| Plan Review Stops For Permit 21040859 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2021-07-16 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-07-16 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-07-16 |
Time |
09:59 |
Sent To |
|
|
| Notes |
| 2021-07-16 09:59:49 | PROPERTY HAS BEEN READDRESSED THE MAIN SOUTH BLDG HAS | | | BEEN CHANGED FROM 709 AVON RD TO 707 AVON RD AND THE | | | BACK UNIT HAS BEEN ASSIGNED 709 AVON RD, |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2021-06-18 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-06-18 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-06-18 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2021-06-18 10:10:15 | PLEASE COORDINATE WITH [email protected] FOR THE LIVABLE | | | SPACE TO BE GIVEN AN ADDRESS. ALL ACCESSORY | | | RESIDENTIAL/COMMERCIAL UNITS AND OR OTHER HABITABLE | | | STRUCTURES WILL BE ISSUED A UNIQUE SECONDARY ADDRESS | | | NUMBER PER CITY'S ADDRESSING POLICY. FRONT AND REAR | | | BUILDINGS WILL NEED TO BE READDRESS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-06-29 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-06-18 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-06-18 |
Time |
06:08 |
Sent To |
|
|
| Notes |
| 2021-06-18 09:04:52 | PROVISO'S: | | | 1) WINDOWS AND DOORS, PG D-1. | | | 2) SITE WALLS, PG S-1. | | | CT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-05-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-05-13 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-05-12 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2021-05-13 10:50:31 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: A PROVISO HAS BEEN PLACED ON THE SITE PLAN: | | | SITE WALLS SHALL BE BY SEPERATE PERMIT. CT | | | | | | | | | 1. VALUE | | | CITY OF WPB CHPT109.3 BUILDING PERMIT VALUATIONS. | | | | | | VALUE CANNOT BE DETERMINED AT THIS TIME. PROJECT DATA | | | STATES ACCESSORY ADDITION IS 159 SF. THIS APPEARS LOW | | | BUT I CANNOT VERIFY DUE TO MISSING DEMENSIONS ON PLANS. | | | UPDATE YOUR PLANS WITH ALL REQUIRED DEMENSIONS. | | | | | | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE | | | BUILDING OFFICIAL | | | | | | 2. PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER | | | SHEETS FOR ALL FLORIDA PRODUCT APPROVALS SUBMITTED. THE | | | COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE VERSION, | | | AND STATUS, FBC R 301. | | | (COVER SHEETS ARE NOT REQUIRED FOR MIAMI DADE NOAS.) | | | | | | 3. PROVIDE A SITE DRAINAGE PLAN. | | | FBC R401.3 SITE DRAINAGE | | | PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH | | | FBC R401.3 DRAINAGE. | | | | | | 4. PROVIDE AN ENERGY SUBMITTAL. | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | 5. CANNOT VERIFY SF OF ADDITION. PROVIDE PLANS WITH | | | REQUIRED DEMENSIONS. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 6. SHOW COMPLIANCE WITH REQUIRED SMOKE ALARMS PER R314. | | | R314.1 GENERAL. | | | SMOKE ALARMS SHALL COMPLY WITH NFPA 72 AND SECTION | | | R314. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-06-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-06-23 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-06-23 |
Time |
14:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-05-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-05-04 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-05-04 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2021-05-04 12:50:42 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) SEPARATER GROUNDING ELECTRODE REQUIRED AT SEPARATE | | | BUILDING. | | | | | | A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE | | | ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND | | | CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF | | | GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; | | | | | | 2) SMOKE ALARMS ARE REUIRED BY FBC R314/315 | | | | | | PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER | | | CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE | | | EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC | | | R314.3, FBC 107.2.1 | | | | | | 3) OUTLETS REQUIRED AT THE FRONT AND REAR OF EACH | | | BUILDING. | | | | | | FOR A ONE FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY | | | DWELLING THAT IS AT GRADE LEVEL, AT LEAST ONE | | | RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND NOT | | | MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE | | | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. NEC | | | 210.52(E)(1) FBC RE3901.7 |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-05-19 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2021-05-19 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2021-05-19 |
Time |
16:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
P |
Date |
2021-08-16 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-08-16 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-08-09 |
Time |
16:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-06-29 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-06-29 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-06-15 |
Time |
08:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-05-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-05-20 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-04-22 |
Time |
14:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2021-08-06 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-08-06 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
ccarvaja |
Date |
2021-07-23 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2021-08-06 12:39:47 | 8/6/21 RECEIVED EMAIL FROM PBC THE IMPACT FEES WERE | | | PROCESSED AND NO FEES ARE DUE. CC | | 2021-07-23 11:34:56 | 7/23/21 EMAILED IMPACT FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2021-05-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-05-13 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-05-13 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2021-05-13 09:31:09 | PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2021-06-22 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-06-22 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-06-22 |
Time |
12:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-05-03 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-05-03 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-05-03 |
Time |
16:08 |
Sent To |
|
|
| Notes |
| 2021-05-03 16:19:15 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21040859 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE | | | CONDITIONED SPACE OF THE NEW ADDITION. FBC RES R402. | | | | | | 2) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE | | | MECHANICAL SYSTEM SHOWN ON THE MECHANICAL EQUIPMENT | | | SIZING SHEET. FBC 107.2.1 | | | | | | 3) PLEASE SHOW ON THE MECHANICAL DRAWING THE CONDENSATE | | | DRAIN LINE AND TERMINATION LOCATION. FBC RES M1411 | | | | | | 4) A MECHANICAL SUB-PERMIT IS REQUIRED. | | | | | | 5) FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN | | | MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE | | | MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE | | | SPECIFIC PROJECT WHICH HE OR SHE INSTALLS. | | | PLEASE, HAVE EITHER A LICENSED ENGINEER, PROVIDE A | | | SIGNED AND SEALED MECHANICAL EQUIPMENT SIZING | | | CALCULATION AND A SIGNED AND SEALED MECHANICAL DRAWING, | | | OR | | | THE MECHANICAL CONTRACTOR INSTALLING THE SYSTEM SHALL | | | PROVIDE THE EQUIPMENT SIZING CALCULATIONS AND A CODE | | | COMPLIANT DESIGN. CONTRACTOR SHALL INCLUDE HIS OR HER | | | PRINTED NAME AND SIGNATURE PER 2017 WPB AMENDMENTS TO | | | THE FLORIDA BUILDING CODE, CHAPTER 1, SECTION 107.2.1. | | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | | | | THERE IS NO MECHANICAL SUB PERMIT FOR THIS JOB. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2021-07-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-07-21 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-07-21 |
Time |
14:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2021-06-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-06-17 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-06-17 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2021-06-17 16:46:24 | 2ND REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 21040859 | | | 6/17/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | GUEST HOUSE PLUMBING. | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) MP1: THE GUEST HOUSE PLUMBING FLOOR PLAN AND | | | ACCESSORY RISER DO NOT MATCH. BASED ON THE FLOOR PLAN, | | | THE WASHING MACHINE DRAIN POINT OF CONNECTION TO THE | | | MAIN SHOULD BE DOWN STREAM OF THE BATHROOMS- PLEASE | | | CORRECT- SECTION 107.2.1 WPB. | | | | | | 2) MP1: INDICATE HOW HOT WATER WILL BE SUPPLIED TO THE | | | GUEST HOUSE BATH FIXTURES- SECTION P2801.1 FBC P. | | | | | | 3) MP1: THE NEW PLUMBING PLAN SHOWS TWO DWELLINGS ON | | | THE SAME LOT WHICH WILL REQUIRE WATER USERS TO INSTALL | | | A BACKFLOW PREVENTION ASSEMBLY AT THE POINT OF | | | DELIVERY. A REDUCED PRESSURE ZONE BACKFLOW DEVICE WILL | | | BE REQUIRED FOR THE WATER METER PER THE CITY OF WEST | | | PALM CROSS UTILITIES DEPARTMENT AND THEIR CONNECTION | | | CONTROL PROGRAM. | | | | | | PLEASE NOTE ON THE PLAN THAT A FL. LICENSED PLUMBING | | | CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR | | | INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE | | | WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF | | | ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY | | | THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION | | | BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB | | | UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR | | | FURTHER INFORMATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-05-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-05-05 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-05-05 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2021-05-05 08:39:04 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 21040859 | | | 5/5/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE PLUMBING PLAN- SHEET MP-1- SHOWN IN THE INDEX ON | | | A-1 WAS NOT UPLOADED FOR REVIEW. PLEASE PROVIDE THE | | | PLAN- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2021-06-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-06-18 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-06-18 |
Time |
06:07 |
Sent To |
|
|
| Notes |
| 2021-06-18 09:05:42 | PROVISO ON PG. S-2: ROOFING BY SEPERATE PERMIT. CT |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-05-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-05-13 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-05-12 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2021-05-13 10:15:39 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. SUBMIT A ROOFING SUB-PERMIT APPLICATION. | | | PERMITS - 105.1 REQUIRED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-06-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-06-18 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-06-18 |
Time |
06:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-05-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-05-13 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-05-12 |
Time |
15:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2021-08-13 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2021-08-13 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2021-08-13 |
Time |
10:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2021-06-28 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2021-06-28 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2021-06-28 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2021-06-28 16:35:39 | NEED LANDSCAPE PERMIT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-05-19 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2021-05-19 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2021-05-19 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2021-05-19 16:28:56 | REQUIRES SEPARATE LANDSCAPE PERMIT |
|
|