| 2021-05-25 13:42:02 | ROOF PRODUCT APPROVALS SUBMITTAL, SECOND BUILDING |
| | REVIEW COMMENTS. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | SUBMITTAL #21040752 |
| | |
| | 1- OK. |
| | |
| | 2- ROOF TILE AND ROOF TILE ADHESIVE PRODUCT APPROVALS |
| | SUBMITTED. CLEARLY MARK ADHESIVE PADDY SIZE AS REQUIRED |
| | BY CITY POLICY FOR ALL ROOFING PERMITS TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC R301.2.1 |
| | FBC-RESIDENTIAL. |
| | NOTE: THIS BUILDING IS LOCATED IN EXPOSURE "D". SEE |
| | STRUCTURAL DRAWING S-2. COORDINATE WITH DESIGNER OF |
| | RECORD TO AVOID CONFLICTS/DELAYS. |
| | |
| | RESPONSE: |
| | ROOF TILE NOA 18-0509.17 SUBMITTED WAS MARKED ON PAGE 5 |
| | OF 9 WITH TILE BOND PADDY OF 13.9 GRAMS. THE MINIMUM |
| | ATTACHMENT RESISTANCE FOR THIS PADDY SIZE IS 31.3 |
| | (FT-LBF). THIS BUILDING IS LOCATED IN EXPOSURE "D". SEE |
| | STRUCTURAL DRAWING S-2. USING TABLE 2A OF THE FRSA |
| | MANUAL (5TH EDITION REVISED) AS A REFERENCE I FOUND |
| | THAT FIELD TILE REQUIRES A MINIMUM OF 39.4 (FT-LBF) |
| | JUST FOR THE FIELD TILE. THEREFORE, SELECTED PADDY SIZE |
| | DOESN'T WORK. NEED TO SELECT A PADDY SIZE THAT WILL |
| | WORK FOR ALL ROOF ZONES, INCLUDING THE PERIMETER AND |
| | CORNER ROOF ZONES. |
| | R301.2.1 FBC-RESIDENTIAL. |
| | |
| | 3- DESIGNER OF RECORD TO REVIEW/APPROVE ABOVE PRODUCT |
| | APPROVAL L ONCE IT IS REVISED. |
| | SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |
| | REMAINDER: |
| | THIS PROJECT WAS APPROVED WITH PROVISO. PLEASE PROVIDE |
| | ALL THE REQUIRED INFORMATION FOR REVIEW PRIOR TO |
| | INSTALLATION TO AVOID CONFLICTS/DELAYS. SEE COPY OF |
| | PROVISO BELOW. |
| | |
| | |
| | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-PROVIDE PRODUCT APPROVAL FOR: |
| | A)ROOF TILE AND SPECIFY FASTENING. IF USING SCREWS, |
| | SPECIFY SIZE & NUMBER. |
| | B)ROOF TILE ADHESIVE IF SPECIFIED ABOVE. |
| | C)FLAT ROOF AS SHOWN ON PLANS. AND, CLEARLY MARK WHICH |
| | APPROVED ASSEMBLY IS GOING TO BE INSTALLED. NOTE: RAS |
| | 117 CALCULATIONS IF REQUIRED. |
| | D)ENTRY DOOR. |
| | E)LAUNDRY DOOR. |
| | F)SLIDING GLASS DOORS. |
| | G)FIXED WINDOWS. |
| | H)HORIZONTAL SLIDING WINDOWS. |
| | I)CASEMENT WINDOWS. |
| | I)OVERHEAD GARAGE DOOR. |
| | |