Plan Review Details - Permit 21040895
Plan Review Stops For Permit 21040895
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-04-30 Cont ID  
Sent By cpuell Date 2021-04-30 Time 08:40 Rev Time 0.00
Received By cpuell Date 2021-04-30 Time 08:40 Sent To  
Notes
2021-04-30 08:41:52ALL BUILDINGS ON PROPERTY TO BE REROOFED (7 BLDGS) ALL
 HAVE 510 43RD ST AS ADDRESS.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-04-16 Cont ID  
Sent By cpuell Date 2021-04-16 Time 10:41 Rev Time 0.00
Received By cpuell Date 2021-04-16 Time 10:41 Sent To  
Notes
2021-04-16 10:42:55MULTIPLE BUILDING ON PARCEL, PLEASE SPECIFY WHICH
 BUILDINGS WILL BE RERROFED. A SITE PLAN OR AERIAL PHOTO
 SHOWING WHICH BUILDINGS WOULD BE VERY HELPFUL, PLEASE
 EMAIL [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-07-07 Cont ID  
Sent By jbrooks Date 2021-07-07 Time 13:08 Rev Time 0.00
Received By jbrooks Date 2021-07-07 Time 07:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-27 Cont ID  
Sent By jbrooks Date 2021-04-27 Time 10:33 Rev Time 0.00
Received By jbrooks Date 2021-04-27 Time 07:30 Sent To  
Notes
2021-04-27 10:34:22JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY, THURSDAY & FRIDAY 7:00 AM TO 3:00
 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. PROVIDE THE FOLLOWING INFORMATION FOR MIAMI-DADE NOA
 NO.: 20-0723.29 FOR THE PROPOSED FLAT ROOF SYSTEM TO BE
 USED CORRESPONDING TO ENGINEERS CALCULATIONS. COVER
 PAGE, EVALUATION REPORTS, LIMITATIONS PAGE AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL25621.02-R2 IS NOT RATED FOR USE IN ZONE 1,
 2 OR 3 FOR STRUCTURES LOCATED IN EXPOSURE D, WITH FLAT
 ROOF LESS THAN 7 DEGREES, HIP ROOF WITH MAX SLOPE OF
 12:12 OR GABLE ROOF WITH SLOPE BETWEEN 4.4:12 & 12:12
 12:12 WITH A MEAN ROOF HEIGHT 30 FEET OR LESS WIND
 SPEED 170 MPH. PROVIDE SIGNED AND SEALED ENGINEERING
 FOR USE OR SELECT A SYSTEM THAT MEETS THE ABOVE
 CRITERIA.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-07-07 Cont ID  
Sent By jbrooks Date 2021-07-07 Time 13:08 Rev Time 0.00
Received By jbrooks Date 2021-07-02 Time 15:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-27 Cont ID  
Sent By jbrooks Date 2021-04-27 Time 10:35 Rev Time 0.00
Received By jbrooks Date 2021-04-26 Time 14:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-29 Cont ID  
Sent By jgomez Date 2021-04-29 Time 09:57 Rev Time 0.00
Received By jgomez Date 2021-04-29 Time 09:56 Sent To  
Notes
2021-04-29 10:00:23ENGINEERING CALCULATIONS WITH ENGINEER'S EMBOSSED SEAL
 AND ORIGINAL SIGNATURE MATCH ONE UPLOADED TO PROJECTDOX
 ON 04/26/21. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-27 Cont ID  
Sent By jbrooks Date 2021-04-27 Time 10:34 Rev Time 0.00
Received By jbrooks Date 2021-04-27 Time 10:34 Sent To  
Notes
2021-04-27 10:35:40JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY, THURSDAY & FRIDAY 7:00 AM TO 3:00
 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL ONE ORIGINAL SIGNED AND SEALED
 PAPER ORIGINAL WITH A WET SIGNATURE TO:
 PETER VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6673.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved