| Plan Review Stops For Permit 21041010 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2023-03-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-03-06 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-03-06 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2023-03-06 15:27:08 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- REVISE ENERGY CALCULATIONS: (A)COMPLETE TOP OF FORM, | | | INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE | | | AND JURISDICTION NUMBER (THIS JURISDICTION IS 604700). | | | (B)REVISE ITEM #1. THIS IS NOT NEW CONSTRUCTION. | | | (C)REVISE ITEM #11. CEILING INSULATION IS REQUIRED. | | | SEC. R405.2.1 FBC-ENERGY CONSERVATION. (D)PROVIDE HOT | | | WATER INFORMATION. (E)ITEM #16 IS TAKING THE CEILING | | | FAN CREDIT. REVISE AS REQUIRED TO MATCH PLANS. | | | (F)REVISE DOORS INFORMATION. WINDOW/DOOR PERMIT | | | #22031558 AND #22031203 THERE ARE NOT WOOD DOORS. NOTE: | | | GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE WINDOW | | | GLAZING AREA. (G)REVISE THE WINDOWS INFORMATION ON PAGE | | | 3 TO MATCH PLANS. ALSO, INCLUDE DOORS WITH GLAZING. | | | 2- REVISE WINDOW/DOOR DESIGN PRESSURES AS REQUIRED TO | | | CORRESPOND TO EXPOSURE ???D???. | | | 3- SHEET S102: ENGINEER OF RECORD TO PROVIDE | | | SPECIFICATIONS FOR THE CONCRETE SLAB VAPOR BARRIER. | | | 4- SHEET S103: SECTION 1: SPECIFY HOW IS THE 2X P.T. | | | RAFTER ATTACHED TO THE BEAM?. | | | 5- SHEET S104: ENGINEER TO PROVIDE SPECIFICATIONS FOR | | | WELDING AT THE BASE AND TOP PLATES OF STEEL COLUMNS. | | | ALSO, CLARIFY WHERE THE STEEL COLUMNS AND BEAMS ARE | | | GOING TO BE INSTALLED. | | | | | | | | | 03/06/23 TALKED TO MARK DONNELLY. GO WITH PROVISO. | | | | | | RESPONSE FROM MARK DONNELLY: | | | PLEASE GO WITH PROVISO. | | | ON THU, MAR 2, 2023 AT 2:15???PM JULIO C. GOMEZ | | | WROTE: | | | GOOD AFTERNOON MARK, | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2023-03-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-03-02 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-03-02 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2023-03-02 13:38:08 | RESIDENTIAL(R3) ADDITION, ALTERATION BUILDING REVIEW | | | COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT # 21041010 | | | 101 GREYMON DR | | | | | | | | | PROVISO NOTE: | | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER | | | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID | | | CONFLICTS/DELAYS. REVISION FEES APPLY (EXCEPT FOR | | | PRODUCT APPROVALS DEFERRED SUBMITTAL). | | | | | | ***IMPORTANT**** | | | CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED AT | | | THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION | | | BEFORE PERMIT ISSUANCE. | | | | | | | | | PREVIOUS COMMENT: | | | (2)-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | 1106 FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY | | | CONSERVATION. | | | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL | | | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID | | | CONFLICTS/DELAYS. | | | | | | RESPONSE | | | REVISE ENERGY CALCULATIONS SUBMITTED: | | | (A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, | | | INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE | | | AND JURISDICTION NUMBER (THIS JURISDICTION IS 604700). | | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | | | (B)REVISE ITEM #1 ON PAGE 1. THIS IS NOT NEW | | | CONSTRUCTION, THIS IS EXISTING. SEC. R101.5.1.1.2 | | | FBC-ENERGY CONSERVATION. | | | | | | (C)REVISE ITEM #11 ON PAGE 1. CEILING INSULATION IS | | | REQUIRED. SEC. R405.2.1 FBC-ENERGY CONSERVATION. | | | | | | (D)SPECIFY HOT WATER SYSTEM INFORMATION AS REQUIRED BY | | | SEC. R403.5.6 FBC-ENERGY CONSERVATION. | | | | | | (E)ITEM #16 ON PAGE 1 IS TAKING THE CEILING FAN CREDIT. | | | PLANS DON'T SHOW CEILING FANS. REVISE AS REQUIRED TO | | | MATCH PLANS OR REVISE PLANS SHOWING THE CEILING FAN | | | SIZES AND NUMBER OF FANS REQUIRED FOR EACH ROOM BASED | | | ON THE SIZE AS REQUIRED BY TABLE R405.7.6 FBC-ENERGY | | | CONSERVATION. | | | | | | (F)REVISE DOORS INFORMATION ON PAGE 3. ACCORDING TO | | | WINDOW/DOOR REPLACEMENT PERMIT #22031558 AND #22031203 | | | THERE ARE NOT WOOD DOORS. PRODUCT APPROVALS SUBMITTED | | | FOR THESE PERMITS ARE FOR GLAZED DOORS. | | | NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE | | | WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY | | | CONSERVATION) | | | | | | (G)REVISE THE WINDOWS INFORMATION ON PAGE 3 TO MATCH | | | PLANS. REVISE AREA AND NUMBER OF WINDOWS TO MATCH | | | PLANS. ALSO, INCLUDE DOORS WITH GLAZING. SEE COMMENT | | | ABOVE. | | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | | | 5- DESIGNER OF RECORD NEEDS TO SPECIFY COMPLETE DESIGN | | | CRITERIA: | | | PREVIOUS COMMENT: | | | D)COMPONENTS AND CLADDING DESIGN PRESSURES (DOORS AND | | | WINDOWS) | | | SEC. R301.2.1 FBC RESIDENTIAL. | | | | | | RESPONSE: | | | BUILDING EXPOSURE WAS REVISED TO D. THE DESIGN | | | PRESSURES SPECIFIED ON THE NEW WIND PRESSURE CHART ON | | | SHEET S100 SEEM TO BE TOO LOW COMPARED TO TABLE | | | R301.2(2)FBC-RESIDENTIAL AND TABLE | | | R301.2(3)FBC-RESIDENTIAL FOR THE HEIGHT AND EXPOSURE | | | ADJUSTMENT TO EXPOSURE D. REVISE DESIGN PRESSURES AS | | | REQUIRED OR ENGINEER TO PROVIDE ACTUAL CALCULATIONS. | | | SEC. 107.2.1.2 CITY AMENDMENTS. | | | | | | 20- PROPOSED PLAN ON SHEET S102: | | | PREVIOUS COMMENT: | | | D)THIS IS A CHANGE OF USE FROM GARAGE TO LIVABLE SPACE. | | | TYPICALLY, GARAGES ARE BUILT WITHOUT A FLOOR VAPOR | | | BARRIER. ENGINEER OF RECORD TO PROVIDE SPECIFICATIONS | | | FOR THE CONCRETE SLAB VAPOR BARRIER AS REQUIRED BY SEC. | | | R506.2.3 FBC-RESIDENTIAL. | | | ALSO, ENGINEER OF RECORD DOESN'T PROVIDE ANY | | | INFORMATION OF HOW THE GARAGE SLAB IS RAISED TO THE | | | EXISTING HOUSE LEVEL AS SHOWN ON SHEET A2.2. PROVIDE | | | COMPLETE INFORMATION. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | RESPONSE: | | | NO ADDRESSED. INFORMATION NO PROVIDED AND FOUNDATION | | | PLAN ON SHEET S102 STAYS "EXISTING SLAB TO REMAIN (NO | | | WORK)". REQUESTED INFORMATION WAS NOT PROVIDED. | | | | | | 21- SHEET S103: | | | PREVIOUS COMMENT: | | | B)SECTION 1: ENGINEER TO SPECIFY LENGTH OF #9 SCREWS. | | | HOW MUCH EMBEDMENT IS REQUIRED INTO THE 4X2 BATTEN?. | | | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.2.1 | | | FBC-RESIDENTIAL. | | | | | | RESPONSE: | | | DETAIL WAS REVISED BUT NOW IT DOESN'T SPECIFY HOW IS | | | THE 2X P.T. RAFTER ATTACHED TO THE BEAM? PROVIDE | | | SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL. | | | | | | PREVIOUS COMMENT: | | | 22)SHEET S104: ENGINEER TO PROVIDE SPECIFICATIONS FOR | | | WELDING AT THE BASE AND TOP PLATES OF STEEL COLUMNS. | | | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301 | | | FBC-RESIDENTIAL. | | | | | | RESPONSE: | | | REPEAT COMMENT. INFORMATION ON SHEET S104 WAS NOT | | | REVISED AND NOW IT IS NOT CLEAR WHERE THE STEEL COLUMNS | | | AND BEAMS ARE GOING TO BE INSTALLED. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-11-17 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-11-17 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2022-11-17 15:18:32 | 11/17/22 MARK DONNELLY EMAILED REVISED SCOPE OF WORK | | | AND APPRAISAL. IT WAS REVIEWED BY ROBERT BROWN AND IT | | | WAS APPROVED. THEREFORE, PROPOSED ALTERATION IS NOT | | | CONSIDERED A SUBSTANTIAL IMPROVEMENT. NO NEED TO RAISE | | | THE HOUSE. JG. | | | | | | RESIDENTIAL(R3) ADDITION, ALTERATION SECOND BUILDING | | | REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT # 21041010 | | | 101 GREYMON DR | | | | | | NOTE: | | | CHANGE OF OCCUPANCY SEC. 605 AND SEC. 1001.2.1, SEC. | | | 604 AND SEC. 901.2, SEC. 801.3 FBC-EXISTING BUILDING. | | | ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND | | | METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE. | | | | | | NOTE: | | | LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING. | | | SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3 | | | FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, | | | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE | | | REQUIREMENTS OF THE FLORIDA BUILDING CODE. | | | | | | NOTE: | | | ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1 | | | FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, | | | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE | | | REQUIREMENTS OF THE FLORIDA BUILDING CODE. | | | | | | ORIGINAL COMMENT: | | | 1- THE PROPOSED ADDITION IS GOING TO BE BUILT IN A AE | | | FLOOD ZONE WITH A BASE FLOOD ELEVATION (BFE) OF 6 FEET | | | BASED ON NAVD 88. | | | THE PROPOSED ADDITION IS CONSIDERED A SUBSTANTIAL | | | IMPROVEMENT. THE ADDITION AND THE EXISTING HOUSE SHALL | | | HAVE THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR | | | ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET. | | | THEREFORE, THE MIN. REQUIRED FINISHED FLOOR ELEVATION | | | IS 8 FEET. | | | NOTE: PLANS NEED TO SHOW THE PROPOSED FINISHED FLOOR | | | ELEVATION USING NAVD 88. NEED TO PROVIDE THE | | | CONSTRUCTION DRAWINGS ELEVATION CERTIFICATE AND SURVEY | | | SHOWING THE FINISH FLOOR ELEVATIONS FOR REVIEW. | | | CITY ORDINANCE 4729-17. | | | SEC. 18-33 TECHNICAL AMENDMENTS TO FLORIDA BUILDING | | | CODE. | | | SEC. 107.3.5.3 CITY AMENDMENTS. | | | | | | RESPONSE: | | | PROPERTY APPRAISAL SUBMITTED WAS REVIEWED WITH ROBERT | | | BROWN (BUILDING OFFICIAL). REVISED SCOPE OF WORK IS NOT | | | CONSIDERED A SUBSTANTIAL IMPROVEMENT. NO NEED TO RAISE | | | THE HOUSE. | | | | | | ORIGINAL COMMENT: | | | 2-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106 | | | FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY | | | CONSERVATION. | | | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL | | | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID | | | CONFLICTS/DELAYS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 3- OK. 2 STORY ADDITION REMOVED FROM SCOPE OF WORK. | | | | | | ORIGINAL COMMENT: | | | 4- LOT DRAINAGE: PROPOSED WORK AFFECTS THE LOT DRAINAGE | | | (DRIVEWAY AND REAR PAVERS). PROVIDE DRAINAGE PLAN | | | SHOWING HOW THE SURFACE DRAINAGE IS KEPT WITHIN THE LOT | | | AND NOT DIVERTED TO ADJACENT PROPERTIES. PROVIDE | | | DRAINAGE PLAN SHOWING COMPLIANCE WITH THE FOLLOWING | | | SECTIONS: R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY | | | AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS. | | | NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED | | | GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM | | | ADJACENT PROPERTIES. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | ORIGINAL COMMENT: | | | 5- ARCHITECT OF RECORD NEEDS TO SPECIFY COMPLETE DESIGN | | | CRITERIA: | | | A)OK. DONE BY NEW ENGINEER. | | | | | | ORIGINAL COMMENT: | | | B)BUILDING EXPOSURE (NOTE: THIS BUILDING IS LOCATED IN | | | EXPOSURE "D". | | | | | | RESPONSE: | | | ENGINEER TO REVISE DESIGN CRITERIA ON SHEET S100. THIS | | | BUILDING IS LOCATED IN EXPOSURE "D" NOT "C". | | | | | | ORIGINAL COMMENT: | | | C)ULTIMATE AND NOMINAL WIND SPEEDS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED BY THE ENGINEER. | | | | | | ORIGINAL COMMENT: | | | D)COMPONENTS AND CLADDING DESIGN PRESSURES (DOORS AND | | | WINDOWS) | | | SEC. R301.2.1 FBC RESIDENTIAL. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED BY THE ENGINEER. | | | | | | NEW COMMENT: | | | E) ENGINEER TO REVISE DESIGN CRITERIA ON SHEET S100. | | | THIS BUILDING IS NOT "OPENED" ENCLOSURE CLASSIFICATION. | | | REVISE ALL INFORMATION AS REQUIRED. | | | | | | 6- OK. 2 STORY ADDITION REMOVED FROM SCOPE OF WORK. | | | | | | ORIGINAL COMMENT: | | | 7- WINDOW SCHEDULE ON SHEET A-4 SPECIFIES "CASWELL | | | WINDOWS". PROVIDE MANUFACTURER'S CUT SHEETS FOR | | | CASEMENT WINDOW "H" SHOWING COMPLIANCE WITH BEDROOM | | | WINDOW EGRESS CLEAR OPENINGS, INCLUDING CLEAR WIDTH | | | OPENING. | | | SEC. R310.2.1 FBC-RESIDENTIAL. | | | | | | RESPONSE: | | | NO INFORMATION SUBMITTED ON REVISED PLANS. PROVIDE | | | COMPLIANCE WITH EMERGENCY EGRESS REQUIREMENTS FOR | | | JUNIOR BEDROOM. CLEARLY SPECIFY TYPE AND SIZE OF | | | WINDOWS AND PROVIDE MANUFACTURER'S CUT SHEETS FOR | | | WINDOW TO BE USED AS EMERGENCY ESCAPE. | | | | | | 8-11- OK. 2 STORY ADDITION REMOVED FROM SCOPE OF WORK. | | | | | | ORIGINAL COMMENT: | | | 12-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. CONTRACTOR TO ADVISE IF SUBMITTING NOW OR | | | LATER AS A DEFERRED SUBMITTAL). | | | | | | A)EXTERIOR DOORS. INSWING AND OUTSWING DOORS AS SHOWN | | | ON PLANS. | | | | | | B)WINDOWS. ALL WINDOW TYPES AS SHOWN ON PLANS. | | | | | | C)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE | | | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION | | | SCHEDULE. SEE CITY SAMPLE. | | | | | | D)METAL ROOF. (IF ROOF IS TO BE REPLACED. PLANS ARE NOT | | | CLEAR ON THIS). | | | | | | E)ROOFING UNDERLAYMENT. (IF ROOF IS TO BE REPLACED. | | | PLANS ARE NOT CLEAR ON THIS). | | | | | | F)WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED: | | | CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY | | | COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. | | | | | | G)FRONT AND REAR PORCH PROPOSED ROOFING PANELS. SEE | | | SHEET S103. | | | | | | 13- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | ORIGINAL COMMENT: | | | 14- PROVIDE DOOR AND WINDOW STRUCTURAL BUCK DETAIL | | | SHOWING COMPLIANCE WITH SEC. R609.7.2.1 | | | FBC-RESIDENTIAL. | | | | | | RESPONSE. | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 15-18- OK. 2 STORY ADDITION REMOVED FROM SCOPE OF WORK. | | | | | | NEW COMMENTS BASED ON REVISED DRAWINGS AND SCOPE OF | | | WORK: | | | 19- BUILDING PLAN REVIEW NOTE ON SHEET A0.0 REFERS TO | | | THE CITY OF CORAL GABLES. REVISE AS REQUIRED. PROVIDE | | | CORRECT INFORMATION. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 20- PROPOSED PLAN ON SHEET S102: | | | A)FLOOR PLAN IS MISSING INFORMATION FOR THE REAR PORCH. | | | LOCATION, FOOTINGS, COLUMNS, ETC. SEC. 107.2.1 CITY | | | AMENDMENTS. SEC. R301.2.1 FBC-RESIDENTIAL. | | | | | | B)FLOOR PLAN IS MISSING INFORMATION FOR NEW FOOTINGS | | | AND COLUMNS INFORMATION SHOWN ON SHEETS S104 AND S105 | | | FOR GARAGE INFILL WALL. SEC. 107.2.1 CITY AMENDMENTS. | | | SEC. R301.2.1 FBC-RESIDENTIAL. | | | | | | C) CONSTRUCTION OF NEW BEAMS BETWEEN DINING ROOM AND | | | KITCHEN AREA IS NOT CLEAR. PROPOSED FLOOR PLAN ON SHEET | | | S102 SHOWS I BEAMS, WHILE INFORMATION ON SHEET S104 AND | | | S105 SHOW DIFFERENT CONSTRUCTION MATERIALS. CLARIFY/ | | | COORDINATE TO AVOID CONFLICTS DELAYS. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | NOTE: WOOD FRAME DETAIL ON SHEET S104 IS MISSING ALL | | | STRUCTURAL CONNECTORS. | | | | | | D)THIS IS A CHANGE OF USE FROM GARAGE TO LIVABLE SPACE. | | | TYPICALLY, GARAGES ARE BUILT WITHOUT A FLOOR VAPOR | | | BARRIER. ENGINEER OF RECORD TO PROVIDE SPECIFICATIONS | | | FOR THE CONCRETE SLAB VAPOR BARRIER AS REQUIRED BY SEC. | | | R506.2.3 FBC-RESIDENTIAL. | | | ALSO, ENGINEER OF RECORD DOESN'T PROVIDE ANY | | | INFORMATION OF HOW THE GARAGE SLAB IS RAISED TO THE | | | EXISTING HOUSE LEVEL AS SHOWN ON SHEET A2.2. PROVIDE | | | COMPLETE INFORMATION. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 21- SHEET S103: | | | A)ENGINEER TO SPECIFY TYPE OF ROOF PANEL AND | | | ATTACHMENT. (NOTE: PRODUCT APPROVAL WILL BE REQUIRED). | | | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.2.1 | | | FBC-RESIDENTIAL. | | | | | | B)SECTION 1: ENGINEER TO SPECIFY LENGTH OF #9 SCREWS. | | | HOW MUCH EMBEDMENT IS REQUIRED INTO THE 4X2 BATTEN?. | | | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.2.1 | | | FBC-RESIDENTIAL. | | | | | | C)SECTION 2: ENGINEER TO SPECIFY TYPE AND LENGTH OF | | | 1/2" SCREWS. HOW MUCH EMBEDMENT IS REQUIRED INTO THE | | | EXISTING CONCRETE WALL. SEC. 107.2.1 CITY AMENDMENTS. | | | SEC. R301.2.1 FBC-RESIDENTIAL. | | | | | | D)ENGINEER TO PROVIDE DETAIL/SPECIFICATIONS FOR | | | FLASHING AT THE WALL INTERSECTION. SEC. R903.2 | | | FBC-RESIDENTIAL. | | | | | | E)ENGINEER TO SPECIFY ROOF PITCH. COORDINATE WITH TYPE | | | OF ROOFING MATERIAL. SEC. R903.4 FBC-RESIDENTIAL. | | | | | | 22)SHEET S104: ENGINEER TO PROVIDE SPECIFICATIONS FOR | | | WELDING AT THE BASE AND TOP PLATES OF STEEL COLUMNS. | | | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301 | | | FBC-RESIDENTIAL. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-10-25 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-10-25 |
Time |
18:07 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-10-24 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2022-10-25 18:07:49 | RESIDENTIAL(R3) ADDITION, ALTERATION SECOND BUILDING | | | REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT # 21041010 | | | 101 GREYMON DR | | | | | | NOTE: | | | CHANGE OF OCCUPANCY SEC. 605 AND SEC. 1001.2.1, SEC. | | | 604 AND SEC. 901.2, SEC. 801.3 FBC-EXISTING BUILDING. | | | ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND | | | METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE. | | | | | | NOTE: | | | LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING. | | | SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3 | | | FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, | | | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE | | | REQUIREMENTS OF THE FLORIDA BUILDING CODE. | | | | | | NOTE: | | | ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1 | | | FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, | | | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE | | | REQUIREMENTS OF THE FLORIDA BUILDING CODE. | | | | | | ORIGINAL COMMENT: | | | 1- THE PROPOSED ADDITION IS GOING TO BE BUILT IN A AE | | | FLOOD ZONE WITH A BASE FLOOD ELEVATION (BFE) OF 6 FEET | | | BASED ON NAVD 88. | | | THE PROPOSED ADDITION IS CONSIDERED A SUBSTANTIAL | | | IMPROVEMENT. THE ADDITION AND THE EXISTING HOUSE SHALL | | | HAVE THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR | | | ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET. | | | THEREFORE, THE MIN. REQUIRED FINISHED FLOOR ELEVATION | | | IS 8 FEET. | | | NOTE: PLANS NEED TO SHOW THE PROPOSED FINISHED FLOOR | | | ELEVATION USING NAVD 88. NEED TO PROVIDE THE | | | CONSTRUCTION DRAWINGS ELEVATION CERTIFICATE AND SURVEY | | | SHOWING THE FINISH FLOOR ELEVATIONS FOR REVIEW. | | | CITY ORDINANCE 4729-17. | | | SEC. 18-33 TECHNICAL AMENDMENTS TO FLORIDA BUILDING | | | CODE. | | | SEC. 107.3.5.3 CITY AMENDMENTS. | | | | | | RESPONSE: | | | PROPERTY APPRAISAL SUBMITTED WAS REVIEWED WITH ROBERT | | | BROWN (BUILDING OFFICIAL). THE COST TO REBUILD THE | | | HOUSE SEEMS TO BE TOO HIGH. | | | | | | ORIGINAL COMMENT: | | | 2-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106 | | | FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY | | | CONSERVATION. | | | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL | | | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID | | | CONFLICTS/DELAYS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 3- OK. 2 STORY ADDITION REMOVED FROM SCOPE OF WORK. | | | | | | ORIGINAL COMMENT: | | | 4- LOT DRAINAGE: PROPOSED WORK AFFECTS THE LOT DRAINAGE | | | (DRIVEWAY AND REAR PAVERS). PROVIDE DRAINAGE PLAN | | | SHOWING HOW THE SURFACE DRAINAGE IS KEPT WITHIN THE LOT | | | AND NOT DIVERTED TO ADJACENT PROPERTIES. PROVIDE | | | DRAINAGE PLAN SHOWING COMPLIANCE WITH THE FOLLOWING | | | SECTIONS: R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY | | | AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS. | | | NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED | | | GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM | | | ADJACENT PROPERTIES. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | ORIGINAL COMMENT: | | | 5- ARCHITECT OF RECORD NEEDS TO SPECIFY COMPLETE DESIGN | | | CRITERIA: | | | A)OK. DONE BY NEW ENGINEER. | | | | | | ORIGINAL COMMENT: | | | B)BUILDING EXPOSURE (NOTE: THIS BUILDING IS LOCATED IN | | | EXPOSURE "D". | | | | | | RESPONSE: | | | ENGINEER TO REVISE DESIGN CRITERIA ON SHEET S100. THIS | | | BUILDING IS LOCATED IN EXPOSURE "D" NOT "C". | | | | | | ORIGINAL COMMENT: | | | C)ULTIMATE AND NOMINAL WIND SPEEDS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED BY THE ENGINEER. | | | | | | ORIGINAL COMMENT: | | | D)COMPONENTS AND CLADDING DESIGN PRESSURES (DOORS AND | | | WINDOWS) | | | SEC. R301.2.1 FBC RESIDENTIAL. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED BY THE ENGINEER. | | | | | | NEW COMMENT: | | | E) ENGINEER TO REVISE DESIGN CRITERIA ON SHEET S100. | | | THIS BUILDING IS NOT "OPENED" ENCLOSURE CLASSIFICATION. | | | REVISE ALL INFORMATION AS REQUIRED. | | | | | | 6- OK. 2 STORY ADDITION REMOVED FROM SCOPE OF WORK. | | | | | | ORIGINAL COMMENT: | | | 7- WINDOW SCHEDULE ON SHEET A-4 SPECIFIES "CASWELL | | | WINDOWS". PROVIDE MANUFACTURER'S CUT SHEETS FOR | | | CASEMENT WINDOW "H" SHOWING COMPLIANCE WITH BEDROOM | | | WINDOW EGRESS CLEAR OPENINGS, INCLUDING CLEAR WIDTH | | | OPENING. | | | SEC. R310.2.1 FBC-RESIDENTIAL. | | | | | | RESPONSE: | | | NO INFORMATION SUBMITTED ON REVISED PLANS. PROVIDE | | | COMPLIANCE WITH EMERGENCY EGRESS REQUIREMENTS FOR | | | JUNIOR BEDROOM. CLEARLY SPECIFY TYPE AND SIZE OF | | | WINDOWS AND PROVIDE MANUFACTURER'S CUT SHEETS FOR | | | WINDOW TO BE USED AS EMERGENCY ESCAPE. | | | | | | 8-11- OK. 2 STORY ADDITION REMOVED FROM SCOPE OF WORK. | | | | | | ORIGINAL COMMENT: | | | 12-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. CONTRACTOR TO ADVISE IF SUBMITTING NOW OR | | | LATER AS A DEFERRED SUBMITTAL). | | | | | | A)EXTERIOR DOORS. INSWING AND OUTSWING DOORS AS SHOWN | | | ON PLANS. | | | | | | B)WINDOWS. ALL WINDOW TYPES AS SHOWN ON PLANS. | | | | | | C)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE | | | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION | | | SCHEDULE. SEE CITY SAMPLE. | | | | | | D)METAL ROOF. (IF ROOF IS TO BE REPLACED. PLANS ARE NOT | | | CLEAR ON THIS). | | | | | | E)ROOFING UNDERLAYMENT. (IF ROOF IS TO BE REPLACED. | | | PLANS ARE NOT CLEAR ON THIS). | | | | | | F)WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED: | | | CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY | | | COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. | | | | | | G)FRONT AND REAR PORCH PROPOSED ROOFING PANELS. SEE | | | SHEET S103. | | | | | | 13- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | ORIGINAL COMMENT: | | | 14- PROVIDE DOOR AND WINDOW STRUCTURAL BUCK DETAIL | | | SHOWING COMPLIANCE WITH SEC. R609.7.2.1 | | | FBC-RESIDENTIAL. | | | | | | RESPONSE. | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 15-18- OK. 2 STORY ADDITION REMOVED FROM SCOPE OF WORK. | | | | | | NEW COMMENTS BASED ON REVISED DRAWINGS AND SCOPE OF | | | WORK: | | | 19- BUILDING PLAN REVIEW NOTE ON SHEET A0.0 REFERS TO | | | THE CITY OF CORAL GABLES. REVISE AS REQUIRED. PROVIDE | | | CORRECT INFORMATION. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 20- PROPOSED PLAN ON SHEET S102: | | | A)FLOOR PLAN IS MISSING INFORMATION FOR THE REAR PORCH. | | | LOCATION, FOOTINGS, COLUMNS, ETC. SEC. 107.2.1 CITY | | | AMENDMENTS. SEC. R301.2.1 FBC-RESIDENTIAL. | | | | | | B)FLOOR PLAN IS MISSING INFORMATION FOR NEW FOOTINGS | | | AND COLUMNS INFORMATION SHOWN ON SHEETS S104 AND S105 | | | FOR GARAGE INFILL WALL. SEC. 107.2.1 CITY AMENDMENTS. | | | SEC. R301.2.1 FBC-RESIDENTIAL. | | | | | | C) CONSTRUCTION OF NEW BEAMS BETWEEN DINING ROOM AND | | | KITCHEN AREA IS NOT CLEAR. PROPOSED FLOOR PLAN ON SHEET | | | S102 SHOWS I BEAMS, WHILE INFORMATION ON SHEET S104 AND | | | S105 SHOW DIFFERENT CONSTRUCTION MATERIALS. CLARIFY/ | | | COORDINATE TO AVOID CONFLICTS DELAYS. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | NOTE: WOOD FRAME DETAIL ON SHEET S104 IS MISSING ALL | | | STRUCTURAL CONNECTORS. | | | | | | D)THIS IS A CHANGE OF USE FROM GARAGE TO LIVABLE SPACE. | | | TYPICALLY, GARAGES ARE BUILT WITHOUT A FLOOR VAPOR | | | BARRIER. ENGINEER OF RECORD TO PROVIDE SPECIFICATIONS | | | FOR THE CONCRETE SLAB VAPOR BARRIER AS REQUIRED BY SEC. | | | R506.2.3 FBC-RESIDENTIAL. | | | ALSO, ENGINEER OF RECORD DOESN'T PROVIDE ANY | | | INFORMATION OF HOW THE GARAGE SLAB IS RAISED TO THE | | | EXISTING HOUSE LEVEL AS SHOWN ON SHEET A2.2. PROVIDE | | | COMPLETE INFORMATION. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 21- SHEET S103: | | | A)ENGINEER TO SPECIFY TYPE OF ROOF PANEL AND | | | ATTACHMENT. (NOTE: PRODUCT APPROVAL WILL BE REQUIRED). | | | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.2.1 | | | FBC-RESIDENTIAL. | | | | | | B)SECTION 1: ENGINEER TO SPECIFY LENGTH OF #9 SCREWS. | | | HOW MUCH EMBEDMENT IS REQUIRED INTO THE 4X2 BATTEN?. | | | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.2.1 | | | FBC-RESIDENTIAL. | | | | | | C)SECTION 2: ENGINEER TO SPECIFY TYPE AND LENGTH OF | | | 1/2" SCREWS. HOW MUCH EMBEDMENT IS REQUIRED INTO THE | | | EXISTING CONCRETE WALL. SEC. 107.2.1 CITY AMENDMENTS. | | | SEC. R301.2.1 FBC-RESIDENTIAL. | | | | | | D)ENGINEER TO PROVIDE DETAIL/SPECIFICATIONS FOR | | | FLASHING AT THE WALL INTERSECTION. SEC. R903.2 | | | FBC-RESIDENTIAL. | | | | | | E)ENGINEER TO SPECIFY ROOF PITCH. COORDINATE WITH TYPE | | | OF ROOFING MATERIAL. SEC. R903.4 FBC-RESIDENTIAL. | | | | | | 22)SHEET S104: ENGINEER TO PROVIDE SPECIFICATIONS FOR | | | WELDING AT THE BASE AND TOP PLATES OF STELL COLUMNS. | | | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301 | | | FBC-RESIDENTIAL. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-06-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-06-29 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-06-29 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2021-06-29 13:15:19 | RESIDENTIAL(R3) ADDITION, BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | SECTION 606 FBC EXISTING BUILDING. CHAPTER 11 | | | FBC-EXISTING BUILDING. | | | PERMIT # 21041010 | | | | | | 1- THE PROPOSED ADDITION IS GOING TO BE BUILT IN A AE | | | FLOOD ZONE WITH A BASE FLOOD ELEVATION (BFE) OF 6 FEET | | | BASED ON NAVD 88. | | | THE PROPOSED ADDITION IS CONSIDERED A SUBSTANTIAL | | | IMPROVEMENT. THE ADDITION AND THE EXISTING HOUSE SHALL | | | HAVE THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR | | | ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET. | | | THEREFORE, THE MIN. REQUIRED FINISHED FLOOR ELEVATION | | | IS 8 FEET. | | | NOTE: PLANS NEED TO SHOW THE PROPOSED FINISHED FLOOR | | | ELEVATION USING NAVD 88. NEED TO PROVIDE THE | | | CONSTRUCTION DRAWINGS ELEVATION CERTIFICATE AND SURVEY | | | SHOWING THE FINISH FLOOR ELEVATIONS FOR REVIEW. | | | CITY ORDINANCE 4729-17. | | | SEC. 18-33 TECHNICAL AMENDMENTS TO FLORIDA BUILDING | | | CODE. | | | SEC. 107.3.5.3 CITY AMENDMENTS. | | | | | | DURING THE PERMITTING OF THIS STRUCTURE THREE DIFFERENT | | | FLOOD ELEVATION CERTIFICATES WILL BE REQUIRED: | | | A) CONSTRUCTION DRAWINGS. | | | B) BUILDING UNDER CONSTRUCTION. | | | C) FINISHED CONSTRUCTION. | | | | | | 2-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106 | | | FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY | | | CONSERVATION. | | | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL | | | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID | | | CONFLICTS/DELAYS. | | | | | | 3- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. 1101.1 | | | FBC-EXISTING BUILDING AND SEC. R401.4 FBC-RESIDENTIAL. | | | | | | 4- LOT DRAINAGE | | | PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE | | | FOLLOWING: | | | R401.3 FBC-RESIDENTIAL. | | | SEC. 107.2.5 CITY AMENDMENTS. | | | SEC. 110.9 CITY AMENDMENTS. | | | | | | 5- ARCHITECT OF RECORD NEEDS TO SPECIFY COMPLETE DESIGN | | | CRITERIA: | | | A)SPECIFY THE CURRENT CODE IN EFFECT, FBC-RESIDENTIAL | | | 7TH EDITION (2020). | | | B)BUILDING EXPOSURE (NOTE: THIS BUILDING IS LOCATED IN | | | EXPOSURE "D" | | | C)ULTIMATE AND NOMINAL WIND SPEEDS. | | | D)COMPONENTS AND CLADDING DESIGN PRESSURES. | | | SEC. R301.2.1 FBC RESIDENTIAL. | | | | | | 6- NOTE: SEPARATE FRAMING PLANS FROM THE PROPOSED FLOOR | | | PLANS. PROVIDE COMPLETE FRAMING PLANS, DETAILS AND | | | SPECIFICATIONS FOR: | | | A)SECOND FLOOR FRAMING PLAN (NOTE: CHECK FLOOR JOIST | | | SPAN AND JOIST SIZE). | | | B)ADDITION ROOF FRAMING PLAN. | | | C)EXISTING ROOF FRAMING PLAN MODIFICATIONS TO RECEIVE | | | PROPOSED ADDITION. | | | D) ALL EXTERIOR WALLS, INCLUDING WALL MEETING EXISTING | | | ROOF. | | | E)CUPOLA ROOF FRAMING PLAN AND WALL CONSTRUCTION. | | | F)ALL EXTERIOR DOORS AND WINDOWS FRAMING DETAILS. | | | SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. | | | G) SPECIFY AND SHOW ON FRAMING PLANS/DETAILS ALL BEAMS, | | | COLUMNS, GIRDERS, FLOOR AND ROOF STRUCTURAL JOISTS. | | | SPECIFY ROOF BOTTOM CHORD FRAMING MEMBERS (SEE 2 STORY | | | WALL SECTION). SPECIFY CONNECTORS AT EACH END OF EACH | | | FRAMING MEMBER. PROVIDE COMPLETE DETAILS/SPECIFICATIONS | | | FOR EACH BEAM AND COLUMN. | | | SEC. 107.2.5.3 CITY AMENDMENTS. | | | SEC. R301.1.1 FBC-RESIDENTIAL. | | | | | | 7- WINDOW SCHEDULE ON SHEET A-4 SPECIFIES "CASWELL | | | WINDOWS". PROVIDE MANUFACTURER'S CUT SHEETS FOR | | | CASEMENT WINDOW "H" SHOWING COMPLIANCE WITH BEDROOM | | | WINDOW EGRESS CLEAR OPENINGS, INCLUDING CLEAR WIDTH | | | OPENING. | | | SEC. R310.2.1 FBC-RESIDENTIAL. | | | | | | 8-TWO STORY WALL SECTION ON SHEET A-3: | | | A)THE PROPOSED ADDITION IS GOING TO BE SUPPORTED BY | | | EXISTING FIRST FLOOR WALL. WALL SECTION SHOWS AN | | | EXISTING FOUNDATION OF 12" WIDE BY 24" DEEP FOOTING. | | | THIS FOOTING TYPE AND SIZE IS NOT COMMON IN THIS AREA. | | | ARCHITECT OF RECORD TO SPECIFY IF THIS FOOTING SIZE WAS | | | FIELD VERIFIED. PROVIDE COMPLETE FOOTING SPECIFICATIONS | | | (INCLUDING FOOTING REINFORCEMENT) AND PROVIDE | | | CALCULATIONS SHOWING THAT IT'S ADEQUATE TO SUPPORT THE | | | PROPOSED SECOND STORY MASONRY ADDITION. (NOTE: | | | COORDINATE WITH SOIL TEST REPORT RECOMMENDATIONS AND | | | GENERAL CONSTRUCTION NOTE #3 ON SHEET A-1). | | | SEC. 107.2.1.2 CITY AMENDMENTS. | | | SEC. R301.1.1 FBC-RESIDENTIAL. | | | | | | B)SECOND FLOOR EXTERIOR WALL CONSTRUCTION IS NOT CLEAR. | | | WALL SECTION SHOWS WOOD FRAME CONSTRUCTION AND MASONRY | | | CONSTRUCTION. IT IS NOT CLEAR WHAT AREAS ARE MASONRY | | | AND WHAT AREAS ARE WOOD FRAME. REVISE PLANS AND WALL | | | SECTIONS AS REQUIRED. CHECK SIZES OF WOOD FRAMED | | | MEMBERS AND THICKNESS OF MASONRY WALL. HOW IS THE | | | MASONRY WALL CONNECTED TO THE BOTTOM WALL?. HOW ARE THE | | | ROOF WOOD FRAMING MEMBERS FASTENED TO THE WALL? HOW ARE | | | THE WALL WOOD FRAMING MEMBERS FASTENED TO THE MASONRY | | | WALL? HOW ARE THE FLOOR JOISTS CONNECTED TO THE WALL?. | | | SPECIFY LEDGER SIZE AND FASTENING. | | | SEC. 107.2.1.2 CITY AMENDMENTS. | | | SEC. R301.1.1 FBC-RESIDENTIAL. | | | | | | C) SPECIFY SIZE OF CONTINUOUS SOFFIT VENT. | | | SEC. R806.2 FBC-RESIDENTIAL. | | | | | | D)SPECIFY WALL INSULATION. | | | SEC. R103.2 FBC-ENERGY CONSERVATION. | | | | | | 9- TYPICALLY, SEC. R806.2 FBC-RESIDENTIAL REQUIRES | | | 1/150 NET FREE VENTILATION AREA. GENERAL CONSTRUCTION | | | NOTE ON SHEET A-1 SPECIFIES 1/300 NET FREE VENTILATION | | | AREA. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS | | | SHOWING COMPLIANCE WITH THE EXCEPTION OF SEC. R806.2 | | | FBC-RESIDENTIAL WHEN DESIGNING 1/300 NET VENTILATION | | | AREA. | | | NOTE: GENERAL CONSTRUCTION NOTE #28 SPECIFIES | | | CONTINUOUS RIDGE VENT. THERE IS NOT RIDGE ON PROPOSED | | | ROOF. SEE ROOF PLAN. | | | | | | 10- WOOD FRAMED WALLS: | | | A) NEED TO SPECIFY THE 7/8" MIN. STUCCO THICKNESS AS | | | REQUIRED BY TABLE R702.1(1) FBC-RESIDENTIAL | | | | | | B)NEED TO SPECIFY TWO WATER RESISTIVE BARRIERS WHEN | | | STUCCO IS APPLIED TO WOOD AS REQUIRED BY SEC. R703.7.3 | | | FBC-RESIDENTIAL. | | | | | | 11-SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC. R807.1 | | | FBC-RESIDENTIAL. | | | | | | 12-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL): | | | | | | A)EXTERIOR DOORS. | | | B)WINDOWS. | | | C)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE | | | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION | | | SCHEDULE. SEE CITY SAMPLE. | | | D)METAL ROOF. | | | E)ROOFING UNDERLAYMENT SPECIFIED ON TWO STORY WALL | | | SECTION. | | | F)ROOF VENTS SPECIFIED BY THE ARCHITECT. SEE PLANS. | | | G)RIDGE ROOF VENT SPECIFIED BY THE ARCHITECT. SEE | | | PLANS. | | | | | | 13- SHEET A-1: | | | A)REVISE/CLARIFY DESIGN LOADS SPECIFIED ON GENERAL | | | CONSTRUCTION NOTES # 20 AND #44. SPECIFIED LOADS DON'T | | | MATCH. | | | SEC. R301.1 FBC-RESIDENTIAL. | | | | | | B)REVISE USE GROUP SPECIFIED UNDER THE SETBACKS | | | HEADING. THIS IS A SINGLE FAMILY RESIDENCE. CORRECT USE | | | GROUP IS R3 NOT R2. | | | SEC. 310.5 FBC-BUILDING. | | | | | | 14- PROVIDE DOOR AND WINDOW STRUCTURAL BUCK DETAIL | | | SHOWING COMPLIANCE WITH SEC. R609.7.2.1 | | | FBC-RESIDENTIAL. | | | | | | 15- PROVIDE ROOF SHEATHING NAIL TYPE, SIZE AND SPACING | | | AS REQUIRED BY SEC. R803.2.3.1 FBC-RESIDENTIAL. | | | NOTE: GENERAL CONSTRUCTION NOTE # 21 ON SHEET A-1 | | | DOESN'T COMPLY. | | | | | | 16- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR | | | STAIRWAY CONSTRUCTION SHOWING COMPLIANCE WITH SEC. | | | R311.7 FBC-RESIDENTIAL. | | | | | | 17-SPECIFY CARBON MONOXIDE ALARM WITHIN ALL SLEEPING | | | ROOMS, INCLUDING EXISTING BEDROOMS AS REQUIRED BY SEC. | | | R315.1 FBC-RESIDENTIAL. | | | | | | 18- REVISE TOTAL PROPOSED AREA SPECIFIED BELOW THE | | | PROPOSED FIRST FLOOR PLAN. TOTAL AREA IS NOT 2,530. | | | SEC. 107.2.1 CITY AMENDMENTS. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-10-13 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-10-13 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-10-13 |
Time |
12:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-05-24 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2021-05-24 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2021-05-24 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2021-05-24 10:28:10 | CODES IN EFFECT | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | REVIEW STATUS: FAILED. SEE NEW COMMENTS BELOW | | | | | | 1) PLEASE PROVIDE A RISER DIAGRAM SHOWING SERVICE | | | CONDUCTORS, METER, PANELS, GROUNDING DETAILS. PLEASE | | | INDICATE SIZE OF CONDUCTORS, PANELS, | | | PANELS RATINGS, ETC. NEC 2017, FBC 107 | | | | | | 2) PLEASE PROVIDE LOAD CALCULATIONS FOR NEW SERVICE AND | | | PANELS NEC 2017 | | | | | | 3) PLEASE PROVIDE UPDATED PANELS SCHEDULES FBC 107 | | | | | | 4) PLEASE SPECIFY AIC RATINGS OF SERVICE AND PANELS NEC | | | 2017 | | | | | | 5) PLEASE SHOW LOCATION OF METER, DISCONNECTS, AND | | | PANELS FBC 20 | | | | | | 6) ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, | | | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN | | | KITCHENS, FAMILY ROOMS, | | | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, | | | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | | SHALL BE AFCI PROTECTED. | | | PROVIDE CORRECTION. NEC 210.12; FBC RE E3902.16 (A NOTE | | | WILL SUFFICE) | | | | | | 7) TAMPER-RESISTANT RECEPTACLES REQUIRED AS PER FBC RE | | | E4002.14, NEC 406.12 (A NOTE WILL SUFFICE) | | | | | | 8) PROVIDE COMPLIANCE: "NOT LESS THAN 90 PERCENT OF THE | | | LAMPS IN PERMANENTLY INSTALLED LUMINAIRES SHALL HAVE AN | | | EFFICACY OF AT LEAST 45 LUMENS-PER-WATT OR SHALL | | | UTILIZE | | | LAMPS WITH AN EFFICACY OF NOT LESS THAN 65 | | | LUMENS-PER-WATT?. A NOTE WILL SUFFICE. FBC EC R404.1 | | | | | | 9) PLEASE CLARIFY CIRCUIT VOLTAGES FOR WASHER AND | | | DRYER. DRAWING SEEMS TO INDICATE TWO 220 VOLTS | | | CIRCUITS. NORMALLY WASHER IS ONLY 120 VOLTS. PLEASE | | | SHOW CIRCUITS ON PANEL SCHEDULE. | | | | | | 10) PLEASE SHOW CIRCUIT FOR WATER HEATER AND SPECIFY | | | CONDUCTOR SIZE AND BREAKER SIZE. | | | | | | | | | SINCERELY, | | | | | | ENRIQUE QUINONEZ PE | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2023-02-16 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-16 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-16 |
Time |
08:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-05 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-10-05 10:51:15 | 1ST GAS REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FRC G2439.5 (614.6) MAKEUP AIR FOR DRYER. | | | PLEASE SHOW THE CALCULATION FOR THE REQUIREMENT OR | | | EXCEPTION TO THE NEED FOR MAKE-UP AIR FOR THE DRYER. | | | | | | 2. 2020 FRC G2415.17.1 (404.17.1) LIMITATIONS - PLASTIC | | | GAS LINE SHALL BE INSTALLED OUTDOORS UNDERGROUND ONLY. | | | IT SHALL NOT BE USED WITHIN OR UNDER ANY BUILDING. | | | PLEASE FIND ANOTHER MATERIAL TO GET INTO THE RANGE. | | | | | | 3. 2020 FRC G2415.14.1 (404.14.1) CONDUIT WITH ONE END | | | TERMINATING OUTDOORS - THE SLEEVE (CONDUIT) MUST | | | TERMINATE IN AN "OCCUPIABLE" PORTION OF THE BUILDING. | | | PLEASE CHOSE A LOCATION THAT IS "OCCUPIABLE". (INSIDE A | | | CABINET COULD BE CONSIDERED OCCUPIABLE) IT CANNOT | | | TERMINATE IN A CONCEALED LOCATION AND CANNOT BE LOCATED | | | BEHIND AN ACCESS PANEL. SHOW THE DETAILS THAT COMPLY | | | WITH ALL THE ASPECTS OF THE SLEEVE TERMINATION INDOORS | | | AND OUTDOORS, AND SEALING. THE SLEEVE WITH ONE END | | | INDOORS WOULD NOT BE SEALED ON THE EXTERIOR, BUT WOULD | | | BE DESIGNED TO PREVENT RODENTS FROM INTRUDING. | | | | | | 4. 2020 FRC G2413.3 (402.3) SIZING - ACCORDING TO THE | | | SIZE CHART YOU'VE REFERENCED, USING THE LONGEST RUN | | | METHOD, YOU WOULD NEED 1 1/4" BETWEEN THE METER AND | | | WATER HEATER. 3/4" BETWEEN THE METER AND BBQ, AND 3/4" | | | TO THE COOKTOP. YOU SHOULD LOOK AT THE PRESSURE DROP | | | (.3 IN W.C.) AND RECONSIDER. | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2021-05-24 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-05-24 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-05-24 |
Time |
15:20 |
Sent To |
|
|
| Notes |
| 2021-05-24 15:23:44 | GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN | | | THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN | | | PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS | | | WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE | | | RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT | | | REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER | | | THE WPB AMENDMENTS TO FBC SEC. 107.2.1. | | | | | | NOTE: YOU MAY CHOOSE TO HAVE A GAS REVIEW DONE THIS | | | TIME AND SUBMIT PLANS. THIS WILL HAVE THE GAS APPROVE | | | FOR A SUB PERMIT, OR IF YOU DECIDED NOT TO, PLEASE PUT | | | A NOTE ON THE ALL GAS EQUIPMENT UNDER A SEPARATE PERMIT | | | BY A LICENSED CONTRACTOR FOR THE GAS SYSTEM. AN N WILL | | | BE PUT ON THIS REVIEW, WHICH STANDS FOR NOT REQUIRED | | | BUT, A SUB PERMIT WON'T BE ISSUED UNIT A REVIEW IS DONE | | | FOR THAT SUB PERMIT, SO PLEASE BE ADVISED ON THIS | | | PROCEDURE. | | | | | | A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR | | | FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC | | | SEC. 105.1. | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-03-20 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-03-20 |
Time |
23:39 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-03-20 |
Time |
23:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-11-03 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-11-03 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-11-03 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2022-11-03 15:20:25 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | PLEASE INDICATE ON ELEVATIONS OR WINDOW/DOOR SCHEDULE | | | THAT ALL WINDOWS WILL FEATURE CLEAR GLASS, AND INDICATE | | | WHETHER LOW-E COATING WILL BE APPLIED (POSSIBLE ON NON | | | STREET FACING ELEVATIONS ONLY) | | | | | | PLEASE ALSO INDICATE THAT ANY MUNTINS WILL BE | | | EXTERNALLY APPLIED WITH EITHER A PYRAMID OR OGEE | | | PROFILE. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-05-28 |
|
|
Cont ID |
|
| Sent By |
aborngra |
Date |
2021-05-28 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
aborngra |
Date |
2021-05-28 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2021-05-28 15:03:30 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S): | | | 1. THE PROPOSED WORK REQUIRES HISTORIC PRESERVATION | | | BOARD APPROVAL. A CERTIFICATE OF APPROPRIATENESS | | | APPLICATION WILL NEED TO BE SUBMITTED IN PAPER AND | | | ELECTRONICALLY. APPLICATION IS AVAILABLE ON CITY | | | WEBSITE OR EMAIL STAFF TO REQUEST APPLICATION. | | | 2. PLEASE REACH OUT TO FRIEDERIKE MITTNER, CITY | | | HISTORIC PRESERVATION PLANNER TO DISCUSS THE PROPOSED | | | WORK BEFORE SUBMITTING TO THE HISTORIC PRESERVATION | | | BOARD. FRIEDERIKE WILL RETURN ON JUNE 10TH. | | | P: 561.822.1457 | E: [email protected] | | | | | | AARON BORNGRABER, AICP | | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | | PLANNING DIVISION | | | [email protected] | OFFICE: 561.822.1428 | TTY: | | | 800.955.8771 | | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | | FL 33402 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-03-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-03-21 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-02-15 |
Time |
15:44 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-11-17 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-11-17 |
Time |
15:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-11-07 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-11-07 |
Time |
07:30 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-10-02 |
Time |
08:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-06-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-06-29 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-05-10 |
Time |
11:20 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2023-03-08 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-03-08 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-03-06 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2023-03-08 11:24:17 | RECEIPT MU-2023-009913 - NO FEES DUE. LEM | | 2023-03-06 16:55:25 | 3/6/23 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2022-10-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-10-24 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-10-24 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2022-10-24 13:25:03 | IMPACT FEES | | | | | | PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR | | | IMPACT FEE ASSESSMENT. | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2021-06-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-06-29 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-06-29 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2021-06-29 13:16:39 | IMPACT FEES | | | | | | PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR | | | IMPACT FEE ASSESSMENT. | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2023-02-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-20 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-20 |
Time |
11:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-10-04 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-10-04 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-10-04 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2022-10-04 10:28:24 | 2ND REVIEW FMC | | | PERMIT: 21041010 | | | | | | CODES IN EFFECT: 2020 | | | | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SUBMITTED MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS CALL FOR A 3.3-TON SYSTEM. SHEET M-1 SHOWS | | | THIS MECHANICAL SYSTEM IS FOR THE ENTIRE HOME. SHEET | | | M-0 INDICATE THE AHU IS A 5-TON SYSTEM. PLEASE SHOW | | | THAT THE NEW SYSTEM MEETS THE 1.15 TIMES MAX LIMIT | | | REQUIRED IN THE FLORIDA ENERGY CODE. FEC R403.7.1.2; | | | FRC M1401.3 | | | | | | 2) SHEET M-1 INDICATES THAT THE DRYER EXHAUST WILL | | | TERMINATE ON THE ROOF. SHEET M-2 PITCHED ROOF CAP | | | DETAIL INDICATES AN INSECT SCREEN IN THE EXHAUST | | | TERMINATION. PLEASE REMOVE THE SCREEN FROM THIS DETAIL | | | OR ADD A NOTE THAT THE DRYER EXHAUST WILL NOT HAVE A | | | SCREEN AT THE DUCT TERMINATION. FRC M1502.3 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-05-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-24 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-24 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2021-05-24 13:34:05 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21041010 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE NEW | | | ADDITION. FBC EC 101.5.1.1.2 | | | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FBC EC R403.7.1 | | | | | | 3) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE | | | DUCTWORK INCLUDING SIZES AND CFM?S AT EACH REGISTER. | | | FBC 107.2.1 | | | | | | 4) PLEASE SHOW THE AHU?S ON THE MECHANICAL DRAWING. FBC | | | 107.2.1 | | | | | | 5) PLEASE PROVIDE ANCHORAGE DETAILS OF THE NEW AND | | | MOVED CONDENSING UNITS. FBC RES M1307.2 | | | | | | 6) PLEASE SHOW THE CONDENSATE PIPING AND TERMINATION | | | LOCATION. FBC RES M1411.3 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
N |
Date |
2023-03-01 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-03-01 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-03-01 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2023-03-01 14:38:03 | 11/17/22 MARK DONNELLY EMAILED REVISED SCOPE OF WORK | | | AND APPRAISAL. IT WAS REVIEWED BY ROBERT BROWN AND IT | | | WAS APPROVED. THEREFORE, PROPOSED ALTERATION IS NOT | | | CONSIDERED A SUBSTANTIAL IMPROVEMENT. NO NEED TO RAISE | | | THE HOUSE. JG. |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
F |
Date |
2022-10-25 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-10-25 |
Time |
18:04 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-10-24 |
Time |
17:51 |
Sent To |
|
|
| Notes |
| 2022-10-25 18:04:18 | ORIGINAL COMMENT: | | | 1- THE PROPOSED ADDITION IS GOING TO BE BUILT IN A AE | | | FLOOD ZONE WITH A BASE FLOOD ELEVATION (BFE) OF 6 FEET | | | BASED ON NAVD 88. | | | THE PROPOSED ADDITION IS CONSIDERED A SUBSTANTIAL | | | IMPROVEMENT. THE ADDITION AND THE EXISTING HOUSE SHALL | | | HAVE THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR | | | ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET. | | | THEREFORE, THE MIN. REQUIRED FINISHED FLOOR ELEVATION | | | IS 8 FEET. | | | CITY ORDINANCE 4729-17. | | | SEC. 18-33 TECHNICAL AMENDMENTS TO FLORIDA BUILDING | | | CODE. | | | SEC. 107.3.5.3 CITY AMENDMENTS. | | | | | | NOTE: | | | DURING THE PERMITTING OF THIS STRUCTURE THREE DIFFERENT | | | FLOOD ELEVATION CERTIFICATES WILL BE REQUIRED: | | | A) CONSTRUCTION DRAWINGS. | | | B) BUILDING UNDER CONSTRUCTION. | | | C) FINISHED CONSTRUCTION. | | | | | | RESPONSE: | | | PROPERTY APPRAISAL SUBMITTED WAS DISCUSSED WITH ROBERT | | | BROWN (BUILDING OFFICIAL). THE COST OF $550.00 PER | | | SQUARE FOOT DECLARED IN THE REPORT TO REBUILD THE HOUSE | | | SEEMS TO BE TOO HIGH. THIS VALUE DOESN'T REFLECT A | | | REALISTIC COST PER SQUARE FOOT VALUE FOR "AVERAGE" | | | CONSTRUCTION QUALITY AS STATED ON APPRAISAL REPORT AND | | | AS SHOWN ON PICTURES SUBMITTED. THIS REPORT IS NOT | | | ACCEPTABLE FOR BUILDING DEPARTMENT TO VERIFY VALUE OF | | | EXISTING STRUCTURE AND TO DETERMINE IF SUBSTANTIAL | | | IMPROVEMENT IS TRIGGERED. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2021-06-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-06-28 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-06-28 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2021-06-28 14:09:34 | 1- THE PROPOSED ADDITION IS GOING TO BE BUILT IN A AE | | | FLOOD ZONE WITH A BASE FLOOD ELEVATION (BFE) OF 6 FEET | | | BASED ON NAVD 88. | | | THE PROPOSED ADDITION IS CONSIDERED A SUBSTANTIAL | | | IMPROVEMENT. THE ADDITION AND THE EXISTING HOUSE SHALL | | | HAVE THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR | | | ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET. | | | THEREFORE, THE MIN. REQUIRED FINISHED FLOOR ELEVATION | | | IS 8 FEET. | | | CITY ORDINANCE 4729-17. | | | SEC. 18-33 TECHNICAL AMENDMENTS TO FLORIDA BUILDING | | | CODE. | | | SEC. 107.3.5.3 CITY AMENDMENTS. | | | | | | NOTE: | | | DURING THE PERMITTING OF THIS STRUCTURE THREE DIFFERENT | | | FLOOD ELEVATION CERTIFICATES WILL BE REQUIRED: | | | A) CONSTRUCTION DRAWINGS. | | | B) BUILDING UNDER CONSTRUCTION. | | | C) FINISHED CONSTRUCTION. | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2023-02-16 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-16 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-16 |
Time |
08:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-10-06 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-10-06 |
Time |
07:40 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-05-24 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-05-24 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-05-24 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2021-05-24 16:08:55 | 05/24/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. PLEASE IDENTIFY THE RANGE, WATER HEATER, AND DRYER | | | AS IF THEY ARE GAS OR ELECTRIC PER THE WPB AMENDMENTS | | | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | | | | 2. A SUB GAS PERMIT IS REQUIRED BY A LICENSED | | | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS | | | TO THE FBC SEC. 105.1. | | | | | | 3. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM | | | FOR THE NEW FIXTURE AND TIE-IN LOCATION PER THE WPB | | | AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL | | | PLUMBING. | | | | | | 4. SIGNED AND SEALED DRAWINGS NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - | | | IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL | | | SIGNATURE - PLEASE DROP OFF AT CITY HALL THE ORIGINAL | | | SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN REVIEW | | | REQUEST FORM" EXPLAINING THE REASON FOR SUBMITTING THE | | | DOCUMENT OR DRAWINGS. THE PLAN REVIEW REQUEST FORM CAN | | | BE OBTAINED BY EMAILING [email protected] AND ASKING FOR THE | | | FORM. | | | | | | 5. ON THE SHEET, ME-1 SHOWS A FLOOR DRAIN. PLEASE | | | PROVIDE TRAP SEAL PROTECTION IN ACCORDANCE WITH 2020 | | | FBC SEC. RESIDENTIAL 3201.2.1.1 POTABLE WATER-SUPPLIED | | | TRAP SEAL PRIMER VALVE. | | | | | | 6. PLEASE SUPPLY MANUFACTURERS' SPECIFICATIONS FOR THE | | | WATER HEATER PER THE WPB AMENDMENTS TO THE FBC | | | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2023-03-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-03-02 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-03-02 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2023-03-02 13:39:51 | NO ROOFING WORK. JG. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2022-10-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-10-24 |
Time |
17:45 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-10-24 |
Time |
17:44 |
Sent To |
|
|
| Notes |
| 2022-10-24 17:48:20 | ROOFING REVIEW | | | | | | ORIGINAL COMMENT: | | | 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. CONTRACTOR TO ADVISE IF SUBMITTING NOW OR | | | LATER AS A DEFERRED SUBMITTAL). | | | | | | A) METAL ROOF. (IF ROOF IS TO BE REPLACED. PLANS ARE | | | NOT CLEAR ON THIS). | | | | | | B)ROOFING UNDERLAYMENT. (IF ROOF IS TO BE REPLACED. | | | PLANS ARE NOT CLEAR ON THIS). | | | | | | C) FRONT AND REAR PORCH PROPOSED ROOFING PANELS. SEE | | | SHEET S103. | | | | | | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-06-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-06-29 |
Time |
13:18 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-06-29 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2021-06-29 13:19:17 | 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL): | | | | | | A)METAL ROOF. | | | B)ROOFING UNDERLAYMENT SPECIFIED ON TWO STORY WALL | | | SECTION. | | | C)ROOF VENTS SPECIFIED BY THE ARCHITECT. SEE PLANS. | | | D)RIDGE ROOF VENT SPECIFIED BY THE ARCHITECT. SEE PLANS | | | | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-03-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-03-02 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-03-02 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2023-02-20 11:45:27 | MECHANICALL DIGITAL SIGNATURES APPROVED ME | | 2023-02-15 15:45:06 | COMBINED DIGITALLY SIGNED ARCH SHEETS IN "SIGNATURES" | | | FOLDER |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-10-13 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-10-13 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-10-13 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2022-10-13 13:38:40 | SIGNATURE REVIEW FAILED | | | | | | SHEETS 000- 014 DO NOT HAVE THE REQUIRED DIGITAL | | | SIGNATURE AS REQUIRED. PLEASE CORRECT AS OUTLINED | | | BELOW. | | | | | | FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF | | | RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | DIGITALLY SEALED AND SIGNED. | | | | | | PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS | | | FOLLOWING PROJECTDOX INSTRUCTIONS | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-06-29 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2021-06-29 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2021-06-29 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2021-06-29 13:39:45 | SIGNATURE REVIEW: | | | | | | ARCHITECTURAL AND STRUCTURAL DRAWINGS SUBMITTED DON'T | | | HAVE A DIGITAL SIGNATURE. PLANS SUBMITTED HAVE A COPY | | | OF THE ARCHITECT'S SEAL AND SIGNATURE. PLANS NEED TO | | | HAVE ARCHITECT'S ORIGINAL SEAL AND SIGNATURE WHEN | | | SUBMITTING DOCUMENTS FOR PUBLIC RECORDS AS REQUIRED BY | | | 61G1-16.003 FAC. | | | PLANS WERE SUBMITTED ELECTRONICALLY. ARCHITECT TO | | | PROVIDE PLANS WITH DIGITAL SIGNATURE OR PROVIDE HARD | | | COPY PLANS WITH THE ORIGINAL SEAL AND SIGNATURE. | | | | | | ARCHITECTS | | | 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND | | | SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2023-03-20 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-03-20 |
Time |
23:39 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-03-20 |
Time |
23:39 |
Sent To |
|
|
| Notes |
| 2023-03-20 23:39:42 | **VALUE OF CONSTRUCTION NO LONGER EXCEEDS 50% OF | | | IMPROVEMENT VALUE, THEREFORE, LANDSCAPE PERMIT IS NOT | | | REQUIRED** |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-11-03 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-11-03 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-11-03 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2022-11-03 15:16:50 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | THE VALUE OF CONSTRUCTION EXCEEDS 50% OF THE | | | IMPROVEMENT VALUE OF THE STRUCTURE, THEREFORE A | | | SEPERATE LANDSCAPE PERMIT IS REQUIRED AND MUST BE | | | SUBMITTED FOR ZONING APPROVAL TO MOVE FORWARD | | | | | | SEC 94-441 (B) | | | | | | NEW DRIVEWAY, SITE WALLS, PATIO, NOT UNDER SCOPE OF | | | THIS PERMIT. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-05-28 |
|
|
Cont ID |
|
| Sent By |
kalexand |
Date |
2021-05-28 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
aborngra |
Date |
2021-05-28 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2021-05-28 15:03:43 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S): | | | 1. THE PROPOSED WORK REQUIRES HISTORIC PRESERVATION | | | BOARD APPROVAL. A CERTIFICATE OF APPROPRIATENESS | | | APPLICATION WILL NEED TO BE SUBMITTED IN PAPER AND | | | ELECTRONICALLY. APPLICATION IS AVAILABLE ON CITY | | | WEBSITE OR EMAIL STAFF TO REQUEST APPLICATION. | | | 2. PLEASE REACH OUT TO FRIEDERIKE MITTNER, CITY | | | HISTORIC PRESERVATION PLANNER TO DISCUSS THE PROPOSED | | | WORK BEFORE SUBMITTING TO THE HISTORIC PRESERVATION | | | BOARD. FRIEDERIKE WILL RETURN ON JUNE 10TH. | | | P: 561.822.1457 | E: [email protected] | | | | | | AARON BORNGRABER, AICP | | | HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES | | | PLANNING DIVISION | | | [email protected] | OFFICE: 561.822.1428 | TTY: | | | 800.955.8771 | | | 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH, | | | FL 33402 | | | |
|
|