Plan Review Details - Permit 21040844
Plan Review Stops For Permit 21040844
Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-06-03 Cont ID  
Sent By cpuell Date 2022-06-03 Time 13:39 Rev Time 0.00
Received By cpuell Date 2022-06-03 Time 13:39 Sent To  
Notes
2022-06-03 13:40:22READ RESPONCE TO COMMENTS 6/1/22 UNABLE TO APPROVE
 REVIEW UNTIL THE ORIGINAL COMMENTS ARE ADDRESSED.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-05-14 Cont ID  
Sent By cpuell Date 2021-05-14 Time 16:35 Rev Time 0.00
Received By cpuell Date 2021-05-14 Time 16:30 Sent To  
Notes
2021-05-14 16:35:32PLEASE REACH OUT TO [email protected] TO DISCUSS THE
 ADDRESSING OF THIS PROJECT. BUILDINGS 1 2 3 AND 4 WILL
 NEED THEIR OWN ADDRESSES. ALL UNITS WILL NEED TO BE
 ASSIGNED ADDRESSES AND ANY UNITS ON THE GROUND FLOOR
 WITH THEIR OWN ENTRANCE WILL HAVE THEIR OWN UNIQUE
 ADDRESS.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 2 Status F Date 2022-06-28 Cont ID  
Sent By scwelter Date 2022-06-28 Time 10:55 Rev Time 0.00
Received By scwelter Date 2022-06-28 Time 11:03 Sent To  
Notes
2022-06-28 11:02:57DEVELOPMENT SUBJECT TO PUBLIC ART REQUIREMENT. EMAIL
 [email protected] WITH PERMIT NUMBER TO OBTAIN AN ART
 ASSESSMENT APPLICATION.
  
 BELOW IS THE CALCULATION
  
 PERMIT $5,175,000
  
 1% $51,750
 OPTION 1 - INTEGRATE ART AT 1% INTO DEVELOPMENT SITE
  
 OR
  
 OPTION 2 PUBLIC ART ACCOUNT (-25% OF THE 1%)
 (-12,937.50)
 TOTAL FEE $38,812.50

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status F Date 2021-04-19 Cont ID  
Sent By scwelter Date 2021-04-19 Time 11:15 Rev Time  
Received By scwelter Date   Time   Sent To  
Notes
2021-04-19 11:16:24PUBLIC ART REQUIREMENT:
 IF TOTAL CONSTRUCTION COSTS OF THIS DEVELOPMENT ARE
 OVER $500,000 IT WILL BE SUBJECT TO THE PUBLIC ART
 REQUIREMENT AS PER CITY ORDINANCE.
 SECTION 78-129: ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT.
 OPTION 1: INSTALL ARTWORK ON THE DEVELOPMENT SITE
 VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE
 TOTAL CONSTRUCTION COSTS; OR
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF
 ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT
 TO THE PUBLIC ART ACCOUNT.
 A COMPLETED PUBLIC ART ASSESSMENT APPLICATION IS
 REQUIRED AT TIME OF BUILDING PERMIT SUBMITTAL.
  
 PLEASE CONTACT SYBILLE WELTER AT [email protected] OR
 561.822.1521 TO OBTAIN AN APPLICATION AND REVIEW THE
 REQUIREMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-06-09 Cont ID  
Sent By rmcphers Date 2022-06-09 Time 14:02 Rev Time 0.00
Received By rmcphers Date 2022-06-08 Time 16:27 Sent To  
Notes
2022-06-09 14:02:44NEW 3 STORY APT BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) DRAWINGS WITH THE WORDS "NOT FOR CONSTRUCTION"
 CANNOT BE APPROVED - PLEASE REMOVE THE COMMENT.
  
 2) SECOND AND THIRD FLOOR EGRESS BALCONY - PLEASE SHOW
 THE DECKING TYPE AND CONNECTIONS TO FRAMING.
  
 3) PLEASE SHOW HOW THE FLOOR/CEILING SYSTEMS COMPLY
 WITH THE REQUIRED MINIMUM STC AND IIC RATINGS FBC
 1207.2 AND 1207.3 (USING TEST REPORTS OR ANALYSIS FROM
 A DESIGN PROFESSIONAL )
  
 4) PRODUCT APPROVAL (FL14724 - R10) HAS BEEN REVISED
 PLEASE PROVIDE THE REVISED ADDITION (FL14724 - R11).
  
 5) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING
 INFORMATION 107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES).
  
 6) PLEASE PROVIDE A SURVEY SEC.94-76(A)(2) OF THE
 ZONING AND LAND DEVELOPMENT CODE.
  
 7) PLEASE SHOW THE WINDOW AND DOOR OPENING REQUIRED
 WIND DESIGN PRESSURES - FBC 1603.1.4 WIND DESIGN DATA.
  
 8) DRAWING S5.2 DETAIL 4 SHOWS STAIR RISER MAXIMUM
 HEIGHT AT 7 3/4" - SHOULD BE 7" PER FBC 1011.5.2
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-07-21 Cont ID  
Sent By rmcphers Date 2021-07-21 Time 13:48 Rev Time 0.00
Received By rmcphers Date 2021-07-19 Time 07:35 Sent To  
Notes
2021-07-19 15:35:53NEW 3 STORY APT BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) DRAWINGS WITH THE WORDS "NOT FOR CONSTRUCTION"
 CANNOT BE APPROVED - PLEASE REMOVE THE COMMENT.
 2) BATHROOM CEILING HEIGHTS NEED TO COMPLY WITH FBC
 1208.2
 3) PLEASE SHOW STAIR WIDTHS FBC 1011.2
 4) PLEASE SHOW STAIR RISER HEIGHTS AND TREAD DEPTHS FBC
 1011.5.2
 5) CONSTRUCTION TYPE IS SHOWN AS IIB - PLYWOOD ROOF
 SHEATHING SHOULD BE SHOWN AS FIRE RETARDANT FBC 603.1
 6) CONSTRUCTION TYPE IS SHOWN AS IIB - CANNOT HAVE
 PLYWOOD AS PART OF THE FLOOR CONSTRUCTION FBC 602.2
 7) WOOD FLOOR SHEATHING WITHIN 18 INCHES OF THE GROUND
 SHALL BE OF NATURALLY DURABLE OR PRESERVATIVE-TREATED
 WOOD. FBC 2304.12.1.1JOISTS, GIRDERS AND SUBFLOOR.
 8) SECOND AND THIRD FLOOR EGRESS BALCONY - PLEASE SHOW
 THE DECKING TYPE AND CONNECTIONS TO FRAMING.
 9) SECOND AND THIRD FLOOR EGRESS BALCONY - MECHANICAL
 DRAWINGS SHOW AC UNITS ON THE EGRESS BALCONIES - PLEASE
 SHOW THAT THE REQUIRED EGRESS WIDTH REMAINS FBC 1005.4
 CONTINUITY.
 THE MINIMUM WIDTH OR REQUIRED CAPACITY OF THE MEANS OF
 EGRESS REQUIRED FROM ANY STORY OF A BUILDING SHALL NOT
 BE REDUCED ALONG THE PATH OF EGRESS TRAVEL UNTIL
 ARRIVAL AT THE PUBLIC WAY.
 10) DRAWING A7.32 SHOWS FIRE RATING INSTALLED OVER MATE
 LINES - PLEASE SHOW THE TYPE OF FIRE STOPPING TO BE
 INSTALLED.
 11) DRAWING A8.21 SHOWS WALL ASSEMBLY (VERTICAL
 ASSEMBLY) AND A NOTE ON THE DRAWING PERTAINING TO A
 HORIZONTAL ASSEMBLY - PLEASE CLARIFY.
 12) DRAWING S-1 SHOWS THE CODE VERSION USED FOR THE
 DESIGN AS 2017 FBC - SHOULD BE THE 2020 FBC - PLEASE
 REVISE.
 13) BUILDING DESIGN CALCULATIONS SHOWS THE 2017 FBC
 USED FOR DESIGN - SHOULD BE THE 2020 FBC - PLEASE
 REVISE.
 14) DRAWING S6 A - PLAN REFERS TO A NOTE NUMBER 9 -
 NOTE NUMBER 9 IS NOT ON THE DRAWING - PLEASE CLARIFY.
 15) DRAWING S6 B - PLAN REFERS TO NOTE NUMBER 8 - NOTE
 NUMBER 8 IS NOT ON THE DRAWING - PLEASE CLARIFY.
 16) DRAWING S6 C - NOTE NUMBER 9 SHOWS ROOF SHEATHING
 ATTACHED TO THE METAL FRAMING WITH NAILS - PLEASE
 CLARIFY METAL FRAMING ATTACHMENTS.
 17) PLEASE SHOW HOW THE WALLS BETWEEN UNITS COMPLY WITH
 THE REQUIRED MINIMUM STC RATINGS FBC 1207.2 (USING TEST
 REPORTS, WALL DESIGN MANUALS OR ANALYSIS FROM A DESIGN
 PROFESSIONAL )
 18) PLEASE SHOW HOW THE FLOOR/CEILING SYSTEMS COMPLY
 WITH THE REQUIRED MINIMUM STC AND IIC RATINGS FBC
 1207.2 AND 1207.3 (USING TEST REPORTS OR ANALYSIS FROM
 A DESIGN PROFESSIONAL )
 19) PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB
 107.2 (UNLESS THE PRODUCT APPROVAL NUMBER IS SHOWN ON
 THE DRAWINGS)
 20) PRODUCT APPROVAL (FL14724 - R10) HAS BEEN REVISED
 PLEASE PROVIDE THE REVISED ADDITION (FL14724 - R11).
 21) PRODUCT APPROVAL FOR THE SWING DOOR (FL11218 - R4)
 SHOWS ANCHORAGE TO A CONCRETE SUBSTRATE ONLY - PLEASE
 PROVIDE ATTACHMENT TYPES AND SPACING FROM THE DESIGN
 PROFESSIONAL. FBC WPB 107.2
 22) PRODUCT APPROVAL FOR THE LOW SLOPE ROOFING (FL17491
 - R5) = NEED TO CHOOSE A ROOFING SYSTEM IN THE PRODUCT
 APPROVAL THAT SHOWS THE REQUIRED WIND DESIGN PRESSURE -
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 PRODUCT APPROVAL - IF NEEDED PLEASE PROVIDE ADDITIONAL
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A HIGHER WIND
 PRESSURE THEN THE CHOSEN ROOFING SYSTEM - SEE NOTES ON
 THE PRODUCT APPROVAL.
 23) PLEASE SHOW THE BUILDING SQUARE FOOTAGE FOOTPRINT.
 24) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING
 INFORMATION 107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES).
 25) PLEASE PROVIDE A SURVEY SEC.94-76(A)(2) OF THE
 ZONING AND LAND DEVELOPMENT CODE.
 26) PLEASE SHOW THE GROUND FLOOR UNITS TO MEET FBC FHA
 REQUIREMENT 6 -REINFORCED WALLS FOR GRAB BARS. SHOW
 LOCATIONS AND BACKING DETAILS.
 27) PLEASE SHOW THE GROUND FLOOR UNITS TO MEET FBC FHA
 REQUIREMENT 7 -USABLE KITCHENS AND BATHROOMS. SHOW THE
 REQUIRED CLEAR FLOOR SPACE ON THE UNIT FLOOR PLANS. (A)
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 THAT ALLOWS A PARALLEL APPROACH BY A PERSON IN A
 WHEELCHAIR IS PROVIDED AT THE RANGE OR COOKTOP AND SINK
 AND EITHER A PARALLEL OR FORWARD APPROACH IS PROVIDED
 AT OVEN, DISH WASHER, REFRIGERATOR/FREEZER OR TRASH
 COMPACTOR. (SEE FIGURE FHAG-6) - - (2)USABLE BATHROOMS.
 TO MEET THE REQUIREMENTS OF SECTION 100.205(C)(3)(IV)
 EITHER.
 ALL BATHROOMS IN THE DWELLING UNIT COMPLY WITH OPTION
 2, OR THE PROVISIONS OF PARAGRAPH (A): OR
 AT LEAST ONE BATHROOM IN THE DWELLING UNIT COMPLIES
 WITH THE PROVISIONS OF PARAGRAPH (B), AND ALL OTHER
 BATHROOMS AND POWDER ROOMS WITHIN THE DWELLING UNIT
 MUST BE ON AN ACCESSIBLE ROUTE WITH USABLE ENTRY DOORS
 IN ACCORDANCE WITH THE GUIDELINES FOR REQUIREMENTS 3
 AND 4.
 28) PLEASE SHOW THE KITCHEN DIMENSIONS TO COMPLY WITH
 FBC FHA REQUIREMENT 7 (1) (B)CLEARANCE BETWEEN COUNTERS
 AND ALL OPPOSING BASE CABINETS, COUNTERTOPS, APPLIANCES
 OR WALLS IS AT LEAST 40 INCHES.
 29) PLEASE SHOW THE COMPONENT WIND DESIGN PRESSURES FOR
 THE OPENINGS AND ROOFING - FBC 1603.1.4 WIND DESIGN
 DATA. (5).DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF
 (KN/M2).
 30) DRAWING G0.03 HAS A STATEMENT "DESIGN IS COMPLIANT
 WITH THE 2017 FBC ACCESSIBILITY CODE (SHOULD BE 2020
 FBC ACCESSIBILITY) PLEASE CORRECT.
 31) PLEASE PROVIDE DETAILS FOR THE "TEXTILE FACADE
 SYSTEM" TO COMPLY WITH THE WIND LOADS FBC 1609
 32) PLEASE PROVIDE DETAILS FOR THE "MURAL PANEL FACADE
 SYSTEM" TO COMPLY WITH THE WIND LOADS FBC 1609
 33) FBC WPB107.3.4.1 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 34) SEPARATE PERMITS ARE REQUIRED FOR PARKING LOT,
 DUMPSTER ENCLOSURES, FENCES, - PLEASE ACKNOWLEDGE THIS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-06-24 Cont ID  
Sent By jleahy Date 2022-06-24 Time 07:36 Rev Time 0.00
Received By jleahy Date 2022-06-23 Time 16:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-07-19 Cont ID  
Sent By jleahy Date 2021-07-19 Time 12:36 Rev Time 0.00
Received By jleahy Date 2021-07-19 Time 06:39 Sent To  
Notes
2021-07-19 12:47:33ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PHONE OUTLET NEEDED IN EACH UNIT 800.154
  
 800.156 DWELLING UNIT COMMUNICATIONS OUTLET. FOR NEW
 CONSTRUCTION, A MINIMUM OF ONE COMMUNICATIONS OUTLET
 SHALL BE INSTALLED WITHIN THE DWELLING IN A READILY
 ACCESSIBLE AREA AND CABLED TO THE SERVICE PROVIDER
 DEMARCATION POINT
  
 2) FIRST FLOOR UNITS ARE REQUIRED TO HAVE AN RECEPTACLE
 OUTLET AT FRONT AND REAR OF UNIT. 210.52(E)(2)
  
 (2) MULTIFAMILY DWELLINGS. FOR EACH DWELLING UNIT OF A
 MULTIFAMILY DWELLING WHERE THE DWELLING UNIT IS LOCATED
 AT GRADE LEVEL AND PROVIDED WITH INDIVIDUAL EXTERIOR
 ENTRANCE/EGRESS, AT LEAST ONE RECEPTACLE OUTLET READILY
 ACCESSIBLE FROM GRADE AND NOT MORE THAN 2.0 M (61?2 FT)
 ABOVE GRADE LEVEL SHALL BE INSTALLED.
  
 3) FAULT CURRENT CALCULATION IS REQUIRED FOR SERVICE
 AND EQUIPMENT, AND LABELS ARE REQUIRED FOR THE
 EQUIPMENT. 110.9, 110,10, 110.24
  
 110.9 INTERRUPTING RATING. EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT FAULT LEVELS SHALL HAVE AN
 INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE AT LEAST
 EQUAL TO THE CURRENT THAT IS AVAILABLE AT THE LINE
 TERMINALS OF THE EQUIPMENT. EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT OTHER THAN FAULT LEVELS SHALL HAVE
 AN INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE AT
 LEAST EQUAL TO THE CURRENT THAT MUST BE INTERRUPTED.
  
 110.10 CIRCUIT IMPEDANCE, SHORT-CIRCUIT CURRENT
 RATINGS, AND OTHER CHARACTERISTICS. THE OVERCURRENT
 PROTECTIVE DEVICES, THE TOTAL IMPEDANCE, THE EQUIPMENT
 SHORT-CIRCUIT CURRENT RATINGS, AND OTHER
 CHARACTERISTICS OF THE CIRCUIT TO BE PROTECTED SHALL BE
 SELECTED AND COORDINATED TO PERMIT THE CIRCUIT
 PROTECTIVE DEVICES USED TO CLEAR A FAULT TO DO SO
 WITHOUT EXTENSIVE DAMAGE TO THE ELECTRICAL EQUIPMENT OF
 THE CIRCUIT. THIS FAULT SHALL BE ASSUMED TO BE EITHER
 BETWEEN TWO OR MORE OF THE CIRCUIT CONDUCTORS OR
 BETWEEN ANY CIRCUIT CONDUCTOR AND THE EQUIPMENT
 GROUNDING CONDUCTOR(S) PERMITTED IN 250.118. LISTED
 EQUIPMENT APPLIED IN ACCORDANCE WITH THEIR LISTING
 SHALL BE CONSIDERED TO MEET THE REQUIREMENTS OF THIS
 SECTION.
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2022-06-07 Cont ID  
Sent By rrossano Date 2022-06-07 Time   Rev Time 0.00
Received By rrossano Date 2022-06-07 Time   Sent To  
Notes
2022-06-07 08:06:46UNDER REVIEW AS FORMAL ENGINEERING SUBMITTAL E19070023,
 WAITING ON REVISED ENGINEERING PLANS.
  
 RICK ROSSANO, SENIOR PROJECT COORDINATOR, CITY OF WPB
 ENGINEERING SERVICES DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected] HTTPS://WWW.WPB.ORG/GOVERNMENT/
 ENGINEERING/ENGINEERING-STANDARDS-DETAILS
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-08-04 Cont ID  
Sent By rrossano Date 2021-08-04 Time   Rev Time  
Received By rrossano Date 2021-08-04 Time   Sent To I
Notes
2021-08-04 08:48:55PLEASE ADDRESS BUILDING & ZONING COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-07-19 Cont ID  
Sent By pleduc Date 2021-07-19 Time   Rev Time 0.00
Received By pleduc Date 2021-07-19 Time 13:15 Sent To  
Notes
2021-07-19 13:41:33FIRE PROVISO COMMENTS:
  
 ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 THE FIRE SPRINKLER SYSTEM SHALL BE INSTALLED
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 THE FIRE ALARM SYSTEM SHALL BE INSTALLED
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-28 Cont ID  
Sent By aoliver Date 2022-06-28 Time 07:17 Rev Time 0.00
Received By aoliver Date 2022-06-02 Time 06:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-04 Cont ID  
Sent By lmarchan Date 2021-08-04 Time 14:35 Rev Time 0.00
Received By lmarchan Date 2021-05-11 Time 09:59 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-07-20 Cont ID  
Sent By rmcphers Date 2021-07-20 Time 13:27 Rev Time 0.00
Received By rmcphers Date 2021-07-20 Time 13:27 Sent To  
Notes
2021-07-20 13:27:57PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-06-10 Cont ID  
Sent By medwards Date 2022-06-10 Time 13:58 Rev Time 0.00
Received By medwards Date 2022-06-10 Time 13:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-07-16 Cont ID  
Sent By medwards Date 2021-07-16 Time 09:54 Rev Time 0.00
Received By medwards Date 2021-07-16 Time 09:54 Sent To  
Notes
2021-07-16 09:54:591ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21040844
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC C403.2.1
  
 2) SHEET M0.01: PLEASE SHOW HOW THE GOODMAN SPLIT
 SYSTEM THAT IS LABELED COOLING ONLY WILL MEET THE
 HEATING REQUIREMENTS OF, FBC M 309.1
  
 3) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR THESE
 UNITS. FBC M TABLE 403.3.1.1
  
 4) CONDENSATE FROM THE CONDENSING UNITS ON THE OUTDOOR
 BALCONIES MUST NOT DRAIN ON THE BALCONIES AS THIS WILL
 CAUSE A NUISANCE. FBC M 307.2.1
  
 5) PLEASE EXPLAIN THE USE OF BUILDING 3 & 4 AND THE
 NORTH & SOUTH POPUP SPACES. FBC 107.2.1
  
 6) PLEASE SHOW HOW THE UNITS ABOVE THE BATHROOM
 CEILINGS WILL BE ACCESSED FOR SERVICING. FBC M 306
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-06-06 Cont ID  
Sent By ccole Date 2022-06-06 Time 14:47 Rev Time 0.00
Received By ccole Date 2022-06-03 Time 13:50 Sent To  
Notes
2022-06-06 14:48:302ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21040844
 6/6/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 2) FAILED. THE REQUESTED ENLARGED SITE SPECIFIC
 DRAWINGS AND DETAILS FOR THE PUBLIC RESTROOMS NOT
 PROVIDED. PLEASE COMPLY. WHERE PUBLIC BATHROOM
 FACILITIES ARE REQUIRED, PLEASE SHOW THE LOCATIONS ON
 THE FLOOR PLAN DRAWINGS AND PROVIDE SITE SPECIFIC FLOOR
 PLANS AND ELEVATION DRAWINGS THAT INCLUDE THE FOLLOWING
 ITEMS- FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSET FROM THE SIDE WALLS-
 SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOORS- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 3) FAILED. REQUESTED DETAILS NOT PROVIDED. WHERE
 DRINKING FOUNTAINS ARE REQUIRED PLEASE REFER TO
 SECTIONS 306, 307, AND 602 FBC ACC AND PROVIDE DRINKING
 FOUNTAIN INSTALLATION DETAILS AND ELEVATION VIEWS
 SHOWING KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, AND
 SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48 IN. CLEAR
 FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH TO THE
 FOUNTAIN- SECTION 602.2 FBC ACC.
  
 4) FAILED. G.0.03- REFER TO REQUIREMENT 7 FBC ACC:
 PLEASE INCLUDE THE REQUIRED COMPLIANCE WITH THE FAIR
 HOUSING ACT DESIGN MANUAL IN THE CODE INFORMATION, AND
 PROVIDE A LIST OF ALL UNITS THAT ARE COVERED UNDER THE
 ACT. THE INDIVIDUAL BATHROOMS SHALL BE DESIGNATED AS
 EITHER SPECIFICATION TYPE A OR B, AND ENLARGED
 DIMENSIONED DRAWINGS AND DETAILS IN ACCORDANCE WITH
 CHAPTER 7 OF THE MANUAL SHALL BE PROVIDED- SEE PAGE
 7.34 OF THE MANUAL. THE USABLE KITCHEN AND BATHROOM
 DESIGN SPECIFICATION REQUIREMENTS ARE LISTED UNDER
 REQUIREMENT 7 FBC ACC AND CHAPTERS 6 AND 7 OF THE
 MANUAL. BASED ON A LACK OF INFORMATION PROVIDED ON THE
 PLANS THE ACCESSIBILITY AND FAIR HOUSING REVIEWS ARE
 CURRENTLY STOPPED PENDING RESUBMITTAL OF REVISED PLANS.
 (SPECIFICATION A OR B SELECTION NOT PROVIDED HOWEVER IT
 APPEARS SPEC B HAS BEEN CHOSEN FOR THE BATHROOMS,
 PLEASE CONFIRM WITH A NOTE. PLEASE REVISE SHEETS A4.01-
 A4.08 TO PROVIDE THE DIMENSIONS OF THE CLEAR FLOOR
 SPACE DIAGRAMS SHOWN FOR THE FIXTURES- SEE PAGES 7.43-
 7.55 OF THE MANUAL.
  
 A) SHEETS A4.01- A4.08: PROVIDE TOILET AND BATHTUB GRAB
 BAR REINFORCEMENT DETAILS- PAGES 6.3- 6.16.
 B) A4.01- A4.08: PROVIDE THE CLEAR FLOOR SPACE
 DIMENSIONS FOR THE DIAGRAMS AT THE KITCHEN SINK AND
 APPLIANCES- PAGES 7.2- 7.6.
  
 5) FAILED. CIVIL PLANS NOT PROVIDED. NUMEROUS
 REFERENCES TO CIVIL PLANS HAVE BEEN MADE ON THE
 DRAWINGS HOWEVER PLANS HAVE NOT BEEN SUBMITTED. A
 COMPLETE PLUMBING REVIEW OF THE PROPOSED PROJECT CANNOT
 BE COMPLETED WITHOUT THE WATER AND SEWER CIVIL PLANS-
 SECTION 107.2.1 WPB. THE CIVIL PLANS SHALL SHOW THE
 LOCATIONS OF ALL POTABLE WATER BACKFLOW PREVENTERS
 WHICH ARE REQUIRED FOR THE NEW SERVICES TO THE
 BUILDINGS- SECTION 608.1 FBC P. PLEASE NOTE THAT FL.
 LICENSED PLUMBING CONTRACTORS SHALL OBTAIN SEPARATE
 PERMITS FOR INSTALLATION OF THE BACKFLOW PREVENTERS IN
 ACCORDANCE WITH SECTION 105.1 WPB AND SEC. 90-33 WPB
 CODE OF ORDINANCES. THE DEVICE SHALL BE TESTED AND
 CERTIFIED BY THE WPB UTILITIES DEPARTMENT PRIOR TO
 FINAL INSPECTION BY THE BUILDING DEPARTMENT. PLEASE
 CONTACT THE WPB UTILITIES CENTRAL OPERATIONS DEPT.AT
 561-822-2210 FOR FURTHER INFORMATION.
  
 PLEASE NOTE DUE TO A CHANGE IN PROCESS, THE BACKFLOW
 PERMIT IS REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF
 THE PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN
 APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 12) FAILED. P301, 302, 303, 304, 305 (SECTIONS 1 & 15):
 THE NOTES INDICATE THAT BATHROOM WET VENTS ARE BEING
 DESIGNED HOWEVER THE DRAWINGS SHOW LAVATORY SINK DRAINS
 CONNECTING BELOW THE SOIL STACKS WHICH IS
 NON-COMPLIANT- SECTION 912.1.1 FBC P. THE PLAN NOTES
 HAVE CHANGED TO INDICATE BOTH A 3-INCH BATHROOM GROUP
 DRAIN AND A 4-INCH TOILET RISER- WHICH IS IT 3 OR
 4-INCH? THERE ARE NO INDIVIDUAL TOILET RISERS.
  
 A) FOR CLARIFICATION, PLEASE IDENTIFY THE LOCATIONS OF
 PIPING SECTIONS (1-15) ON SHEET P301- SEC. 107.2.1 WPB.
  
 16) FAILED. NOT PROVIDED. PLEASE NOTE IN ACCORDANCE WTH
 SEC. 1101.2 RAINWATER FROM ROOFS AND STORM WATER FROM
 PAVED AREAS, YARDS, COURTS ABMND COURTYARDS SHALL DRAIN
 TO AN APPROVED PLACE OF DISPOSAL. PROVIDE A ROOF
 DRAINAGE PLAN AND ISOMETRIC DRAWING- SECTIONS 1101-
 1108 FBC P. PLEASE INCLUDE CALCULATIONS, AND CIVIL
 PLANS THAT SHOW ROOF DRAIN PIPE CONTINUATIONS TO THE
 STORM DRAINS SYSTEMS FOR THE SITE.
  
 17) FAILED. NO NOTES PROVIDED IN RESPONSE. PROVIDE
 IRRIGATION PLANS- SEE APPENDIX F PART 1.B FBC P. THE
 PLANS MAY BE DEFERRED AND SUBMITTED UNDER SEPARATE
 PERMIT.
  
 18) FAILED. NO NOTES PROVIDED IN RESPONSE. PLEASE BE
 ADVISED THAT GREASE INTERCEPTORS MAY BE REQUIRED FOR
 THE RETAIL SPACES IF COMMERCIAL COOKING EQUIPMENT WILL
 BE INSTALLED- SECTION 1003.3.1 FBC P.
  
 NEW COMMENTS:
  
 1) SHEETS P0.01 & P0.02: PLEASE PROVIDE ENLARGED
 FIXTURE SCHEDULES (NOT NOTES) SHOWING THE MAKES AND
 MODELS OF THE PUBLIC AND RESIDENTIAL USE PLUMBING
 FIXTURES- SEC. 107.2.1 & 107.3.5.1.3 WPB.
  
 2) P0.01: THE HWR LINE SHALL BE ROUTED TO THE COLD
 WATER INLET PIPE OF THE WATER HEATER AND THE COLD WATER
 INLET PIPE OR THE HOT WATER RETURN CONNECTION OF THE
 THERMOSTATIC MIXING VALVE- SEC. 607.2.2 FBC P.
  
 3) G1.01: PLEASE SHOW THE ACCESSIBLE ROUTE AND TRAVEL
 DISTANCE FROM THE MOST REMOTE BUSINESS/RETAIL OCCUPANCY
 TO THE PUBLIC BATHROOMS- SEC. 403.3 FBC P.
  
 4) P0.01 & P2.01: SHOW THE WATER HEATER DRAIN PAN LINES
 AND TERMINATION LOCATIONS- SEC- 504.7- 504.7.2 FBC P.
  
 5) PLEASE PROVIDE THE WATER HEATER EFFICIENCY DATA IN
 THE ENERGY/GAUGE COMPLIANCE REPORT- TABLE C404.2 FBC
 EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-07-19 Cont ID  
Sent By ccole Date 2021-07-19 Time 14:34 Rev Time 0.00
Received By ccole Date 2021-07-16 Time 17:26 Sent To  
Notes
2021-07-19 14:34:341ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21040844
 7/19/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET G.0.03: PROVIDE PLUMBING FIXTURE CALCULATIONS
 FOR THE PROPOSED RESIDENTIAL AND ACCESSORY BUSINESS
 OCCUPANCIES- TABLE 403.1 FBC P. PROVIDE A SCHEDULE THAT
 SHOWS THE REQUIRED AND PROVIDED NUMBER OF PLUMBING
 FIXTURES. THE CURRENT PLANS DO NOT INDICATE THE
 LOCATIONS OF THE BUSINESS OCCUPANCY PLUMBING FIXTURES.
 PLEASE REVISE THE PLANS TO SHOW THE LOCATIONS OF ALL
 REQUIRED FIXTURES AND PROVIDE PLUMBING PIPING PLANS AND
 RISER DRAWINGS- SECTION 107.2.1 WPB.
  
 2) WHERE PUBLIC BATHROOM FACILITIES ARE REQUIRED,
 PLEASE SHOW THE LOCATIONS ON THE FLOOR PLAN DRAWINGS
 AND PROVIDE SITE SPECIFIC FLOOR PLANS AND ELEVATION
 DRAWINGS THAT INCLUDE THE FOLLOWING ITEMS- FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSET FROM THE SIDE WALLS-
 SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOORS- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 3) WHERE DRINKING FOUNTAINS ARE REQUIRED PLEASE REFER
 TO SECTIONS 306, 307, AND 602 FBC ACC AND PROVIDE
 DRINKING FOUNTAIN INSTALLATION DETAILS AND ELEVATION
 VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT HEIGHTS,
 AND SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48 IN.
 CLEAR FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH TO
 THE FOUNTAIN- SECTION 602.2 FBC ACC, AND SHOW HOW THE
 LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE WITH
 SECTION 307.2 PROTRUSION LIMITS.
  
 4) G.0.03- REFER TO REQUIREMENT 7 FBC ACC: PLEASE
 INCLUDE THE REQUIRED COMPLIANCE WITH THE FAIR HOUSING
 ACT DESIGN MANUAL IN THE CODE INFORMATION, AND PROVIDE
 A LIST OF ALL UNITS THAT ARE COVERED UNDER THE ACT. THE
 INDIVIDUAL BATHROOMS SHALL BE DESIGNATED AS EITHER
 SPECIFICATION TYPE A OR B, AND ENLARGED DIMENSIONED
 DRAWINGS AND DETAILS IN ACCORDANCE WITH CHAPTER 7 OF
 THE MANUAL SHALL BE PROVIDED- SEE PAGE 7.34 OF THE
 MANUAL. THE USABLE KITCHEN AND BATHROOM DESIGN
 SPECIFICATION REQUIREMENTS ARE LISTED UNDER REQUIREMENT
 7 FBC ACC AND CHAPTERS 6 AND 7 OF THE MANUAL. BASED ON
 A LACK OF INFORMATION PROVIDED ON THE PLANS THE
 ACCESSIBILITY AND FAIR HOUSING REVIEWS ARE CURRENTLY
 STOPPED PENDING RESUBMITTAL OF REVISED PLANS.
  
 5) NUMEROUS REFERENCES TO CIVIL PLANS HAVE BEEN MADE ON
 THE DRAWINGS HOWEVER PLANS HAVE NOT BEEN SUBMITTED. A
 COMPLETE PLUMBING REVIEW OF THE PROPOSED PROJECT CANNOT
 BE COMPLETED WITHOUT THE WATER AND SEWER CIVIL PLANS-
 SECTION 107.2.1 WPB. THE CIVIL PLANS SHALL SHOW THE
 LOCATIONS OF ALL POTABLE WATER BACKFLOW PREVENTERS
 WHICH ARE REQUIRED FOR THE NEW SERVICES TO THE
 BUILDINGS- SECTION 608.1 FBC P. PLEASE NOTE THAT FL.
 LICENSED PLUMBING CONTRACTORS SHALL OBTAIN SEPARATE
 PERMITS FOR INSTALLATION OF THE BACKFLOW PREVENTERS IN
 ACCORDANCE WITH SECTION 105.1WPB AND SEC. 90-33 WPB
 CODE OF ORDINANCES. THE DEVICE SHALL BE TESTED AND
 CERTIFIED BY THE WPB UTILITIES DEPARTMENT PRIOR TO
 FINAL INSPECTION BY THE BUILDING DEPARTMENT. PLEASE
 CONTACT THE WPB UTILITIES CENTRAL OPERATIONS DEPT.AT
 561-822-2210 FOR FURTHER INFORMATION.
  
 6) P0.01: THE LOCATION OF THE THERMAL EXPANSION TANK IS
 NON-COMPLIANT FOR THE WATER HEATER SHOWN ON THE RIGHT
 SIDE OF THE DRAWING- SECTION 607.3 FBC P.
  
 7) P101, 102, 103: PLEASE PROVIDE DOMESTIC WATER RISER
 DRAWINGS FOR EACH OF THE FOUR BUILDINGS- SECTION
 107.3.5.1.3 WPB.
  
 8) P101, 102, 103: SHOW THE LOCATIONS OF MAIN SHUT OFF
 VALVES AT THE WATER RISERS TO THE UPPER FLOORS, AND AT
 THE ENTRANCES OF THE DWELLING UNITS- SECTION 606.1(4 &
 6) FBC P.
  
 9) P201, P301: PROVIDE THE DRAIN PIPE SIZES ON THE
 DRAWING- SECTION 710 FBC P.
  
 10) P301, 302, 303, 304, 305: PROVIDE DRAIN AND VENT
 PIPE SIZES ON THE DRAWINGS INCLUDING VENT STACKS, STACK
 VENTS, AND HEADERS- SECTIONS 904.1.2, 904.5, 906.1 FBC
 P.
  
 11) P301, 302, 303, 304, 305: THE WASHING MACHINE STACK
 VENT SHALL BE MINIMUM 3 IN. DIAMETER- SECTION 913.3 FBC
 P. PLEASE CORRECT THE NOTES ON THE DRAWING.
  
 12) P301, 302, 303, 304, 305 (SECTIONS 1 & 15): THE
 NOTES INDICATE THAT BATHROOM WET VENTS ARE BEING
 DESIGNED HOWEVER THE DRAWINGS SHOW LAVATORY SINK DRAINS
 CONNECTING BELOW THE SOIL STACKS WHICH IS
 NON-COMPLIANT- SECTION 912.1.1 FBC P.
  
 13) P301, P305 SECTION 14: THE KITCHEN SINK DRAIN SHALL
 NOT CONNECT TO THE WET VENT FOR THE BATHROOM- SECTIONS
 912.1 & 912.2 FBC P.
  
 14) P303 SECTION 5, P305 SECTION 15: DRAIN PIPE
 HORIZONTAL CONTINUATION SYMBOLS MISSING- SECTION 706.1
 FBC P.
  
 15) P3.01: IDENTIFY FUTURE FIXTURE DRAIN LOCATIONS AND
 INDICATE APPROVED CAPS WILL BE INSTALLED ON THE PIPE
 STUB OUTS- SECTION 704.4 FBC P.
  
 16) PROVIDE A ROOF DRAINAGE PLAN AND ISOMETRIC DRAWING-
 SECTIONS 1101- 1108 FBC P. PLEASE INCLUDE CALCULATIONS,
 AND CIVIL PLANS THAT SHOW ROOF DRAIN PIPE CONTINUATIONS
 TO THE STORM DRAINS SYSTEMS FOR THE SITE.
  
 17) PROVIDE IRRIGATION PLANS- SEE APPENDIX F PART 1.B
 FBC P. THE PLANS MAY BE DEFERRED AND SUBMITTED UNDER
 SEPARATE PERMIT.
  
 18) PLEASE BE ADVISED THAT GREASE INTERCEPTORS MAY BE
 REQUIRED FOR THE RETAIL SPACES IF COMMERCIAL COOKING
 EQUIPMENT WILL BE INSTALLED- SECTION 1003.3.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2022-06-09 Cont ID  
Sent By rmcphers Date 2022-06-09 Time 14:07 Rev Time 0.00
Received By rmcphers Date 2022-06-09 Time 14:07 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-07-20 Cont ID  
Sent By rmcphers Date 2021-07-20 Time 13:28 Rev Time 0.00
Received By rmcphers Date 2021-07-20 Time 13:28 Sent To  
Notes
2021-07-20 13:28:39SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-06-09 Cont ID  
Sent By rmcphers Date 2022-06-09 Time 14:23 Rev Time 0.00
Received By rmcphers Date 2022-06-09 Time 14:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-07-20 Cont ID  
Sent By rmcphers Date 2021-07-20 Time 13:48 Rev Time 0.00
Received By rmcphers Date 2021-07-20 Time 13:48 Sent To  
Notes
2021-07-16 09:56:01SIGNATURES FOR THE MECHANICAL SHEETS ARE APPROVED. ME

Review Stop Z ZONING
Rev No 2 Status F Date 2022-06-13 Cont ID  
Sent By Kdefranc Date 2022-06-13 Time 16:36 Rev Time 0.00
Received By kdefranc Date 2022-06-13 Time 16:34 Sent To  
Notes
2022-06-13 16:34:556/13/22 ? FAILED
  
 PREVIOUS REVIEW COMMENT TO BE ADDRESSED:
 THIS PROJECT REQUIRES A SITE PLAN APPROVAL. THIS
 PROJECT IS STILL WITHIN THE SITE PLAN APPROVAL PROCESS.
  
  
 KEVIE DEFRANC
 PLANNER ? PLANNING DIVISION
 [email protected]
 561-822-1449
  

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By awooten Date 2021-07-23 Time   Rev Time  
Received By   Date 2021-07-23 Time   Sent To  
Notes
2021-07-23 16:25:15*********************************ZONING REVIEW
 FAILED*********************************
  
 THIS PROJECT REQUIRES A SITE PLAN APPROVAL. THIS
 PROJECT IS STILL WITHIN THE SITE PLAN APPROVAL PROCESS.
  
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449