Plan Review Details - Permit 21040896
Plan Review Stops For Permit 21040896
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-05-18 Cont ID  
Sent By rmcphers Date 2021-05-18 Time 14:55 Rev Time 0.00
Received By rmcphers Date 2021-05-18 Time 14:55 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-05-03 Cont ID  
Sent By rmcphers Date 2021-05-03 Time 15:47 Rev Time 0.00
Received By rmcphers Date 2021-05-03 Time 15:47 Sent To  
Notes
2021-05-03 15:48:14PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-05-19 Cont ID  
Sent By rmcphers Date 2021-05-19 Time 12:46 Rev Time 0.00
Received By rmcphers Date 2021-05-19 Time 12:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-05-18 Cont ID  
Sent By rmcphers Date 2021-05-18 Time 14:49 Rev Time 0.00
Received By rmcphers Date 2021-05-18 Time 14:49 Sent To  
Notes
2021-05-18 14:54:58CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE SHOWER AREA WALL FINISH TO COMPLY
 WITH FBC 1210.2.3 (WHAT IS THE SHOWER AREA WALL FINISH
 - TILE?)
 2) DRAWING A2 DOES NOT STATE THAT THE FLOORING IS BEING
 REPLACED - DRAWING A1 DEMO PLAN DOES SHOW FLOORING TO
 BE REPLACED - TO REPLACE THE FLOORING WE WILL NEED THE
 FOLLOWING DOCUMENTS -
 THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 PLEASE EMAIL ME THE PROPOSED TEST REPORTS TO VERIFY
 BEFORE RESUBMITTING TO PROJECTDOX ( [email protected]
 )
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-03 Cont ID  
Sent By rmcphers Date 2021-05-03 Time 15:46 Rev Time 0.00
Received By rmcphers Date 2021-05-03 Time 15:27 Sent To  
Notes
2021-05-03 15:47:35CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE SHOWER AREA WALL FINISH TO COMPLY
 WITH FBC 1210.2.3

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-04-29 Cont ID  
Sent By equinone Date 2021-04-29 Time 09:40 Rev Time 0.00
Received By equinone Date 2021-04-29 Time 09:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-05-20 Cont ID  
Sent By pleduc Date 2021-05-20 Time   Rev Time 0.00
Received By pleduc Date 2021-05-20 Time 09:38 Sent To  
Notes
2021-05-20 09:45:29FIRE PROVISO:
  
 FIRE SPRINKLERS AND FIRE ALARM EQUIPMENT SHALL BE
 PROTECTED FROM PAINTING OR DAMAGE.
  
 THE FIRE SPRINKLER/FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO AND RECONSTRUCTION.
  
 ANY WORK INVOLVING FIRE SPRINKLERS/FIRE ALARM SYSTEMS
 OR EQUIPMENT SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-20 Cont ID  
Sent By rmcphers Date 2021-05-20 Time 12:08 Rev Time 0.00
Received By lmarchan Date 2021-05-04 Time 16:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-03 Cont ID  
Sent By rmcphers Date 2021-05-03 Time 15:48 Rev Time 0.00
Received By rmcphers Date 2021-04-16 Time 11:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-05-13 Cont ID  
Sent By ccole Date 2021-05-13 Time 12:40 Rev Time 0.00
Received By ccole Date 2021-05-13 Time 12:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-27 Cont ID  
Sent By ccole Date 2021-04-27 Time 15:25 Rev Time 0.00
Received By ccole Date 2021-04-27 Time 14:28 Sent To  
Notes
2021-04-27 15:26:201ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21040896
 4/27/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SHOWER PAN INSTALLATION DETAIL- SECTION
 421.5.2 FBC P.
  
 2) PROVIDE SHOWER VALVE AND BATHTUB FAUCET
 SPECIFICATIONS- SECTIONS 412.3 & 412.5 FBC P.
  
 3) ADVISORIES:
 A) REFER TO SECTION 1002.1: THE HORIZONTAL DISTANCES
 FROM THE CENTERLINES OF THE NEW SHOWER AND BATHTUB
 DRAIN OUTLETS TO THE CENTERLINES OF THE INLETS OF THE
 EXISTING TRAPS SHALL NOT EXCEED 30". PLEASE PLACE A
 NOTE ON THE PLAN INDICATING COMPLIANCE.
 B) RELOCATING DRAIN OUTLETS WILL REQUIRE THE FLOOR TO
 BE X-RAYED TO IN ORDER TO LOCATE REINFORCING STEEL OR
 POST STRESSED FLOOR TENDONS. PLEASE PLACE A NOTE ON THE
 PLANS TO VERIFY COMPLIANCE WILL BE MET- SECTION 107.2.1
 WPB.
 C) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE
 AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1
 FBC P AND SECTION 714.4.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-04-16 Cont ID  
Sent By equinone Date 2021-04-16 Time 13:14 Rev Time 0.00
Received By equinone Date 2021-04-16 Time 13:14 Sent To  
Notes
2021-04-16 13:14:40SEALED AND SIGNED PAPER ORIGINALS ROUTED TO INCOMING.
 EQ