Plan Review Details - Permit 21040876
Plan Review Stops For Permit 21040876
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-04-19 Cont ID  
Sent By cpuell Date 2021-04-19 Time 10:42 Rev Time 0.00
Received By cpuell Date 2021-04-19 Time 10:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-12-21 Cont ID  
Sent By jgomez Date 2021-12-21 Time 15:32 Rev Time 0.00
Received By jgomez Date 2021-12-21 Time 13:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-11-02 Cont ID  
Sent By jgomez Date 2021-11-02 Time 17:00 Rev Time 0.00
Received By jgomez Date 2021-11-02 Time 14:23 Sent To  
Notes
2021-11-02 17:02:23RESIDENTIAL (R3) ADDITION, THIRD BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21040876
  
 ORIGINAL COMMENT:
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106
 FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY
 CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. REVISED FORM WAS NOT
 SUBMITTED.
  
 B)THERE ARE TWO DIFFERENT ENERGY CALCULATIONS
 SUBMITTED. ONE IS FORM 405-2020 PREPARED BY M. ABBOTT
 AND FORM R402-2020 PREPARED BY THE ARCHITECT.
 INFORMATION ON FORM R402-2020 DOESN'T MEET THE MINIMUM
 PRESCRIPTIVE REQUIREMENTS FOR THE GLAZED FENESTRATION
 (SHGC) AND THE A/C UNIT CAN NOT BE INSTALLED IN THE
 ATTIC. THIS FORM CAN NOT BE USED. PLEASE REMOVE THIS
 FORM.
 USE FORM R405-2020 AND MAKE SURE IS SIGNED BY THE OWNER
 OR ARCHITECT TO AVOID CONFLICTS/DELAYS.
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. REVISED FORM WAS NOT
 SUBMITTED.
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME, JURISDICTION NUMBER (THIS
 IS JURISDICTION #604700). SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. REVISED FORM WAS NOT
 SUBMITTED.
  
 D)
 E)
  
 E)DOOR INFORMATION SHOWS A 1FT X 5FT DOOR ON THE SOUTH
 SIDE. PLANS DON'T SHOW THIS DOOR. WHERE IS THIS DOOR
 LOCATED AT?. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. REVISED FORM WAS NOT
 SUBMITTED.
  
 F)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. REVISED FORM WAS NOT
 SUBMITTED.
  
 NOTE:
 WHEN RESUBMITTING, PLEASE SEPARATE THE ENERGY
 CALCULATIONS FROM THE A/C LOAD CALCULATIONS AND ANY
 OTHER A/C RELATED INFORMATION. A/C PLAN TO BE SUBMITTED
 UNDER THE DRAWINGS FOLDER.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 TO AVOID MORE DELAYS, PLEASE FEEL FREE TO CONTACT ME IF
 YOU HAVE ANY QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-12 Cont ID  
Sent By jgomez Date 2021-08-12 Time 18:17 Rev Time 0.00
Received By jgomez Date 2021-08-12 Time 15:01 Sent To  
Notes
2021-08-12 18:19:17RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21040876
  
 ORIGINAL COMMENT:
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106
 FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY
 CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION.
  
 B)THERE ARE TWO DIFFERENT ENERGY CALCULATIONS
 SUBMITTED. ONE IS FORM 405-2020 PREPARED BY M. ABBOTT
 AND FORM R402-2020 PREPARED BY THE ARCHITECT.
 INFORMATION ON FORM R402-2020 DOESN'T MEET THE MINIMUM
 PRESCRIPTIVE REQUIREMENTS FOR THE GLAZED FENESTRATION
 (SHGC) AND THE A/C UNIT CAN NOT BE INSTALLED IN THE
 ATTIC. THIS FORM CAN NOT BE USED. PLEASE REMOVE THIS
 FORM.
 USE FORM R405-2020 AND MAKE SURE IS SIGNED BY THE OWNER
 OR ARCHITECT TO AVOID CONFLICTS/DELAYS.
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME, JURISDICTION NUMBER (THIS
 IS JURISDICTION #604700). SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 D)PROVIDE CORRECT INFORMATION FOR ITEM #2. THE QUESTION
 ON THIS ITEM IS SINGLE FAMILY OR MULTIPLE FAMILY?.
 "DETACHED IS NOT THE ANSWER. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) COORDINATE ATTIC INSULATION AND ATTIC VENTILATION
 WITH ARCHITECT'S PLANS. THESE ITEMS WILL NEED TO BE
 REVISED BY THE ARCHITECT. SEE ITEMS #2(B) AND #7(D)
 BELOW.
  
 E)DOOR INFORMATION SHOWS A 1FT X 5FT DOOR ON THE SOUTH
 SIDE. PLANS DON'T SHOW THIS DOOR. WHERE IS THIS DOOR
 LOCATED AT?. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
  
 ORIGINAL COMMENT:
 2- PROVIDE COMPLETE ROOF FRAMING PLAN FOR THE ADDITION.
 CLEARLY SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.
 ALSO, CLEARLY SPECIFY CONNECTION TO EXISTING.
 SEC. R301.2.1 FBC-RESIDENTIAL.
 NOTE: TYPICAL WALL SECTION ON SHEET A-3 SPECIFIES ROOF
 TRUSSES. IT IS NOT CLEAR HOW TRUSSES ARE BUILT IF ONLY
 TOP CHORD IS SHOWN. COORDINATE WITH ITEM #6 BELOW.
 REVISE/CLARIFY.
  
 RESPONSE:
 FRAMING OF THE NEW ROOF CORNERS IS NOT CLEAR. ROOF
 FRAMING PLAN ON SHEET S-1 SHOW THE STRUCTURAL ROOF
 FRAMING MEMBERS BEING SPACED MORE THAN 24" O.C. AND IT
 LOOKS LIKE THE CORNER IS NOT PROPERLY FRAMED TO SUPPORT
 THE REQUIRED LOADS, SPECIALLY AT THE CANTILEVERED ROOF
 AREA ON THE NORTH CORNER OF THE ROOF. PROVIDE COMPLETE
 FRAMING DETAIL/SPECIFICATIONS FOR BOTH CORNERS. SPECIFY
 ALL FRAMING MEMBERS AND CONNECTORS AT ALL ENDS. SEC.
 R301.1 FBC-RESIDENTIAL AND SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B)BASED ON THE ROOF FRAMING PLAN ON SHEET S-1 AND THE
 TYPICAL WALL SECTION ON SHEET A-3, IT LOOKS LIKE THE
 INTENTION OF THE ARCHITECT IS TO DESIGN AN UNVENTED
 ATTIC. ARCHITECT TO PROVIDE COMPLETE SPECIFICATIONS
 SHOWING COMPLIANCE WITH SEC. R806.5 FBC-RESIDENTIAL FOR
 UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER ASSEMBLIES.
 TYPICALLY, THIS IS DONE USING FOAM INSULATION.
 NOTE: IF SPECIFYING FOAM INSULATION, THEN PROVIDE ICC
 EVALUATION REPORT REVIEWED BY THE ARCHITECT OF RECORD
 PRIOR TO SUBMITTAL.
 NOTE: COORDINATE WITH ITEM #7(D) BELOW.
  
 3- OK
 4- OK
  
 ORIGINAL COMMENT:
 5-PROVIDE COMPLETE WIND DESIGN CRITERIA. SEC. R301.2.1
 FBC-RESIDENTIAL.
 SPECIFY BUILDING EXPOSURE, ULTIMATE AND NOMINAL WIND
 SPEED.
  
 6- OK
  
 ORIGINAL COMMENT:
 7- TYPICAL WALL SECTION ON SHEET A-3:
 A)PROVIDE SPECIFICATIONS CLEARLY SHOWING HOW COMPLYING
 WITH THE NEW 2020 CODE REQUIREMENT FOR ROOFING
 UNDERLAYMENT. SEC. R905.1.1.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 PROVIDE PRODUCT APPROVAL OF PEEL AND STICK UNDERLAYMENT
 SPECIFIED BY THE ARCHITECT. NOTE: PEEL AND STICK
 UNDERLAYMENT SHALL BE APPROVED FOR SHINGLES OVER 30#
 ASPHALT FELT AS SPECIFIED BY THE ARCHITECT.
  
 B)OK
 C)OK
  
 D)WALL SECTION SPECIFIES R-30 CEILING INSULATION.
 CLEARLY SPECIFY WHAT TYPE OF INSULATIONS IS PROPOSED.
 BUTT INSULATION OR FOAM INSULATION. ALSO, IT IS NOT
 CLEAR IF R-30 INSULATION WILL FIT IN THIS CEILING AREA.
 VERIFY AS REQUIRED. WALL SECTION SHOWS ROOF RAFTERS BUT
 IT SPECIFIES ROOF TRUSSES. COORDINATE WITH ITEM #2
 ABOVE.
 NOTE: IF SPECIFYING FOAM INSULATION, THEN PROVIDE ICC
 EVALUATION REPORT REVIEWED BY THE ARCHITECT OF RECORD
 PRIOR TO SUBMITTAL.
  
 RESPONSE:
 BASED ON THE ROOF FRAMING PLAN ON SHEET S-1 AND THE
 TYPICAL WALL SECTION ON SHEET A-3, IT LOOKS LIKE THE
 INTENTION OF THE ARCHITECT IS TO DESIGN AN UNVENTED
 ATTIC. ARCHITECT TO PROVIDE COMPLETE SPECIFICATIONS
 SHOWING COMPLIANCE WITH SEC. R806.5 FBC-RESIDENTIAL FOR
 UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER ASSEMBLIES.
 TYPICALLY, THIS IS DONE USING FOAM INSULATION. REVISE
 AS REQUIRED AND REVISE INSULATION R-VALUE ACCORDINGLY.
  
 NOTE: IF SPECIFYING FOAM INSULATION, THEN PROVIDE ICC
 EVALUATION REPORT REVIEWED BY THE ARCHITECT OF RECORD
 PRIOR TO SUBMITTAL.
  
 E) OK
  
 F)WALL SECTION SPECIFIES SOFFIT VENTS AT 96" O.C.
 SOFFIT NEEDS CROSS VENTILATION AS REQUIRED BY SEC.
 R806.1 FBC-RESIDENTIAL. WALL SECTIONS SHOWS ROOF
 RAFTERS. ROOF RAFTERS DON'T PROVIDE CROSS VENTILATION
 WHEN THE VENTS ARE SPACED AT 96" O.C. THIS NEED TO BE
 COORDINATED WITH ITEM #2 ABOVE AND REVISE WALL SECTION
 SPECIFICATIONS AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 COORDINATE WITH ITEM #7(D) ABOVE.
  
 ORIGINAL COMMENT:
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF SHINGLES.
  
 RESPONSE:
 NOA 20-0318.05 SUBMITTED IS ONLY FOR THE RIDGE CAP
 SHINGLES. NEED TO PROVIDE THE PRODUCT APPROVAL FOR TH
 SHINGLES ALSO.
  
 B)PEEL AND STICK UNDERLAYMENT SPECIFIED BY THE
 ARCHITECT. NOTE: PEEL AND STICK UNDERLAYMENT SHALL BE
 APPROVED FOR SHINGLES OVER 30# ASPHALT FELT AS
 SPECIFIED BY THE ARCHITECT.
  
 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 TO AVOID MORE DELAYS, PLEASE FEEL FREE TO CONTACT ME IF
 YOU HAVE ANY QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-05-26 Cont ID  
Sent By jgomez Date 2021-05-26 Time 14:33 Rev Time 0.00
Received By jgomez Date 2021-05-26 Time 10:09 Sent To  
Notes
2021-05-26 14:35:57RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21040876
  
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106
 FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY
 CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 2- PROVIDE COMPLETE ROOF FRAMING PLAN FOR THE ADDITION.
 CLEARLY SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.
 ALSO, CLEARLY SPECIFY CONNECTION TO EXISTING.
 SEC. R301.2.1 FBC-RESIDENTIAL.
 NOTE: TYPICAL WALL SECTION ON SHEET A-3 SPECIFIES ROOF
 TRUSSES. IT IS NOT CLEAR HOW TRUSSES ARE BUILT IF ONLY
 TOP CHORD IS SHOWN. COORDINATE WITH ITEM #6 BELOW.
 REVISE/CLARIFY.
  
 3- PROVIDE COMPLETE BEAM AND HEADER SCHEDULE. PROVIDE
 COMPLETE SPECIFICATIONS FOR RAKED BEAM SHOWN ON THE
 WEST ELEVATION. PROVIDE SPECIFICATIONS FOR BEAM ABOVE
 NEW OPENING WHERE EXISTING DOOR AND WINDOW WILL BE
 REMOVED TO ALLOW FOR THE ADDITION.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 4- PROVIDE COMPLETE FOUNDATION PLAN FOR THE ADDITION.
 CLEARLY SPECIFY ALL FOOTINGS. ALSO, CLEARLY SPECIFY
 CONNECTION TO EXISTING.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLETE WIND DESIGN CRITERIA. SEC. R301.2.1
 FBC-RESIDENTIAL.
 SPECIFY BUILDING EXPOSURE, ULTIMATE AND NOMINAL WIND
 SPEED.
  
 5- SHEET A-2:
 A)EXISTING INTERIOR LIVING SPACE, ADDITION INTERIOR
 LIVING SPACE AND ADDITION PORCH BUILDING AREAS SHOWN
 UNDER THE SCOPE OF WORK DON'T MATCH BUILDING AREAS
 SHOWN ON PLANS SUBMITTED. ALSO, THESE BUILDING AREAS
 DON'T MATCH CITY RECORDS AND BUILDINGS AREAS SHOWN IN
 PALM BEACH COUNTY PROPERTY APPRAISAL WEBSITE.
 CLARIFY/REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B) REVISE CODE REFERENCES. CURRENT ASCE 7 EDITION
 REFERENCED IN THE CURRENT FBC 2020 IS THE ASCE 7-16 NOT
 ASCE 7-10. REVISE AS REQUIRED.
 CHAPTER 553 F.S.
  
 C) DOOR SCHEDULE SHOWN DOESN'T MATCH DOOR SHOWN ON
 PLANS. REVISE/CLARIFY AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 6- TYPICAL WALL SECTION ON SHEET A-3:
 A)PROVIDE SPECIFICATIONS CLEARLY SHOWING HOW COMPLYING
 WITH THE NEW 2020 CODE REQUIREMENT FOR ROOFING
 UNDERLAYMENT. SEC. R905.1.1.1 FBC-RESIDENTIAL.
  
 B) THERE IS A NOTE TO SEE ELEVATIONS FOR ROOF PITCH.
 ROOD PITCH IS NOT SPECIFIED IN THE ELEVATIONS. SPECIFY
 ROOF PITCH. SEC. R905.2.2 FBC-RESIDENTIAL.
  
 C)PROVIDE SPECIFICATIONS FOR THE CONCRETE SLAB VAPOR
 BARRIER AS REQUIRED BY SEC. R506.2.3 FBC-RESIDENTIAL.
 CLEARLY SPECIFY THE REQUIRED THICKNESS.
  
 D)WALL SECTION SPECIFIES R-30 CEILING INSULATION.
 CLEARLY SPECIFY WHAT TYPE OF INSULATIONS IS PROPOSED.
 BUTT INSULATION OR FOAM INSULATION. ALSO, IT IS NOT
 CLEAR IF R-30 INSULATION WILL FIT IN THIS CEILING AREA.
 VERIFY AS REQUIRED. WALL SECTION SHOWS ROOF RAFTERS BUT
 IT SPECIFIES ROOF TRUSSES. COORDINATE WITH ITEM #2
 ABOVE.
 NOTE: IF SPECIFYING FOAM INSULATION, THEN PROVIDE ICC
 EVALUATION REPORT REVIEWED BY THE ARCHITECT OF RECORD
 PRIOR TO SUBMITTAL.
  
 E) REVISE CLARIFY WALL INSULATION. WALL SECTION
 SPECIFIES R-7.5 WALL INSULATION, WHILE KEY NOTE #1 ON
 SHEET A-2 SPECIFIED R-4.1 WALL INSULATION. REVISE AS
 REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 F)WALL SECTION SPECIFIES SOFFIT VENTS AT 96" O.C.
 SOFFIT NEEDS CROSS VENTILATION AS REQUIRED BY SEC.
 R806.1 FBC-RESIDENTIAL. WALL SECTIONS SHOWS ROOF
 RAFTERS. ROOF RAFTERS DON'T PROVIDE CROSS VENTILATION
 WHEN THE VENTS ARE SPACED AT 96" O.C. THIS NEED TO BE
 COORDINATED WITH ITEM #2 ABOVE AND REVISE WALL SECTION
 SPECIFICATIONS AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 G) WALL SECTION DOESN'T SPECIFY CONNECTION OF NEW ROOF
 FRAMING MEMBER TO EXISTING WALL. PROVIDE INFORMATION.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF SHINGLES.
  
 B)SLIDING GLASS DOORS.
  
 C) SINGLE SWING DOOR.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: COORDINATE WITH DOOR AND WINDOW SCHEDULES SHOWN
 ON PLANS TO AVOID CONFLICTS/DELAYS.
  
 9- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION OR PROVIDE COPY OF SIGNED CONTRACTS INCLUDING
 DESIGN PROFESSIONAL FEES.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-05-13 Cont ID  
Sent By fgiaquin Date 2021-05-13 Time 20:01 Rev Time 0.00
Received By fgiaquin Date 2021-05-13 Time 19:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-12-21 Cont ID  
Sent By jgomez Date 2021-12-21 Time 15:43 Rev Time 0.00
Received By jgomez Date 2021-11-29 Time 06:36 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-11-02 Cont ID  
Sent By jgomez Date 2021-11-02 Time 17:22 Rev Time 0.00
Received By jgomez Date 2021-10-18 Time 12:06 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-12 Cont ID  
Sent By jgomez Date 2021-08-12 Time 18:23 Rev Time 0.00
Received By jgomez Date 2021-07-21 Time 14:31 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-26 Cont ID  
Sent By jgomez Date 2021-05-26 Time 14:42 Rev Time 0.00
Received By jgomez Date 2021-04-29 Time 09:36 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-12-02 Cont ID  
Sent By lmarchan Date 2021-12-02 Time 14:54 Rev Time 0.00
Received By lmarchan Date 2021-11-30 Time 07:44 Sent To  
Notes
2021-12-02 14:54:19RECEIPT MU-2021-056422 - $0.00 DUE
2021-11-30 07:44:3411/30/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-05-26 Cont ID  
Sent By jgomez Date 2021-05-26 Time 14:41 Rev Time 0.00
Received By jgomez Date 2021-05-26 Time 14:40 Sent To  
Notes
2021-05-26 14:41:46IMPACT FEES REVIEW COMMENTS:
  
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-08-02 Cont ID  
Sent By medwards Date 2021-08-02 Time 09:31 Rev Time 0.00
Received By medwards Date 2021-08-02 Time 09:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-05-12 Cont ID  
Sent By medwards Date 2021-05-12 Time 14:01 Rev Time 0.00
Received By medwards Date 2021-05-12 Time 13:49 Sent To  
Notes
2021-05-12 14:02:061ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21040876
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC
 101.5.1.1.2
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS SHOWING THE EXISTING AHU IS SIZED TO
 HANDLE THE ADDITIONAL LOAD. FBC EC R403.7
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-05-14 Cont ID  
Sent By lcrespo Date 2021-05-14 Time 12:55 Rev Time 0.00
Received By lcrespo Date 2021-05-14 Time 12:54 Sent To  
Notes
2021-05-14 14:22:29NO PLUMBING WORK IN THIS STURCTURE.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2021-11-02 Cont ID  
Sent By jgomez Date 2021-11-02 Time 17:18 Rev Time 0.00
Received By jgomez Date 2021-11-02 Time 17:18 Sent To  
Notes
2021-11-02 17:20:071-SHINGLES NOA 19-0312.04
  
 2- SHINGLES UNDERLAYMENT NOA 18-1109.03

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-08-12 Cont ID  
Sent By jgomez Date 2021-08-12 Time 18:21 Rev Time 0.00
Received By jgomez Date 2021-08-12 Time 18:21 Sent To  
Notes
2021-08-12 18:21:52ROOFING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21040876
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF SHINGLES.
 RESPONSE:
 NOA 20-0318.05 SUBMITTED IS ONLY FOR THE RIDGE CAP
 SHINGLES. NEED TO PROVIDE THE PRODUCT APPROVAL FOR TH
 SHINGLES ALSO.
  
 B)PEEL AND STICK UNDERLAYMENT SPECIFIED BY THE
 ARCHITECT. NOTE: PEEL AND STICK UNDERLAYMENT SHALL BE
 APPROVED FOR SHINGLES OVER 30# ASPHALT FELT AS
 SPECIFIED BY THE ARCHITECT.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-05-26 Cont ID  
Sent By jgomez Date 2021-05-26 Time 14:43 Rev Time 0.00
Received By jgomez Date 2021-05-26 Time 14:41 Sent To  
Notes
2021-05-26 14:44:11ROOFING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21040876
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF SHINGLES.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-12-21 Cont ID  
Sent By jgomez Date 2021-12-21 Time 15:38 Rev Time 0.00
Received By jgomez Date 2021-12-21 Time 15:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-12-21 Cont ID  
Sent By jgomez Date 2021-11-02 Time 17:20 Rev Time 0.00
Received By jgomez Date 2021-11-02 Time 17:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-08-02 Cont ID  
Sent By medwards Date 2021-08-02 Time 09:31 Rev Time 0.00
Received By medwards Date 2021-08-02 Time 09:31 Sent To  
Notes
2021-08-02 09:32:53ARCHITECT NEEDS TO DIGITALLY SIGN THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-05-12 Cont ID  
Sent By medwards Date 2021-05-12 Time 14:07 Rev Time 0.00
Received By medwards Date 2021-05-12 Time 14:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-07-28 Cont ID  
Sent By rthermid Date 2021-07-28 Time   Rev Time 0.00
Received By rthermid Date 2021-07-28 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-05-14 Cont ID  
Sent By rthermid Date 2021-05-14 Time   Rev Time  
Received By rthermid Date 2021-05-14 Time   Sent To I
Notes
2021-05-14 10:53:06ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 5/14/2021
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE THE SETBACKS OF THE PROPOSED ADDITION
 TO ALL PROPERTY LINES. PER THE CITY ZONING AND LAND
 DEVELOPMENT CODE, ATTACHED SOLID ROOF STRUCTURES MUST
 MEET THE PRINCIPAL STRUCTURE SETBACKS.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved