| 2021-04-23 10:57:14 | 04/23/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A LICENSED CONTRACTOR MUST REQUIRE A BUILDING PERMIT |
| | FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 105.1. |
| | |
| | 2. PLEASE PROVIDE A WATER PLUMBING RISER DIAGRAM PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) |
| | RESIDENTIAL PLUMBING. |
| | |
| | 3. PLEASE PROVIDE A HAND DRAWING FOR THE SCOPE OF WORK |
| | SHOWING THE WORK AREA LOCATIONS WITH A DESCRIPTION OF |
| | WHAT IS BEING REPLACED PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. A THERMAL EXPANSION DEVICE MAY BE REQUIRED IF ONE |
| | NOT PRESENT PER THE 2020 FBC R 2903.4. |
| | |
| | 5. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION, |
| | DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT |
| | SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO |
| | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 6. WHERE OR IF THE FLOOR WILL BE CUT TO ACCOMMODATE |
| | PIPING, PLEASE PROVIDE DETAIL FOR THE REPAIR OF THE |
| | CONCRETE. SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. SHOW |
| | THE WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE |
| | CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE. |
| | SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM |
| | EMBEDMENT DEPTH INTO THE EXISTING SLAB, AND THE SPACING |
| | OF THE DOWELS IN THE CENTER. THE REPAIR SHALL ALSO |
| | INCLUDE TERMITE TREATMENT OF THE SOIL AND THE REQUIRED |
| | VAPOR BARRIER OVER THE SOIL. A COPY OF THE TERMITE |
| | CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |