Plan Review Details - Permit 21040833
Plan Review Stops For Permit 21040833
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-05-17 Cont ID  
Sent By jwitmer Date 2021-05-17 Time 14:49 Rev Time 0.00
Received By jwitmer Date 2021-05-17 Time 14:44 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-04-27 Cont ID  
Sent By jwitmer Date 2021-04-27 Time 17:11 Rev Time 0.00
Received By jwitmer Date 2021-04-27 Time 15:45 Sent To  
Notes
2021-04-27 17:11:15TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-07-01 Cont ID  
Sent By jwitmer Date 2021-07-01 Time 11:11 Rev Time 0.00
Received By jwitmer Date 2021-07-01 Time 10:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-06-01 Cont ID  
Sent By jwitmer Date 2021-06-01 Time 11:57 Rev Time 0.00
Received By jwitmer Date 2021-06-01 Time 10:32 Sent To  
Notes
2021-06-01 11:52:06WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21040833
 ADD: 400 N, FLAGLER DR. SUITES: 1903 / 1904
 CONT: RICHARD MCDONALD CONSTRUCTION CO. INC.
 TEL: 561-795-4055
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. JUNE 1ST/ 2021
 ACTION: DENIED
  
 1) 3RD REQUEST. IT APPEARS THAT WORK IS BEING COMPLETED
 IN 2 UNITS 1903 & 1094. THE PROPOSED TENANT SPACES
 TRANSGRESS LEGAL BOUNDARY LINES BETWEEN THE CONDOMINIUM
 UNITS WHICH WILL NEED TO BE COMBINED TO FORM 'THE
 SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE
 COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY
 OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 2) SHEET A1.1.1: COMPLIED.
  
 3) COMPLIED. W. P. B. BUILDING DEPARTMENT HAS
 ALL (3) REQUIRED TEST ON FILE AT CITY HALL
 ON (F) DRIVE FLOOR UNDERLAYMENTS FOR:
  
 PROFLEX SUPER SIM 90 /TILE OR MARBLE
 IIC = 50 DB / 6 INCH SLAB P. T. / NO DROPPED CEILING /
 ASTM E-492
 STC = 52 DB / 6 INCH SLAB P. T./ NO DROPPED / CEILING
 ASTM E-90
 FLAME= 0 ASTM-E84
 SMOKE= 0 ASTM E-84
  
 4) COMPLIED.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-05-17 Cont ID  
Sent By jwitmer Date 2021-05-17 Time 15:42 Rev Time 0.00
Received By jwitmer Date 2021-05-17 Time 14:44 Sent To  
Notes
2021-05-17 15:20:34WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21040833
 ADD: 400 N, FLAGLER DR. SUITES: 1903 / 1904
 CONT: RICHARD MCDONALD CONSTRUCTION CO. INC.
 TEL: 561-795-4055
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. MAY 17TH/ 2021
 ACTION: DENIED
  
 1) 2ND REQUEST. IT APPEARS THAT WORK IS BEING COMPLETED
 IN 2 UNITS 1903 & 1094. THE PROPOSED TENANT SPACES
 TRANSGRESS LEGAL BOUNDARY LINES BETWEEN THE CONDOMINIUM
 UNITS WHICH WILL NEED TO BE COMBINED TO FORM 'THE
 SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE
 COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY
 OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 2) SHEET A1.1.1: COMPLIED.
  
 3) SHEET A1.1.2. UNDER THE HEADING FLOOR FINISHES LIST
 PORCELAIN TILE AS THE FLOOR FINISH. THE UNDERLAYMENT
 INDICATED IS PROFLEX MSC-90) PROFLEX MEGA-SOUND
 CONTROL). THE IIC AND STC RATINGS WERE SHOWN WITH
 TESTING ON A 8 INCH SLAB. THE TEST REPORTS SUBMITTED
 ARE FOR PROFLEX MSC WITH AN 8-INCH SLAB. THE SLAB
 THICKNESS FOR THIS BUILDING IS NOT KNOWN, THAT IS WHY
 WE REQUEST ALL TESTING REPORTS BE ON A 6-INCH SLAB. TO
 DATE WE HAVE NOT SEEN THIS PRODUCT TESTED FOR 6-INCH
 CONCRETE SLABS. PLEASE BE AWARE THAT PROFLEX DOES MAKE
 A UNDERLAYMENT THAT HAS BEEN TESTED ON A 6 INCH
 CONCRETE SLAB. THE CITY IS IN RECEIPT OF THIS PRODUCT
 AND IS IN F DRIVE, PRODUCT TESTING IS NOT REQUIRED
 SINCE WE HAVE IT ON FILE. IT JUST NEEDS TO BE NOTED ON
 THE PLANS JUST AS ANY OTHER PRODUCT THAT HAS SUBMITTED
 REPORTS AND RECORDED ON F DRIVE.
 PROFLEX SUPER SIM 90
 IIC 50
 STC 52
 FLAME 0
 SMOKE 0
  
 1ST ROUND OF COMMENTS. SHEET A1.1.2 FLOOR FINISH
 SCHEDULE INDICATES THE FLOOR FINISH IS CURRENTLY TBD/
 TO BE DETERMINED. UNTIL THE FLOOR FINISHES ARE KNOWN WE
 CANNOT SPECULATE ON IF THE UNDERLAYMENT WAS TESTED WITH
 THAT FINISH MATERIAL FOR ANY OF THE REQUIRED 3 TESTS,
 IIC, STC AND FLAME SPREAD. PLEASE NOTE THE CITY IS IN
 RECEIPT OF THE PROFLEX PRODUCT RCU 500/ 6-INCH SLAB/
 FOR USE WITH QUARRY TILE.
  
 FLOOR INSULATION (FBC-B 2020) FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) COMPLIED.
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-04-27 Cont ID  
Sent By jwitmer Date 2021-04-27 Time 17:14 Rev Time 0.00
Received By jwitmer Date 2021-04-27 Time 15:45 Sent To  
Notes
2021-04-27 17:14:04WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21040833
 ADD: 400 N, FLAGLER DR. SUITES: 1903 / 1904
 CONT: RICHARD MCDONALD CONSTRUCTION CO. INC.
 TEL: 561-795-4055
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. APRIL 27TH/ 2021
 ACTION: DENIED
  
 1) IT APPEARS THAT WORK IS BEING COMPLETED IN 2 UNITS
 1903 & 1094. THE PROPOSED TENANT SPACES TRANSGRESS
 LEGAL BOUNDARY LINES BETWEEN THE CONDOMINIUM UNITS
 WHICH WILL NEED TO BE COMBINED TO FORM 'THE SITE'. A
 'UNITY OF TITLE' SHALL BE RECORDED AT THE COUNTY
 COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY OF
 TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 2) SHEET A1.1.1:
 2A) UNDER THE HEADING OF PROJECT DATA THE DESIGN WIND
 PRESSURES ARE GIVEN FOR WINDOWS AND DOORS AS WORST
 CASE. POSITIVE + 63.3 PSF (ASSUMED VASD) AND THE
 NEGATIVE PRESSURES ARE GIVEN AT -84.7 (ASSUMED VASD).
 THE ENGINEERING EXPRESS SHEET IS HIGHLIGHTED EXPOSURE
 D, INTERIOR WALL ZONE 4, MEAN ROOF HEIGHT AT 220 MEAN
 ROOF HEIGHT 0F 220. THE WORST-CASE PRESSURES FOR WALL
 ZONE 4 WOULD BE +67.0/ - 67.0 @ 10 SQ. FT. SHOP DRAWING
 STAMP OF APPROVAL BY YOUR OFFICE. WHY THE DIFFERENCE IN
 REQUIRED PRESSURES? 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED. THE SUBMITTED PRODUCT APPROVALS CANNOT BE
 REVIEWED UNTIL THE UNTIL THE DISCREPANCY IN PRESSURES
 IS RESOLVED.
  
 2B) TRASH CHUTE LABELED 004AND DOOR TO TRASH CHUTE IS
 LABELED 106. THE DOOR SCHEDULE HAS THE DOOR 106 AS
 GREAT ROOM AND NO FIRE RATING. PLEASE SEE IN THE 2020
 FBC-B SECTION 713.13.3 CHUTE ACCESS ROOMS. OPENING
 PROTECTIVES OF NOT LESS THAN ? HRS. AND SELF-CLOSING OR
 AUTOMATIC CLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH 716.5.9.3.
  
 2C) PLEASE REVIEW DOORS IDENTIFIED AS 101 AND 110 ENTRY
 DOORS FROM THE ELEVATOR LOBBY. THE DOOR SCHEDULE DOES
 NOT SHOW THESES DOORS WITH A FIRE RATING. PLEASE REVIEW
 IN THE 2020 FBC-BUILDING CODE SECTION 3006.3 HOISTWAY
 PROTECTION AND WHICH METHOD OF PROTECTION IS GOING TO
 BE PROVIDED.
  
 3) SHEET A1.1.2 FLOOR FINISH SCHEDULE INDICATES THE
 FLOOR FINISH IS CURRENTLY TBD/ TO BE DETERMINED. UNTIL
 THE FLOOR FINISHES ARE KNOWN WE CAN NOT SPECULATE ON IF
 THE UNDERLAYMENT WAS TESTED WITH THAT FINISH MATERIAL
 FOR ANY OF THE REQUIRED 3 TESTS, IIC, STC AND FLAME
 SPREAD. PLEASE NOTE THE CITY IS IN RECEIPT OF THE
 PROFLEX PRODUCT RCU 500/ 6 INCH SLAB/ FOR USE WITH
 QUARRY TILE.
  
 FLOOR INSULATION (FBC-B 2020) FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) SHEET A1.1.2 THE WALL FINISH SCHEDULE E IS VERY
 VAGUE WHEN IT COMES TO THE BATHROOM & RESTROOM AREAS.
 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT
 IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
  
 4A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 4B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 4C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 4D) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS
 A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-05-21 Cont ID  
Sent By equinone Date 2021-05-21 Time 08:59 Rev Time 0.00
Received By equinone Date 2021-05-21 Time 08:45 Sent To  
Notes
2021-05-21 08:59:43SEE JAKE HEALY NOTES AND APPROVAL ON DRAWINGS. EQ

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-05-03 Cont ID  
Sent By equinone Date 2021-05-03 Time 16:52 Rev Time 0.00
Received By equinone Date 2021-05-03 Time 16:43 Sent To  
Notes
2021-05-03 16:52:53CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL
 OR THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE
 CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 1) PLEASE SHOW LOCATION OF ALL SMOKE DETECTORS (NEW AND
 EXISTING) FBC 2020
  
 2) PROVIDE COMPLIANCE: "NOT LESS THAN 90 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LUMINAIRES SHALL HAVE
 AN EFFICACY OF AT LEAST 45 LUMENS-PER-WATT OR SHALL
 UTILIZE LAMPS WITH AN EFFICACY OF NOT LESS THAN 65
 LUMENS-PER-WATT?.
 A NOTE WILL SUFFICE. FBC EC R404.1
  
 3) PLEASE PROVIDE A LIST OF ELECTRICAL SYMBOLS FOR THE
 ELECTRICAL DRAWINGS (FOR EXAMPLE NOT CLEAR WHAT
 RECEPTACLES LABELED CTOP ARE) FBC 107
  
 4) PERMIT APPLICATION WAS SUBMITTED AFTER JAN 2021 SO
 THE NEC 2017 AND FBC 2020 CODES APPLY. PLEASE UPDATE
 YOUR CODE REFERENCES TO REFLECT THE NEW CODES IN
 EFFECT. FBC 107
  
 5) ARE ALL RECEPTACLES AND LIGHTS SHOWN NEW?
  
  
  
 ENRIQUE QUINONEZ PE
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-04-23 Cont ID  
Sent By pleduc Date 2021-04-23 Time   Rev Time 0.00
Received By pleduc Date 2021-04-23 Time 15:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-06-01 Time 11:57 Rev Time 0.00
Received By aoliver Date 2021-05-27 Time 14:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-24 Cont ID  
Sent By medwards Date 2021-05-24 Time 08:00 Rev Time 0.00
Received By medwards Date 2021-05-12 Time 07:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-04 Cont ID  
Sent By lmarchan Date 2021-05-04 Time 09:43 Rev Time 0.00
Received By lmarchan Date 2021-04-21 Time 16:38 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-05-17 Cont ID  
Sent By jwitmer Date 2021-05-17 Time 14:45 Rev Time 0.00
Received By jwitmer Date 2021-04-27 Time 15:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-05-24 Cont ID  
Sent By medwards Date 2021-05-24 Time 07:56 Rev Time 0.00
Received By medwards Date 2021-05-24 Time 07:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-05-03 Cont ID  
Sent By medwards Date 2021-05-03 Time 10:12 Rev Time 0.00
Received By medwards Date 2021-05-03 Time 10:04 Sent To  
Notes
2021-05-03 10:14:33SHEET M1.1: PLEASE SHOW THE RETURN AIR PATH FROM EACH
 BEDROOM BACK TO THE AHU'S. FBC M 601.6
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-05-03 Cont ID  
Sent By tklarge Date 2021-05-03 Time 09:47 Rev Time 0.00
Received By tklarge Date 2021-05-03 Time 09:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-07-01 Cont ID  
Sent By jwitmer Date 2021-07-01 Time 11:11 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-05-24 Cont ID  
Sent By medwards Date 2021-05-24 Time 07:59 Rev Time 0.00
Received By medwards Date 2021-05-24 Time 07:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-05-03 Cont ID  
Sent By medwards Date 2021-05-03 Time 10:16 Rev Time 0.00
Received By medwards Date 2021-05-03 Time 10:16 Sent To  
Notes
***NONE***