 PLANS. REVISE WINDOW ORIENTATION, WINDOW AREA AND
 WINDOW OVERHANG DEPTH AND SEPARATION TO MATCH
 ARCHITECT'S PLANS AND EXTERIOR ELEVATIONS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 G)BUILDER TO COMPLETE AND SIGN THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 5- ENERGY CALCULATIONS (SECOND FLOOR):
 A)ITEM #2 IS INCORRECT. IT IS ASKING IF "SINGLE FAMILY
 OR MULTIPLE FAMILY". WHAT IS "ATTACHED". REVISE AS
 REQUIRED. PROVIDE CORRECT ANSWER.
 NOTE: REVISE ITEM #3 ALSO. PROVIDE NUMBER OF UNITS.
 THIS IS A DUPLEX.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 B)ITEM #5 SPECIFIES NO WORST CASE SCENARIO, BUT TOP OF
 PAGE 2 SPECIFIES AN ANGLE ROTATION OF 270 DEGREES.
 REVISE AS REQUIRED. ENERGY CALCULATIONS NEED TO BE SITE
 SPECIFIC AS REQUIRED BY SEC. R405.4.2.1 (4) FBC- ENERGY
 CONSERVATION.
  
 C)DOORS INFORMATION ON PAGE 4 OF 6 IS INCORRECT.
 ACCORDING TO ARCHITECT'S EXTERIOR ELEVATIONS, ENTRY
 DOORS HAVE A LARGE GLASS PANEL. SEE PLANS. THIS DOOR
 SHOULD BE INCLUDED IN THE WINDOW/GLAZING AREA AS
 REQUIRED BY SEC. R405.5.3 FBC- ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 D)BUILDER TO COMPLETE AND SIGN THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 3- DEFERRED SUBMITTAL: PROVIDE PRODUCT APPROVALS PRIOR
 TO INSTALLATION. ALL PRODUCT APPROVALS NEED TO BE
 APPROVED IN WRITING BY DESIGNER OF RECORD PRIOR TO
 SUBMITTAL:
 A)ENTRY DOOR.
 B)SLIDING GLASS DOORS.
 C)SINGLE HUNG WINDOWS
 D)ROOF SHINGLES.
 E)ROOF RIDGE VENT. SEE ROOF RIDGE DETAIL ON SHEET A-5.
 F)SHUTTERS WITH COMPLETE INSTALLATION SCHEDULE IF DOORS
 AND WINDOWS DON'T HAVE IMPACT GLAZING.
  
 4- WINDOWS AND DOORS DETAILS ON SHEET A-4 ARE MISSING
 THE STRUCTURAL BUCK FASTENING SPECIFICATIONS. DESIGNER
 OF RECORD NEEDS TO SPECIFY FASTENER TYPE, SIZE AND
 SPACING. PRODUCT APPROVAL IS ONLY FOR THE WINDOW/DOOR
 ATTACHMENT.
 SEC. R301.1 FBC-RESIDENTIAL.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-16 Cont ID  
Sent By jgomez Date 2021-06-16 Time 14:07 Rev Time 0.00
Received By jgomez Date 2021-06-16 Time 10:03 Sent To  
Notes
2021-06-16 14:08:37COMMENTS UPDATED 07/07/21 AND EMAILED TO VICTOR
 VELASQUEZ.
 THERE IS A CONCERN ABOUT THE DESIGN OF THE BEAM AND
 COLUMNS SUPPORTING THE WEIGHT OF PROPOSED 8" CONCRETE
 SLAB (THIS WAS DISCUSSED WITH ROBERT BROWN, BUILDING
 OFFICIAL):
 1- SECOND FLOOR CONCRETE SLAB:
 A)STRUCTURAL PLANS SHOW AN 8" CONCRETE SLAB TO BE
 SUPPORTED ON 8X20 CONCRETE BEAM AND 3-1/4 X 3-1/4 X 1/4
 TUBE COLUMNS. PROVIDE CALCULATIONS SHOWING THAT THE
 STEEL REINFORCEMENT SPECIFIED FOR THE CONCRETE BEAM
 (2#5 BARS ON TOP AND 2#7 BARS AT BOTTOM)IS ADEQUATE TO
 TRANSFER THE BENDING MOMENT OF THE CONTINUOUS CONCRETE
 BEAM AT THE STEEL COLUMNS. ALSO, CHECK THE BUCKLING OF
 THE TUBE COLUMNS. SEC. 107.2.1.2 CITY AMENDMENTS. SEC.
 R301.1 FBC-RESIDENTIAL.
 B)FOUNDATION PLAN IS MISSING THE FOOTING FOR COLUMN
 SUPPORTING THE REAR END OF 8X20 CONCRETE BEAM. SEC.
 107.2.1.2 CITY AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL.
 C)CLARIFY WHY COLUMN SUPPORTING THE REAR END OF 8X20
 CONCRETE BEAM IS DIFFERENT THAN THE ONE SPECIFIED AT
 THE FRONT END. SEC. 107.2.1.2 CITY AMENDMENTS. SEC.
 R301.1 FBC-RESIDENTIAL.
  
  
  
  
 COMMENTS UPDATED 06/22/21.
 GOOD AFTERNOON MR. VELASQUEZ,
 THE ANSWER IS YES. YOU NEED TO PROVIDE AN APPROVED
 ASSEMBLY THAT MEETS THE FIRE RATING SPECIFIED ON THE
 TWO STORY WALL SECTION AND BUILDING SECTION A-A.
 THE ASSEMBLY NEEDS TO BE TESTED IN ACCORDANCE WITH ASTM
 E119 OR UL 263 OR ANY OTHER METHOD DESCRIBED IN SEC.
 703.3 FBC-BUILDING.
  
 NOTE:
 1) ALSO, NEED TO PROVIDE A FIRE RATED WALL ASSEMBLY FOR
 FIRST FLOOR EXTERIOR WALL SUPPORTING THE SECOND FLOOR
 ASSEMBLY SPECIFIED ON TWO STORY WALL SECTION AND
 BUILDING SECTION A-A.
 I APOLOGIZE, I MEANT TO ADD THIS IN MY COMMENTS, BUT
 SOMEHOW I DIDN'T DO IT. NOW THAT I HAVE A SECOND CHANCE
 TO READ THE COMMENTS I REALIZED THIS. I WILL UPDATE MY
 COMMENTS ACCORDINGLY.
  
 2)ALSO, PROVIDE DETAIL AND SPECIFICATIONS FOR
 MONOLITHIC BEAM SUPPORTING THE 8" CONCRETE SLAB SHOWN
 ON THE TWO STORY WALL SECTION AND BUILDING SECTION A-A.
 I APOLOGIZE, I MEANT TO ADD THIS IN MY COMMENTS, BUT
 SOMEHOW I DIDN'T DO IT. NOW THAT I HAVE A SECOND CHANCE
 TO READ THE COMMENTS I REALIZED THIS. I WILL UPDATE MY
 COMMENTS ACCORDINGLY.
  
 THANK YOU
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
 NEW DUPLEX (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21041108
  
 1- INTERIOR STEEL COLUMNS SUPPORTING THE SECOND FLOOR
 CONCRETE SLAB NEED TO BE FIRE RATED AS REQUIRED BY SEC.
 R302.3.1 FBC-RESIDENTIAL. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR APPROVED ASSEMBLIES SHOWING FIRE
 RESISTANCE COMPLIANCE.
  
 2- SECOND FLOOR ASSEMBLY: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR APPROVED ASSEMBLIES SHOWING FIRE
 RESISTANCE COMPLIANCE THRU FLOOR ASSEMBLY PENETRATIONS
 AS REQUIRED BY SEC. 302.4 FBC-RESIDENTIAL.
  
 3- LOT DRAINAGE:
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 4- ENERGY CALCULATIONS (FIRST FLOOR):
 A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION.
  
 B)DESIGN LOCATION SPECIFIED ON TOP OF FORM 405-2020 AND
 UNDER CLIMATE HEADING ON PAGE 2 OF 6 IS INCORRECT. THIS
 HOUSE IS NOT IN FORT PIERCE. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. NEED CORRECT LOCATION AND BUILDER'S NAME. SEC.
 R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 D)ITEM #2 IS NOT CLEAR. ITEM #2 IS ASKING IF "SINGLE
 FAMILY OR MULTIPLE FAMILY". WHAT IS "DETACHED". REVISE
 AS REQUIRED. PROVIDE CORRECT ANSWER.
 NOTE: COORDINATE WITH ITEM #3.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 E)ITEM #5 SPECIFIES WORST CASE SCENARIO. ENERGY
 CALCULATIONS NEED TO BE SITE SPECIFIC AS REQUIRED BY
 SEC. R405.4.2.1 (4) FBC- ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 F)CONDITIONED FLOOR AREA SPECIFIED ON ITEM #6 DOESN'T
 MATCH AREA SPECIFIED ON ARCHITECT'S PLANS. REVISE AS
 REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)CEILING INFORMATION ON ITEM #11 IS INCORRECT. REVISE
 THE AREA. THE CEILING OF THE FIRST FLOOR IS THE SECOND
 FLOOR ASSEMBLY AND IT IS NOT VENTED. ALSO,
 ARCHITECTURAL PLANS DON'T SPECIFY INSULATION. REVISE AS
 REQUIRED TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 H)ROOF INFORMATION ON PAGE 3 OF 6 IS INCORRECT. REVISE
 AS REQUIRED.
 NOTE: COORDINATE WITH ITEM 4(G) ABOVE. AND, COORDINATE
 WITH ARCHITECT'S PLANS FOR SECOND FLOOR ENERGY
 CALCULATIONS. SEE CORRECT ROOF TYPE AND ROOFING
 MATERIAL.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 I)ATTIC INFORMATION ON PAGE 3 OF 6 IS INCORRECT. THERE
 IS NOT ATTIC ON THE FIRST FLOOR.
 NOTE: COORDINATE WITH ITEM 4(G) ABOVE. AND, COORDINATE
 WITH ARCHITECT'S PLANS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 J)CEILING INFORMATION ON PAGE 3 OF 6 IS INCORRECT. THE
 CEILING ON FIRST FLOOR IS CONCRETE NOT WOOD. SEE PLANS.
 NOTE: COORDINATE WITH ITEM 4(G) ABOVE. AND, COORDINATE
 WITH ARCHITECT'S PLANS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 K)DOORS INFORMATION ON PAGE 4 OF 6 IS INCORRECT.
 ACCORDING TO ARCHITECT'S EXTERIOR ELEVATIONS, ENTRY
 DOORS HAVE A LARGE GLASS PANEL. SEE PLANS. THIS DOOR
 SHOULD BE INCLUDED IN THE WINDOW/GLAZING AREA AS
 REQUIRED BY SEC. R405.5.3 FBC- ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 L) WINDOWS INFORMATION ON PAGE 4 OF 6 DOESN'T MATCH
 PLANS. REVISE WINDOW ORIENTATION, WINDOW AREA AND
 WINDOW OVERHANG DEPTH AND SEPARATION TO MATCH
 ARCHITECT'S PLANS AND EXTERIOR ELEVATIONS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 M)BUILDER TO COMPLETE AND SIGN THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 5- ENERGY CALCULATIONS (SECOND FLOOR):
 A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION.
  
 B)DESIGN LOCATION SPECIFIED ON TOP OF FORM 405-2020 AND
 UNDER CLIMATE HEADING ON PAGE 2 OF 6 IS INCORRECT. THIS
 HOUSE IS NOT IN FORT PIERCE. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. NEED CORRECT LOCATION AND BUILDER'S NAME. SEC.
 R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 D)ITEM #2 IS NOT CLEAR. ITEM #2 IS ASKING IF "SINGLE
 FAMILY OR MULTIPLE FAMILY". WHAT IS "DETACHED". REVISE
 AS REQUIRED. PROVIDE CORRECT ANSWER.
 NOTE: COORDINATE WITH ITEM #3.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 E)ITEM #5 SPECIFIES WORST CASE SCENARIO. ENERGY
 CALCULATIONS NEED TO BE SITE SPECIFIC AS REQUIRED BY
 SEC. R405.4.2.1 (4) FBC- ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 F)CONDITIONED FLOOR AREA SPECIFIED ON ITEM #6 DOESN'T
 MATCH AREA SPECIFIED ON ARCHITECT'S PLANS. REVISE AS
 REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)CEILING INFORMATION ON ITEM #11 IS INCORRECT. REVISE
 THE CEILING AREA.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 H)ROOF INFORMATION ON PAGE 3 OF 6 IS INCORRECT. TYPE OF
 ROOF IS NOT GABLE. THE ROOFING MATERIAL IS NOT BARREL
 TILE. SEE PLANS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 I)ATTIC INFORMATION ON PAGE 3 OF 6 IS INCORRECT.
 TYPICALLY VENT RATIO IS 1/150. SEE SEC. R806.2
 FBC-RESIDENTIAL. SEE PLANS AND REVISE AS REQUIRED.
 (PLANS DON'T SHOW VENTILATION RATIO OF 1/300 AS ALLOWED
 BY THE EXCEPTION OF SEC. R806.2 FBC-RESIDENTIAL).
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 J)DOORS INFORMATION ON PAGE 4 OF 6 IS INCORRECT.
 ACCORDING TO ARCHITECT'S EXTERIOR ELEVATIONS, ENTRY
 DOORS HAVE A LARGE GLASS PANEL. SEE PLANS. THIS DOOR
 SHOULD BE INCLUDED IN THE WINDOW/GLAZING AREA AS
 REQUIRED BY SEC. R405.5.3 FBC- ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 K) WINDOWS INFORMATION ON PAGE 4 OF 6 DOESN'T MATCH
 PLANS. REVISE WINDOW ORIENTATION, WINDOW AREA AND
 WINDOW OVERHANG DEPTH AND SEPARATION TO MATCH
 ARCHITECT'S PLANS AND EXTERIOR ELEVATIONS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 L)BUILDER TO COMPLETE AND SIGN THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 HANDRAILS AND GUARDRAILS SHOWING COMPLIANCE TABLE
 R301.5, SEC. R311.7.8 AND SEC. R312.1 FBC-RESIDENTIAL.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ENTRY DOOR.
 B)SLIDING GLASS DOORS.
 C)SINGLE HUNG WINDOWS
 D)ROOF SHINGLES.
 E)ROOF RIDGE VENT. SEE ROOF RIDGE DETAIL ON SHEET A-5.
 F)SHUTTERS WITH COMPLETE INSTALLATION SCHEDULE IF DOORS
 AND WINDOWS DON'T HAVE IMPACT GLAZING.
  
 8- PROVIDE DETAIL/SPECIFICATIONS FOR SECOND FLOOR
 FINISH FLOOR. NEED FLOOR SOUND INSULATION BETWEEN
 DWELLING UNITS AS REQUIRED BY SEC. 105.2 CITY
 AMENDMENTS.
 THE FOLLOWING FLOOR SOUND INFORMATION MAY BE SUBMITTED
 LATER AS A DEFERRED SUBMITTAL WHEN REVIEWED BY THE
 ARCHITECT OF RECORD:
 FLOORING SOUND INSULATION MATERIAL:
 A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION
 (2020).
 B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
 C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 9- WINDOWS AND DOORS DETAILS ON SHEET A-4 ARE MISSING
 THE STRUCTURAL BUCK FASTENING SPECIFICATIONS. DESIGNER
 OF RECORD NEEDS TO SPECIFY FASTENER TYPE, SIZE AND
 SPACING.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 10- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $359,252. THE
 PERMIT FEE BALANCE IS $1825.90.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-10-01 Cont ID  
Sent By fgiaquin Date 2021-10-01 Time 23:35 Rev Time 0.00
Received By fgiaquin Date 2021-10-01 Time 21:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-08-17 Cont ID  
Sent By fgiaquin Date 2021-08-17 Time 21:25 Rev Time 0.00
Received By fgiaquin Date 2021-08-17 Time 19:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-05-18 Cont ID  
Sent By fgiaquin Date 2021-05-18 Time 23:36 Rev Time 0.00
Received By fgiaquin Date 2021-05-18 Time 22:27 Sent To  
Notes
2021-05-18 23:36:49ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO EQUIPMENT GROUND SHOWN FROM SERVICE DISCONNECTS
 TO INTERIOR PANELS. NEC 250.4A3
  
 2. RISER ONLY SHOWS ONE METER AND DISC BUT PLANS SHOWS
 DISC/METER FOR EACH UNIT. PROVIDE CORRECTION. FBC
 107.2.1
  
 3. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
  
 4. NO ARC-FAULT PROTECTION SHOWN. PROVIDE CORRECTION
 PER NEC 210.12
  
 5. SMOKE ALARMS MUST BE 3FT FROM BEDROOMS NFPA 72
 29.8.3.4 #6
  
 6. NO WORKING CLEARANCE FOR AC CONDENSOR DISCONNECTS
 NEC 110.26A1
  
 7. TAMPERPROOF RECEPTACLES REQUIRED NEC 406.12
  
 8. GEC TO CONCRETE ENCASED ELECTRODE IS TO BE MINIMUM
 #4 CU NEC 250.66B
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-10-26 Cont ID  
Sent By lmarchan Date 2021-10-26 Time 12:07 Rev Time 0.00
Received By lmarchan Date 2021-10-15 Time 06:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-10-14 Cont ID  
Sent By lmarchan Date 2021-10-14 Time 11:45 Rev Time 0.00
Received By lmarchan Date 2021-09-10 Time 12:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-01 Cont ID  
Sent By lmarchan Date 2021-09-01 Time 08:40 Rev Time 0.00
Received By lmarchan Date 2021-08-05 Time 14:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-06-16 Cont ID  
Sent By jgomez Date 2021-06-16 Time 14:27 Rev Time 0.00
Received By jgomez Date 2021-05-05 Time 17:05 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-12-13 Cont ID  
Sent By lmarchan Date 2021-12-13 Time 15:18 Rev Time 0.00
Received By lmarchan Date 2021-10-19 Time 15:01 Sent To  
Notes
2021-12-13 11:56:27RECEIPT MU-2021-051441 - $7439.26 PAID
2021-10-19 15:01:5110/19/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-06-16 Cont ID  
Sent By jgomez Date 2021-06-16 Time 14:12 Rev Time 0.00
Received By jgomez Date 2021-06-16 Time 14:12 Sent To  
Notes
2021-06-16 14:13:02IMPACT FEES
  
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-08-19 Cont ID  
Sent By medwards Date 2021-08-19 Time 12:44 Rev Time 0.00
Received By medwards Date 2021-08-19 Time 11:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-05-14 Cont ID  
Sent By medwards Date 2021-05-14 Time 14:10 Rev Time 0.00
Received By medwards Date 2021-05-14 Time 12:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-09-24 Cont ID  
Sent By ccole Date 2021-09-24 Time 16:53 Rev Time 0.00
Received By ccole Date 2021-09-24 Time 16:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-08-13 Cont ID  
Sent By ccole Date 2021-08-13 Time 10:52 Rev Time 0.00
Received By ccole Date 2021-08-13 Time 09:06 Sent To  
Notes
2021-08-13 10:52:392ND REVIEW FBC-2020 RES.
 PERMIT- 21041108
 8/13/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENT #1 FROM THE 1ST
 REVIEW PRINTED BELOW HAS NOT BEEN COMPLETED ADDRESSED.
 THE REVISED PLAN SHOWS ELECTRIC TANKLESS WATER HEATERS
 ON THE EXTERIOR OF THE BUILDING WHICH WOULD NOT BE A
 TYPICAL APPROVED INSTALLATION LOCATION. PLEASE PROVIDE
 AN EQUIPMENT SCHEDULE ON THE PLAN AND SUBMIT
 MANUFACTURER?S SPECIFICATIONS AND INSTALLATION
 GUIDELINES. PLEASE NOTE THE MANUFACTURER MAY REQUIRE
 THE UNITS WILL TO BE HOUSED IN APPROVED WEATHER AND
 WIND RESISTANT BOXES. IT IS ALSO IMPORTANT TO NOTE THAT
 THE CICUIT BREAKER SIZES AND 4.5 KVA RATINGS SHOWN IN
 THE ELECTRICAL PANEL BOX SCHEDULE FOR THE TANKLESS
 UNITS WOULD INDICATE A VERY LOW CAPACITY UNIT, NOT
 TYPICALLY USED FOR WHOLE HOUSE HOT WATER DISTRIBUTION.
  
 1) SHEET E-1: SHOW THE LOCATIONS OF THE WATER HEATERS
 AND PROVIDE EQUIPMENT SCHEDULES INDICATING MAKES,
 MODELS, GALLON SIZES, AND EFFICIENCY RATINGS- SECTION
 P2801.1 FBC RES AND C404.2 FBC EC. PLEASE NOTE THAT
 INSTALLATION OF PANS AND PAN DRAINS WILL BE REQUIRED
 FOR STORAGE WATER HEATERS IF LOCATED WHERE LEAKAGE WILL
 CAUSE DAMAGE- SECTIONS P2801.6, P2801.6.1, & P2801.6.2
 FBC RES. PLEASE PROVIDE DETAILS ON THE PLAN AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE WATER HEATERS-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-05-17 Cont ID  
Sent By ccole Date 2021-05-17 Time 15:16 Rev Time 0.00
Received By ccole Date 2021-05-17 Time 11:44 Sent To  
Notes
2021-05-17 15:16:531ST REVIEW FBC-2020 RES.
 PERMIT- 21041108
 5/17/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET E-1: SHOW THE LOCATIONS OF THE WATER HEATERS
 AND PROVIDE EQUIPMENT SCHEDULES INDICATING MAKES,
 MODELS, GALLON SIZES, AND EFFICIENCY RATINGS- SECTION
 P2801.1 FBC RES AND C404.2 FBC EC. PLEASE NOTE THAT
 INSTALLATION OF PANS AND PAN DRAINS WILL BE REQUIRED
 FOR STORAGE WATER HEATERS IF LOCATED WHERE LEAKAGE WILL
 CAUSE DAMAGE- SECTIONS P2801.6, P2801.6.1, & P2801.6.2
 FBC RES. PLEASE PROVIDE DETAILS ON THE PLAN AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE WATER HEATERS-
 SECTION 107.2.1 WPB.
  
 2) E-1: PLEASE REVISE THE RISER TO CLEARLY SHOW THE
 BATHROOM WET VENTS ARE IN COMPLIANCE WITH SECTION-
 P3108.2.1 FBC RES- NOT MORE THAN ONE WET-VENTED FIXTURE
 DRAIN SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED
 FIXTURE DRAIN CONNECTION.
  
 3) A SEPARATE PERMIT IS REQUIRED FOR THE SEPTIC SYSTEM.
 FOR PERMITTING INFORMATION PLEASE CONTACT THE PALM
 BEACH COUNTY DEPARTMENT OF HEALTH- ENVIRONMENTAL HEALTH
 DIVISION.
  
 4) PLEASE NOTE THAT THE PROPOSED PROJECT IS A
 MULTI-FAMILY DWELLING BUILDING WHICH REQUIRES WATER
 USERS TO INSTALL BACKFLOW PREVENTION ASSEMBLIES AT THE
 POINTS OF DELIVERY. THE TYPE OF BACKFLOW ASSEMBLY
 REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF HAZARD
 POSED BY THE WATER USER. A REDUCED PRESSURE ZONE
 BACKFLOW DEVICE WILL BE NEEDED FOR THE WATER METER PER
 THE CITY OF WEST PALM CROSS UTILITIES AND THEIR
 CONNECTION CONTROL PROGRAM. PLEASE NOTE THAT A FL.
 LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A SEPARATE
 PERMIT FOR INSTALLATION OF THE BACKFLOW PREVENTER IN
 ACCORDANCE WITH SECTION 105.1 WPB AND SEC. 90-33 WPB
 CODE OF ORDINANCES. THE DEVICE SHALL BE TESTED AND
 CERTIFIED BY THE WPB UTILITIES DEPARTMENT PRIOR TO
 FINAL INSPECTION BY THE BUILDING DEPARTMENT. PLEASE
 CONTACT THE WPB UTILITIES CENTRAL OPERATIONS DEPT.AT
 561-822-2210 FOR FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2021-08-20 Cont ID  
Sent By jgomez Date 2021-08-20 Time 17:28 Rev Time 0.00
Received By jgomez Date 2021-08-20 Time 17:27 Sent To  
Notes
2021-08-20 17:29:51PROVIDE ROOFING PRODUCT APPROVALS AS A DEFERRED
 SUBMITTAL OR SUBMIT COMPLETE INFORMATION FOR REVIEW
 WHEN APPLYING FOR THE ROOFING SUB-PERMIT.JG.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-06-16 Cont ID  
Sent By jgomez Date 2021-06-16 Time 14:11 Rev Time 0.00
Received By jgomez Date 2021-06-16 Time 14:11 Sent To  
Notes
2021-06-16 14:12:15ROOFING REVIEW COMMENTS:
  
 1-- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF SHINGLES.
 B) ROOF RIDGE VENT. SEE ROOF RIDGE DETAIL ON SHEET A-5.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-09-23 Cont ID  
Sent By jgomez Date 2021-09-23 Time 14:36 Rev Time 0.00
Received By jgomez Date 2021-09-23 Time 14:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-08-20 Cont ID  
Sent By jgomez Date 2021-08-20 Time 17:30 Rev Time 0.00
Received By jgomez Date 2021-08-20 Time 17:29 Sent To  
Notes
2021-08-20 17:30:46SIGNATURE REVIEW COMMENTS.
  
 1- ARCHITECTURAL AND STRUCTURAL PLANS SUBMITTED DON'T
 HAVE THE ARCHITECT'S SEAL AND SIGNATURE. ALL DRAWINGS
 NEED ARCHITECT'S ORIGINAL SEAL/SIGNATURE AS REQUIRED BY
 SEC. 481 F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
 PLANS WERE SUBMITTED ELECTRONICALLY. NEED PLANS WITH
 ARCHITECT'S DIGITAL SIGNATURE OR PROVIDE HARD COPY
 PLANS WITH THE ORIGINAL SEAL AND SIGNATURE.
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2- SURVEY NEEDS ORIGINAL SEAL/SIGNATURE AS REQUIRED BY
 CHAPTER 472 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR
 PUBLIC RECORDS. PROVIDE HARD COPY WITH ORIGINAL
 SEAL/SIGNATURE OR UPLOAD SURVEY WITH DIGITAL SIGNATURE.
  
 3- SOIL TEST REPORT WAS NOT SIGNED BY THE ENGINEER OF
 RECORD. NEED ORIGINAL SEAL/SIGNATURE AS REQUIRED BY
 CHAPTER 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR
 PUBLIC RECORDS.
 SUBMIT DRAWINGS ELECTRONICALLY WITH ENGINEER'S DIGITAL
 SIGNATURE OR PROVIDE HARD COPY WITH ENGINEER'S ORIGINAL
 SEAL AND SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-06-16 Cont ID  
Sent By jgomez Date 2021-06-16 Time 14:13 Rev Time 0.00
Received By jgomez Date 2021-06-16 Time 14:13 Sent To  
Notes
2021-06-14 16:08:26SIGNATURE REVIEW COMMENTS.
  
 1- UNABLE TO VERIFY ARCHITECTS DIGITAL SIGNATURE FOR
 ALL THE ARCHITECTURAL, STRUCTURAL AND ELECTRICAL PLANS.
 AFTER PLANS ARE REVISED UPLOAD THEM TO PROJECTDOX WITH
 VERIFIABLE DIGITAL SIGNATURE.
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2- SURVEY NEEDS ORIGINAL SEAL/SIGNATURE AS REQUIRED BY
 CHAPTER 472 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR
 PUBLIC RECORDS. PROVIDE HARD COPY WITH ORIGINAL
 SEAL/SIGNATURE OR UPLOAD SURVEY WITH DIGITAL SIGNATURE.
  
 3- SOIL TEST REPORT WAS NOT SIGNED BY THE ENGINEER OF
 RECORD. NEED ORIGINAL SEAL/SIGNATURE AS REQUIRED BY
 CHAPTER 471 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR
 PUBLIC RECORDS.
 SUBMIT DRAWINGS ELECTRONICALLY WITH ENGINEER'S DIGITAL
 SIGNATURE OR PROVIDE HARD COPY WITH ENGINEER'S ORIGINAL
 SEAL AND SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2021-10-25 Cont ID  
Sent By ajones Date 2021-10-25 Time 15:57 Rev Time 0.00
Received By ajones Date 2021-10-25 Time 15:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2021-10-14 Cont ID  
Sent By ajones Date 2021-10-14 Time 11:44 Rev Time 0.00
Received By ajones Date 2021-10-14 Time 11:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-08-31 Cont ID  
Sent By kalexand Date 2021-08-31 Time 19:45 Rev Time 0.00
Received By kalexand Date 2021-08-31 Time 19:45 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-06-02 Cont ID  
Sent By kalexand Date 2021-06-02 Time 17:39 Rev Time 0.00
Received By kalexand Date 2021-06-02 Time 17:39 Sent To  
Notes
2021-06-02 17:40:34ZONING PLAN REVIEW
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE THE TOTAL HEIGHT OF THE PROPOSED HOME ON AN
 ELEVATION PLAN. PURSUANT TO THE ZLDR, SECTION 94-611,
 HEIGHT OF STRUCTURE MEANS THE VERTICAL DISTANCE FROM
 THE AVERAGE ELEVATION OF THE FINISHED GRADE OF THE
 STRUCTURE TO THE HIGHEST PORTION OF THE STRUCTURE,
 SUBJECT TO SPECIFIED HEIGHT REQUIREMENTS OF THIS
 CHAPTER. FOR BUILDINGS, THE HEIGHT SHALL BE MEASURED AS
 THE VERTICAL DISTANCE FROM THE AVERAGE ELEVATION OF THE
 FINISHED GRADE OF THE BUILDING TO THE HIGHEST POINT OF
 THE TOP OF THE STRUCTURE OF A FLAT ROOF, OR TO THE DECK
 LINE OF A MANSARD ROOF, OR TO THE MEAN HEIGHT LEVEL
 BETWEEN EAVES AND RIDGE FOR GABLE, HIP, AND GAMBREL
 ROOFS.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved