Plan Review Details - Permit 21040860
Plan Review Stops For Permit 21040860
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-01-28 Cont ID  
Sent By cpuell Date 2022-01-28 Time 10:15 Rev Time 0.00
Received By cpuell Date 2022-01-28 Time 10:15 Sent To  
Notes
2022-01-28 10:15:41PRIMARY ADDRESS OK FOR SCOPE OF WORK.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-11-24 Cont ID  
Sent By rmcphers Date 2021-11-24 Time 10:39 Rev Time 0.00
Received By rmcphers Date 2021-11-24 Time 10:39 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-11-17 Cont ID  
Sent By rmcphers Date 2021-11-17 Time 16:07 Rev Time 0.00
Received By rmcphers Date 2021-11-17 Time 15:02 Sent To  
Notes
2021-11-17 16:08:12PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-11-24 Cont ID  
Sent By rmcphers Date 2021-11-24 Time 10:39 Rev Time 0.00
Received By rmcphers Date 2021-11-24 Time 10:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-17 Cont ID  
Sent By rmcphers Date 2021-11-17 Time 16:24 Rev Time 0.00
Received By rmcphers Date 2021-11-17 Time 15:02 Sent To  
Notes
2021-11-17 16:24:02RESTROOM REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) ACCESSIBLE RESTROOM - PLEASE STATE THAT THE TOILET
 PAPER HOLDER DISTANCE FROM THE FACE OF THE TOILET IS TO
 THE CENTER LINE OF THE DISPENSER FBC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 2) PLEASE SHOW WALLS FINISHES AT MOP SINK TO COMPLY
 WITH FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE)

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-11-04 Cont ID  
Sent By jleahy Date 2021-11-04 Time 16:20 Rev Time 0.00
Received By jleahy Date 2021-11-04 Time 16:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-10-29 Cont ID  
Sent By pleduc Date 2021-10-29 Time   Rev Time 0.00
Received By pleduc Date 2021-10-29 Time 10:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-28 Cont ID  
Sent By lmarchan Date 2022-01-28 Time 10:15 Rev Time 0.00
Received By cpuell Date 2022-01-20 Time 08:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-04 Cont ID  
Sent By lmarchan Date 2022-01-04 Time 10:13 Rev Time 0.00
Received By lmarchan Date 2021-11-23 Time 13:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-17 Cont ID  
Sent By rmcphers Date 2021-11-17 Time 16:35 Rev Time 0.00
Received By rmcphers Date 2021-10-28 Time 15:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-10-29 Cont ID  
Sent By medwards Date 2021-10-29 Time 10:39 Rev Time 0.00
Received By medwards Date 2021-10-29 Time 10:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-12-03 Cont ID  
Sent By lcrespo Date 2021-12-03 Time 10:17 Rev Time 0.00
Received By lcrespo Date 2021-12-03 Time 10:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-11-02 Cont ID  
Sent By lcrespo Date 2021-11-02 Time 16:03 Rev Time 0.00
Received By lcrespo Date 2021-11-02 Time 16:03 Sent To  
Notes
2021-11-02 16:03:4411/02/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A1.1.1 AND A1.1.3;
 A. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 DRINKING FOUNTAIN PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 LAV OF THE OPEN SPACE IN THE WOMEN'S RESTROOM PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. ON SHEET A2.0.1;
  
 A. WOULD YOU PLEASE SHOW CLEAR FLOOR SPACE AND
 DIMENSIONS FOR THE LAV OF THE OPEN SPACE IN THE WOMEN'S
 RESTROOM PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. ON DETAIL FIVE, WOULD YOU PLEASE SHOW THE TOILET
 PAPER DISPENSERS SHALL BE 7" INCHES MINIMUM AND 9"
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF DISPENSER PER THE 2020 FBC ACC SEC.
 604.7.
  
 C. HANDICAP WATER CLOSET FLUSH CONTROL SHALL BE HAND
 OPERATED OR AUTOMATIC AND SHALL BE 36" INCHES MAXIMUM
 ABOVE THE FINISH FLOOR PER THE 2020 FBC ACC SEC.
 604.9.5.
  
 D. IN AMBULATORY, THE GRAB BARS DO NOT MATCH THE
 DIMENSIONS SHOWN. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 E. IN THE AMBULATORY STALL, WOULD YOU PLEASE SHOW THE
 17 INCHES MINIMUM AND 19 INCHES MAXIMUM FROM THE
 SIDEWALL OR PARTITION IN THE AMBULATORY ACCESSIBLE
 TOILET COMPARTMENT SPECIFIED IN 604.8.2. WATER CLOSETS
 SHALL BE ARRANGED FOR A LEFT-HAND OR RIGHT-HAND
 APPROACH.
  
 F. WOULD YOU PLEASE SHOW THE PARTITION WALLS PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 G. WOULD YOU, PLEASE NOTE THAT THE DOOR HARDWARE SHALL
 BE 34 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. WHERE SLIDING DOORS ARE FULLY
 OPEN, OPERATING HARDWARE SHALL BE EXPOSED AND USABLE
 FROM BOTH SIDES PER THE 2020 FBC ACC. SEC. 404.2.7.
  
 3. ON SHEET A2.02;
  
 A. WOULD YOU PLEASE SHOW THE PARTITION WALLS NOT
 GREATER THAN 12 INCHES FROM AND EXTEND NOT LESS THAN 60
 INCHES ABOVE THE FINISHED FLOOR SURFACE PER THE 2020
 FBC 405.3.5PARTITIONS.
  
 B. ON DETAIL FIVE, WOULD YOU PLEASE SHOW THE TOILET
 PAPER DISPENSERS SHALL BE 7" INCHES MINIMUM AND 9"
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF DISPENSER PER THE 2020 FBC ACC SEC.
 604.7.
  
 C. HANDICAP WATER CLOSET FLUSH CONTROL SHALL BE HAND
 OPERATED OR AUTOMATIC AND SHALL BE 36" INCHES MAXIMUM
 ABOVE THE FINISH FLOOR PER THE 2020 FBC ACC SEC.
 604.9.5.
  
 D. WOULD YOU, PLEASE NOTE THAT THE DOOR HARDWARE SHALL
 BE 34 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. WHERE SLIDING DOORS ARE FULLY
 OPEN, OPERATING HARDWARE SHALL BE EXPOSED AND USABLE
 FROM BOTH SIDES PER THE 2020 FBC ACC. SEC. 404.2.7.
  
  
 4. ON SHEET A2.0.3;
  
 A. ON DETAIL ONE, WOULD YOU PLEASE SHOW THE BOTTOM OF
 THE DRINKING FOUNTAIN TO BE A MINIMUM OF 27" KNEE
 CLEARANCE PER THE 2020 FBC SEC. 306.3.
  
 B. ON DETAIL THREE, WOULD YOU PLEASE SHOW THE TOILET
 PAPER DISPENSERS SHALL BE 7" INCHES MINIMUM AND 9"
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF DISPENSER PER THE 2020 FBC ACC SEC.
 604.7.
  
 C. ON DETAIL FOUR AND EIGHT, WOULD YOU PLEASE SHOW THE
 BOTTOM OF THE LAV TO BE A MINIMUM OF 27" KNEE CLEARANCE
 PER THE 2020 FBC SEC. 306.3.
  
 D. WOULD YOU, PLEASE SHOW THE TOILET IS 16 INCHES TO 18
 INCHES TO THE CENTER PER THE 2020 FBC ACC SEC. 604.2
 LOCATION.
  
 E. WOULD YOU PLEASE SHOW THE 30 X 48 IN. CLEAR FLOOR
 SPACE FOR A FORWARD APPROACH TO THE WHEELCHAIR
 ACCESSIBLE DRINKING FOUNTAIN 2020 FBC ACC SEC. 602.2
 CLEAR FLOOR SPACE
  
 F. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET?
  
 5. ON SHEET P-4.1;
  
 A. WOULD YOU PLEASE SHOW THE TRAP PRIMER FOR FLOOR
 DRAINS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. HOT WATER LINES LOOPED FOR THE RECIRCULATING SYSTEM
 IT IS NOT IN A CONTINUOUS LOOP. THERE IS A REQUIREMENT
 IN THE FLORIDA ENERGY CODE SEC. C404.6.1. THERE IS A
 TEE FOR THE TWO RESTROOMS, AND TWO CHECK VALVES MAY BE
 USED ON EACH SIDE OF THE EXIT TEE TO DIRECT THE FLOW TO
 A TWO-LOOP IF PREFERRED FOR THE CORRECTION!
  
 C. THERE IS NO COLD WATER SHOWN IN THE RESTROOMS. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. WOULD YOU, PLEASE SHOW THE HAMMER ARRESTOR FOR THE
 DRINKING FOUNTAIN PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. THERE IS AN ON DETAIL FIVE THAT SAYS INSULATION FOR
 ? INCH, AND IT SHALL BE 1' PER TABLE C403.2.10 MINIMUM
 PIPE INSULATION THICKNESS. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-11-24 Cont ID  
Sent By rmcphers Date 2021-11-24 Time 10:44 Rev Time 0.00
Received By rmcphers Date 2021-11-24 Time 10:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-11-17 Cont ID  
Sent By rmcphers Date 2021-11-17 Time 16:32 Rev Time 0.00
Received By rmcphers Date 2021-11-17 Time 16:32 Sent To  
Notes
2021-11-17 16:35:33SIGNATURE REVIEW
  
 DRAWING A4.0.1 DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-01-27 Cont ID  
Sent By eschneid Date 2022-01-27 Time 16:15 Rev Time 0.25
Received By eschneid Date 2022-01-27 Time 16:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-12-29 Cont ID  
Sent By eshneide Date 2021-12-29 Time 15:14 Rev Time 0.25
Received By eschneid Date 2021-12-29 Time 15:05 Sent To  
Notes
2021-12-29 15:14:29FAILED
  
 1) THE CITYPLACE RETAIL MANAGEMENT APPROVAL STAMP IS
 REQUIRED ON THE PLANS. ALTERNATIVELY, YOU MAY PROVIDE A
 LETTER FROM CITYPLACE RETAIL MANAGEMENT WHICH APPROVES
 THE SPECIFIC PLANS SUBMITTED AS PART OF THE PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  